1. fire control panels

Transkript

1. fire control panels
2
0
P R O D U C T C A T A L O G U E 06
The
Group
www.detectomat.com
contents
page
1.
1.1
1.2
1.3
1.4
1.5
1.6
1.7
fire control panels
detect 3004 fire control panel and accessories ...............................................................................................................4-11
detect 3016 fire control panel and accessories .............................................................................................................12-17
detect 3004/3016 panel accessories ............................................................................................................................18-23
network components ....................................................................................................................................................24-28
programming tools and software ...................................................................................................................................29-30
visualization .................................................................................................................................................................31-32
conventional panels ...........................................................................................................................................................32
2.
2.1
2.2
2.3
detectors
loop3000 – adressable detectors..................................................................................................................................33-39
CT 3000 – conventional detectors .................................................................................................................................39-42
detector accessoires.....................................................................................................................................................43-48
3.
3.1
3.2
3.3
manual call points
loop3000 – addressable manual call points ..................................................................................................................49-52
CT 3000 – conventional call points ...............................................................................................................................52-54
accessoires for manual call points......................................................................................................................................55
4.
loop3000 modules ......................................................................................................................................................56-58
5.
loop3000 – radio extension ........................................................................................................................................59-61
6.
6.1
6.2
6.3
6.4
6.5
6.6
special detectors
aspiration smoke detectors ...........................................................................................................................................62-65
accessoires smoke detectors ........................................................................................................................................66-69
infrared beam detectors................................................................................................................................................70-71
sensor cable detectors .......................................................................................................................................................72
flame detectors ............................................................................................................................................................73-75
intrisically safe detectors ..............................................................................................................................................75-78
7.
home smoke detectors ...............................................................................................................................................79-82
8.
8.1
8.2
signalling devices
signalling devices for loop3000 ....................................................................................................................................83-85
conventional signalling devices .....................................................................................................................................85-90
9.
door magnets and accessoires...................................................................................................................................91-95
10.
detector testing devices .............................................................................................................................................96-97
11.
Article index .............................................................................................................................................................98-103
12.
Terms & Conditions of Sale detectomat GmbH .......................................................................................................104-106
Produktaktualisierungen finden Sie
laufend unter www.detectomat.de
Stand August 2006
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 31973
fire control panel
detect 3004
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2 slots for fire brigade and network interface
128 programmable detector zones
up to 4 x 126 loop3000 components
up to 16 inputs for conventional detector zones
maximum loop length 3.000 m (using installation cable
IY(St)Y 2 x 0,8 mm)
monitored loop operation with detection system loop3000
facility for integration of fire brigade interface, display panel,
transmission- and key-depot adapter interface
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V / 90 mA)
monitored signal transmitter 400 mA
2 RS 232 interfaces for personal computer, printer, modem,
building management system
network compatible via bitbus interface up to 32 fire control
panels controls or additional 63 bitbus components
operation and event memory for 500 messages (first in first
out principle)
possibility via mounting panel to integrate a protocol-printer and
LED indicator modules for zone alarm and zone fault indication
option to equip a redundant main board processor (second CPU)
power supply 72 W and monitored battery condition
storing space for two batteries 12 V / 26 Ah
technical specification
input voltage
frequency
operation voltage
power supply
emergency power
quiesent current
alarm current
interfaces
display
zone LED´s
sounder output
external user output
relay output
open collector output
operation temperature
humidity
protection class
housing color
front color
material
weight
dimensions (H x W x D)
approvals
Microprocessor controlled modular fire control panel DIN EN 54,
VDE 0833 and VdS approved. For use with the loop3000 fire
detection system components.
•
•
•
display- and control panel DIN EN 54 part 2
4 alphanumeric lines LCD- display with backlight
2 slots for detector interface boards (max. to equip up to 4 loops
or 16 conventional fire zones)
complies with
230 V AC (-15 % / +10%)
50 / 60 Hz
21,0 up to 29,2 V DC
72 W
max. 2 x 12 V / 26 Ah
86 mA
146 mA
2 x RS 232/422 Bitbus (option)
LCD 4 x 20 characters
poss. for up to 48 zone indicators
24 V DC / 400 mA monitored
24 V DC / 800 mA
3 change over 250 V / 5 A
9 open collector 30 V DC / 90 mA
-5°C up to +40°C
up to 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
12,5 kg
490 mm x 420 mm x 210 mm
VdS: G 203068, S 295054, LPCB,
GOST, Hungary, Bulgaria, Lithuania,
Czech Republik, Ukrain, Slovakia,
Slovenia, Spain, Switzerland, Belgium
EN 54 - 2
remarks: if you use a printer 30106 you can use only 18 ah- or
smaller batteries
4
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 31972
fire control panel shallow
detect 3004 - shallow
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2 slots for fire brigade and network interface
128 programmable detector zones
up to 4 x 126 loop3000 components
up to 16 inputs for conventional detector zones
maximum loop length 3.000 m (using installation cable
IY(St)Y 2 x 0,8 mm)
monitored loop operation with detection system loop3000
facility for integration of fire brigade interface, display panel,
transmission- and key-depot adapter interface
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V / 90 mA)
monitored signal transmitter 400 mA
additional external output 24V / 800mA
2 RS 232 interfaces for personal computer, printer, modem,
building management system
network compatible via bitbus interface up to 32 fire control
panels or additional 63 bitbus components
operation and event memory for 500 messages (first in first
out principle)
possibility via mounting panel to integrate a protocol-printer and
LED indicator modules for zone alarm and zone fault indication
option to equip a redundant main board processor (second CPU)
power supply 72 W and monitored battery condition
storing space for two batteries 12 V / 12 Ah
technical specification
input voltage
frequency
operation voltage
power supply
emergency power
quiesent current
alarm current
interfaces
display
zone LED´s
sounder output
external user output
relay output
open collector output
operation temperature
humidity
protection class
housing color
front color
material
weight
dimensions (H x W x D)
approvals
Microprocessor controlled modular fire control panel, shallow
version, DIN EN 54, VDE 0833 and VdS approved. For use with
the loop3000 fire detection system components.
complies with
•
•
•
display- and control panel DIN EN 54 part 2
4 alphanumeric lines LCD- display with backlight
2 slots for detector interface boards (max. to equip up to 4 loops
or 16 conventional fire zones)
230 V AC (-15 % / +10%)
50 / 60 Hz
21,0 up to 29,2 V DC
72 W
max. 2 x 12 V / 26 Ah
86 mA
146 mA
2 x RS 232/422 Bitbus (option)
LCD 4 x 20 characters
poss. for up to 48 zone indicators
24 V DC / 400 mA monitored
24 V DC / 800 mA
3 change over 250 V / 5 A
9 open collector 30 V DC / 90 mA
-5°C up to +40°C
up to 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
12,5 kg
490 mm x 420 mm x 150 mm
VdS: S 295054, LPCB, GOST,
Hungary, Bulgaria, Lithuania, Czech
Republik, Ukrain, Slovakia, Slovenia,
Spain, Switzerland, Belgium
EN 54 - 2
remarks: usable as master remote and control panel in a network with
the language kit LK ABF, this version of the remote and control panel
offers space for LED indicators, printer, separate power supply etc
5
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 32049
fire control panel 19" rack mount
detect 3004-19"
•
•
•
•
•
network compatible via bitbus interface up to 32 fire panel
controls or additional 63 bitbus components
operation and event memory for 500 messages
(first in first out principle)
suitable for 19" rack mount
option to equip a redundant main board processor (second CPU)
power supply 72 W and monitored battery condition
technical specification
Microprocessor controlled modular fire control panel,
19" rack mount version, DIN EN 54, VDE 0833 and VdS approved.
For use with the loop3000 fire detection system components.
•
•
•
display- and control panel DIN EN 54 part 2
4 alphanumeric lines LCD- display with backlight
2 slots for detector interface boards (max. to equip up to 4 loops
or 16 conventional fire zones)
2 slots for fire brigade and network interface
128 programmable detector zones
up to 4 x 126 loop3000 components
up to 16 inputs for conventional detector zones
maximum loop length 3.000 m (using installation cable
IY(St)Y 2 x 0,8 mm)
monitored loop operation with detection system loop3000
possibility for integration of fire brigade interface, display panel,
transmission- and key-depot adapter interface
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V / 90 mA)
monitored signal transmitter 400 mA
additional external output 24V / 800mA
2 RS 232 interfaces for personal computer, printer, modem,
building management system
•
•
•
•
•
•
•
•
•
•
•
•
art. 31974
language kit German
language kit integrates German software, German description,
German labelling
art. 31975
language kit English
language kit integrates English software, English description,
English labelling, additional languages available on request
input voltage
frequency
operation voltage
power supply
emergency power
quiesent current
alarm current
interfaces
display
zone LED´s
sounder output
external user output
relay output
open collector output
operation temperature
humidity
protection class
front color
dimensions (H x W x D)
approvals
complies with
230 V AC (-15 % / +10 %)
50 / 60 Hz
21,0 up to 29,2 V DC
72 W
max. 2 x 12 V / 26 Ah
86 mA
146 mA
2 x RS 232/422 Bitbus (option)
LCD 4 x 20 characters
poss. for up to 48 zone indicators
24 V DC / 400 mA monitored
24 V DC / 800 mA
3 change over 250 V / 5 A
9 open collector 30 V DC / 90 mA
-5°C up to +40°C
up to 95 %
IP 30
tele grey, RAL 7046
6HE x 19" x 150 mm
VdS: G 203068, S 295054, LPCB,
GOST, Hungary, Bulgaria, Lithuania,
Czech Republik, Ukrain, Slovakia,
Slovenia, Spain, Switzerland, Belgium
EN 54 - 2
remarks:
• the panel is designed to be mounted in a 19"- rack
• the power pack is separately mounted in the 19"- rack
• additional space is required for battery storage
LK 3004 D
remarks: it is essential to specify the language kit when ordering
LK 3004 GB
remarks: it is essential to specify the language kit when ordering
6
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 31817
1-loop interface
DLI 3240 X1-1L
•
•
•
•
•
•
•
•
•
maximum loop length 3.000 m (installation cable IY(St)Y 2 x 0,8 mm)
all loop3000 components can be addressed automatically
manual addressable with EasyCheck 3000 (31482)
two - wire - loop
8 freely programmable open collector outputs
3 open collector outputs 30 V DC / 90 mA for alarm and fault
loop voltage 32 V DC, loop current 100 mA
RS 232 interface for additional data monitoring
slot for optional redundant processor
technical specification
operation voltage
quiesent current
alarm current
interfaces
open collector output
operation temperature
weight
dimensions (H x W x D)
picture similar
to plug in to the detect 3004 fire control panel for
max. 126 loop3000 components
art. 30209
2-loop interface
20 up to 28 V DC
40 mA
max. 100 mA
RS 232
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
remarks: use the current version of the loop calculator to determin
the maximum number of loop devices/components and mix
DLI 3240 X1-2L
•
•
•
•
•
•
•
•
•
maximum loop length 3.000 m (installation cable IY(St)Y 2 x 0,8 mm)
all loop3000 components can be addressed automatically
manual addressable with EasyCheck 3000 (31482)
two - wire - loop
8 freely programmable open collector outputs
3 open collector outputs 30 V DC / 90 mA for alarm and fault
loop voltage 32 V DC, loop current 100 mA per loop
RS 232 interface for additional data monitoring
slot for optional redundant processor
technical specification
operation voltage
quiesent current
alarm current
interfaces
open collector output
operation temperature
weight
dimensions (H x W x D)
to plug in to the detect 3004 fire control panel for
max. 2x126 loop3000 components
20 up to 28 V DC
40 mA
max. 2 x 100 mA
RS 232
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
remarks: use the current version of the loop calculator to determin
the maximum number of loop devices/components and mix
7
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 32098
2-loop interface active
DLI 3240 P X1
•
•
•
•
•
•
•
•
•
maximum loop length 3.000 m (installation cable IY(St)Y 2 x 0,8 mm)
all loop3000 components can be addressed automatically
manual addressable with EasyCheck 3000 (31482)
two - wire - loop
8 freely programmable open collector outputs
3 open collector outputs 30 V DC / 90 mA for alarm and fault
loop voltage 32 V DC, loop current 140 mA per loop
RS 232 interface for additional data monitoring
slot for optional redundant processor
technical specification
operation voltage
quiesent current
alarm current
interfaces
open collector output
operation temperature
weight
dimensions (H x W x D)
picture similar
to plug in to the detect 3004 fire control panel for
max. 2x126 loop3000 components
art. 31312
2-loop interface redundant
20 up to 28 V DC
40 mA
max. 2 x 140 mA
RS 232
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
remarks: use the current version of the loop calculator to determin
the maximum number of loop devices/components and mix
CP DLI 3240 X1-R
•
•
•
•
•
•
•
•
•
maximum loop length 3.000 m (installation cable IY(St)Y 2 x 0,8 mm)
all loop3000 components can be addressed automatically
manual addressable with EasyCheck 3000 (31482)
two - wire - loop
8 freely programmable open collector outputs
3 open collector outputs 30 V DC / 90 mA for alarm and fault
loop voltage 32 V DC, loop current 100 mA per loop
RS 232 interface for additional data monitoring
redundant second processor for emergency operation
technical specification
operation voltage
quiesent current
alarm current
interfaces
open collector output
operation temperature
weight
dimensions (H x W x D)
to plug in to the detect 3004 fire control panel for
max. 2x126 loop3000 components
20 up to 28 V DC
40 mA
max. 2 x 100 mA
RS 232
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
remarks: use the current version of the loop calculator to determin
the maximum number of loop devices/components and mix
8
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 30210
conventional interface for 8 fire zones
CP CLI X1
to plug in to the detect 3004 fire control panel for max. 8
conventional fire zones
•
•
•
•
maximum 25 conventional detectors per fire zone connectable
8 freely programmable open collector outputs 30 V DC / 90 mA
3 open collector outputs 30 V DC / 90 mA
slot for optional redundant processor
technical specification
operation voltage
alarm current
open collector output
operation temperature
weight
dimensions (H x W x D)
art. 30927
ground circuit module
20 up to 28 V DC
85 mA + 50 mA per zone output
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
CP EM
to plug in to the detect 3004 fire control panel for monitoring of
the galvanic separation between ground potential and all secundary
voltages e.g. fire zone, monitoring outputs
technical specification
operation voltage
quiesent current
open collector output
operation temperature
front color
material
weight
dimensions (H x W x D)
art. 30088
LED indicator modul
18 up to 30 V DC
7 mA
fault output voltage: max 29 V
fault output current: max. 0,1 A
-5°C up to +50°C
green
polyamid PA6.6
50 g
59 mm x 20 mm x 60 mm
CP ZM 8
two LED indicators for 8 zones per modul to plug into the fire control
panel detect 3004 for zone alarm and zone fault indication
•
•
1 red and 1 yellow LED per fire zone
8 fire zones on 1 modul
technical specification
alarm current
operation temperature
dimensions (H x W)
3 mA per zone
-5°C up to +40°C
93 mm x 80 mm
remarks: a maximum of 6 LED indicator modules are available,
an adapter plate 30386 is required for more than 16 zones
9
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 30386
adapter for LED indicator modul
CP ADB 48
to plug into the detect 3004 fire conrol panel more than two LED
indicator modules 30088
technical specification
operation temperature
dimensions (H x W)
-5°C up to +40°C
55 mm x 108 mm
remarks: a maximum of 6 alarm indicator zones available,
adapter plate 30386 irequired after 16 zones
art. 31946
mounting plate
expansion mounting plate to plug in to the detect 3004 fire control
panel front for up to 6 LED indicator modules or / and protocol printer
including front foil
•
•
•
mounting plate for maximum 6 LED indicator modules
provides facility for protocol printer 30099 or 30106
zones can be identified by labelling
art. 30111
CP MP 3004
technical specification
operation temperature
dimensions (H x W)
-5°C up to +40°C
228 mm x 365 mm
remarks: installation into the detect 3004 fire control
panel possible
extinguishing control modul
CP ETB X1
plug in extinguishing control module for the detect 3004 fire panel
to control one extinguishing area
•
•
•
direct activation of the extinguishing area valves
4 monitored control lines for signal transmitter and solenoid valves
activation from loop or conventional interface
technical specification
operation voltage
quiesent current
alarm current
sounder output
external user output
operation temperature
dimensions (H x W x D)
20 up to 28 V DC
45 mA
60 mA + 1 A per output
4 x 24 V DC / 1 A monitored
4 x 24 V DC / 1 A monitored
-5°C up to +40°C
140 mm x 140 mm x 20 mm
remarks: an additional extinguishing panel is not necessary
10
www.detectomat.com
1. fire control panels
1.1 detect 3004 fire control panel and accessories
art. 31318
universal expansion housing
UZG-1
provides additional space for ancilary components
•
•
sheet steal housing compatible with fire control panel detect 3004
lock for door
technical specification
protection class
housing color
front color
material
weight
dimensions (H x W x D)
art. 30113
redundant main board processor
to plug in to the detect 3004 fire panel to duplicate the main
board processor
CP CPU X1-R
technical specification
approvals
•
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
5 kg
490 mm x 420 mm x 210 mm
VdS G 203 068
takes over the control in case of CPU-failure
11
www.detectomat.com
1. fire control panels
1.2 detect 3016 fire control panel and accessories
art. 31989
fire control panel
detect 3016
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
additional two extension with 2+1 slots connectable
(max. to equip up to 16 loops or 64 conventional fire zones)
2 slots for fire brigade and network interface
192 programmable detector zones
up to 16 x 126 loop3000 components
up to 64 conventional fire zones
maximum loop length 3.000 m (using installation cable
IY(St)Y 2 x 0,8 mm)
monitored loop operation with detection system loop3000
integrated fire brigade interface for control of display panel,
transmission- and key-depot adapter interface
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V / 90 mA)
monitored signal transmitter 400 mA
2 additional external outputs 24V / 800mA
2 RS 232 interfaces for personal computer, printer, modem,
building management system
network compatible via bitbus interface up to 32 fire control
panels or additional 63 bitbus components
operation and event memory for 500 messages (first in first
out principle)
possibility via mounting panel to integrate a protocol-printer and
LED indicator modules for zone alarm and zone fault indication
option to equip a redundant main board processor (second CPU)
power supply 192 W and monitored battery condition
storing space for two batteries 12 V / 45 Ah
technical specification
input voltage
frequency
operation voltage
power supply
emergency power
interfaces
display
zone LED´s
sounder output
external user output
relay output
open collector output
operation temperature
humidity
protection class
housing color
front color
material
weight
dimensions (H x W x D)
approvals
Microprocessor controlled modular fire control panel DIN EN 54, V
DE 0833 and VdS approved. For use with the loop3000 fire detection
system components.
•
•
•
display- and control panel DIN EN 54 part 2
4 alphanumeric lines LCD- display with backlight
the basic version offers 5 slots for detector interface boards
and 1 slot for OC - boards
complies with
230 V AC (-15 % / +10%)
50 / 60 Hz
21,0 up to 29,2 V DC
192 W
max. 2 x 12 V / 45 Ah
2x RS 232/422 Bitbus (option)
LCD 4 x 20 characters
poss. for up to 192 zone indicators
24 V DC / 400 mA monitored
2 x 24 V DC / 800 mA
3 change over 250 V / 5 A
9 open collector 30 V DC / 90 mA
-5°C up to +40°C
max. 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
30,0 kg
750 mm x 600 mm x 240 mm
VdS: G 203067, S 295054, LPCB,
GOST, CCC, Hungary, Bulgaria,
Lithuania, Czech Republik, Ukrain,
Slovakia, Slovenia, Spain,
Switzerland, Belgium
EN 54 - 2
remarks: if you use a printer 30106 you can use only up to 5 LED
indicator modules for 160 fire zones
12
www.detectomat.com
1. fire control panels
1.2 detect 3016 fire control panel and accessories
art. 31990
fire control panel 19" rack mount
detect 3016-19"
•
•
•
•
•
•
operation and event memory for 500 messages
(first in first out principle)
suitable for 19" rack mount
possibility via mounting panel to integrate a protocol-printer and
LED indicator modules for zone alarm and zone fault indication
option to equip a redundant main board processor (second CPU)
power supply 192 W and monitored battery condition
usable for two batteries 12 V / up to 65 Ah
technical specification
Microprocessor controlled modular fire control panel,
19" rack mount version, DIN EN 54, VDE 0833 and VdS approved.
For use with the loop3000 fire detection system components.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
display- and control panel DIN EN 54 part 2
4 alphanumeric lines LCD- display with backlight
the basic version offers 5 slots for detector interface boards and
1 slot for OC - boards
additional two extension with 2+1 slots connectable
(max. to equip up to 16 loops or 64 conventional fire zones)
2 slots for fire brigade and network interface
192 programmable detector zones
up to 16 x 126 loop3000 components
up to 64 conventional fire zones
maximum loop length 3.000 m (using installation cable
IY(St)Y 2 x 0,8 mm)
monitored loop operation with detection system loop3000
integrated fire brigade interface for control of display panel,
transmission- and key-depot adapter interface
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V / 90 mA)
monitored signal transmitter 400 mA
2 additional external outputs 24V / 800mA
2 RS 232 interfaces for personal computer, printer, modem,
building management system
network compatible via bitbus interface up to 32 fire control
panels or additional 63 bitbus components
art. 31991
language kit German
language kit integrates German software, German description,
German labelling
art. 31992
language kit English
language kit integrates English software, English description,
English labelling, additional languages available on request
input voltage
frequency
operation voltage
power supply
emergency power
interfaces
display
zone LED´s
sounder output
external user output
relay output
open collector output
operation temperature
humidity
protection class
front color
material
weight
dimensions (H x W x D)
approvals
complies with
230 V AC (-15 % / +10%)
50 / 60 Hz
21,0 up to 29,2 V DC
192 W
max. 2 x 12 V / 45 Ah
2x RS 232/422 Bitbus (option)
LCD 4 x 20 characters
poss. for up to 192 zone indicators
24 V DC / 400 mA monitored
2 x 24 V DC / 800 mA
3 change over 250 V / 5 A
9 open collector 30 V DC / 90 mA
-5°C up to +40°C
max. 95 %
IP 30
tele grey, RAL 7046
sheet steel
20 kg
6 HE x 19"
VdS: G 203067, S 295054, LPCB,
GOST, CCC, Hungary, Bulgaria,
Lithuania, Czech Republik, Ukrain,
Slovakia, Slovenia, Spain,
Switzerland, Belgium
EN 54 - 2
remarks:
• the panel is designed to be mounted in a 19"- rack
• the power pack is separately mounted in the 19"- rack
• additional space is required for battery storage
LK 3016 D
remarks: it is essential to specify the language kit when ordering
LK 3016 GB
remarks: it is essential to specify the language kit when ordering
13
www.detectomat.com
1. fire control panels
1.2 detect 3016 fire control panel and accessories
art. 30201
2-loop interface redundant
DLI 3240 X2-R
to plug in to the detect 3016 fire control panel for max. 2 x 126
loop3000 components
•
•
•
•
•
•
•
•
•
maximum loop length 3.000 m (installation cable IY(St)Y 2 x 0,8 mm)
all loop3000 components can be addressed automatically
manual addressable with EasyCheck 3000 (31482)
two - wire - loop
8 freely programmable open collector outputs
3 open collector outputs 30 V DC / 90 mA for alarm and fault
oop voltage 32 V DC, loop current 100 mA per loop
RS 232 interface for additional data monitoring
redundant board processor unit to duplicate the functions
technical specification
operation voltage
quiesent current
alarm current
interfaces
open collector output
operation temperature
weight
dimensions (H x W x D)
20 up to 28 V DC
40 mA
max. 2 x 100 mA
RS 232
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
remarks: use the current version of the loop calculator to determin
the maximum number of loop devices/components and mix
art. 32099
2-loop interface active, redundant
DLI 3240 P X2-R
to plug in to the detect 3016 fire control panel for max. 2 x 126
loop3000 components
•
•
•
•
•
•
•
•
•
maximum loop length 3.000 m (installation cable IY(St)Y 2 x 0,8 mm)
all loop3000 components can be addressed automatically
manual addressable with EasyCheck 3000 (31482)
two - wire - loop
8 freely programmable open collector outputs
3 open collector outputs 30 V DC / 90 mA for alarm and fault
loop voltage 32 V DC, loop current 140 mA per loop
RS 232 interface for additional data monitoring
redundant board processor unit to duplicate the functions
technical specification
picture similar
operation voltage
quiesent current
alarm current
interfaces
open collector output
operation temperature
weight
dimensions (H x W x D)
approvals
20 up to 28 V DC
40 mA
max. 2 x 140 mA
RS 232
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
VdS: G 203067
remarks: use the current version of the loop calculator to determin
the maximum number of loop devices/components and mix
14
www.detectomat.com
1. fire control panels
1.2 detect 3016 fire control panel and accessories
art. 30096
conventional interface redundant 8 fire zones
CP CLI X2-R
to plug in to the detect 3016 fire control panel for max. 8 conventional
fire zones
•
•
•
•
maximum 25 conventional detectors per fire zone connectable
8 freely programmable open collector outputs 30 V DC / 90 mA
3 open collector outputs 30 V DC / 90 mA
redundant board processor unit to duplicate the functions
technical specification
operation voltage
quiesent current
alarm current
open collector output
operation temperature
weight
dimensions (H x W x D)
art. 30097
extension module
20 up to 28 V DC
60 mA
85 mA + 50 mA per zone output
11 open collector 30 V DC / 90 mA
-5°C up to +40°C
200 g
140 mm x 140 mm x 30 mm
CP ECB
to expand the detect 3016 fire control panel mother board
•
3 slots for plug in 2 additional loop-/conventional interfaces
and 1 alarm module
technical specification
operation temperature
-5°C up to +40°C
remarks: maximum up to 2 units per detect 3016 fire control
panel usable
art. 30098
LED indicator modul
CP ZM 32
two LED indicators for 32 zones per modul to plug into the fire control
panel detect 3016 for zone alarm and zone fault indication
•
•
1 red and 1 yellow LED per fire zone
32 fire zones on 1 modul
technical specification
alarm current
operation temperature
dimensions (H x W)
3 mA per zone
-5°C up to +40°C
108 mm x 193 mm
remarks: maximum of 6 LED indicator modules
15
www.detectomat.com
1. fire control panels
1.2 detect 3016 fire control panel and accessories
art. 31947
mounting plate
expansion mounting plate to plug in to the detect 3016 fire control
panel front for up to 6 LED indicator modules or / and protocol printer
including front foil
•
•
•
mounting plate for maximum 6 LED indicator modules
provides possibility for protocol printer 30099 or 30106
zones can be identified by labelling
CP MP 3016
technical specification
operation temperature
dimensions (H x W)
-5°C up to +40°C
400 mm x 483 mm
remarks: laterly installation into the detect 3016 fire control
panel possible
art. 30164
mounting panel
expansion mounting front to add 19" components for the 19" cabinate
MP-1
technical specification
material
dimensions (H x W)
sheet steel
878 mm x 485 mm
remarks: one mounting plate MP-1 is included in the deivery of the
19" cabinet 30162 und 30163
art. 30167
19" front panel 64
19" FP-1
to integrate 2 zone alarm device indications type 30098
•
front foil with label for fire zones 1-64
technical specification
front color
material
dimensions (H x W)
art. 30168
19" front panel 128
19" FP-2
to integrate 2 zone alarm device indications type 30098
technical specification
•
front color
material
dimensions (H x W)
front foil with label for fire zone 65 - 128
art. 30169
19" front panel 192
tele grey, RAL 7046
sheet steel
3HE x 19"
19" FP-3
to integrate 2 zone alarm device indications type 30098
technical specification
•
front color
material
dimensions (H x W)
front foil with label for fire zone 129 - 192
tele grey, RAL 7046
sheet steel
3HE x 19"
16
www.detectomat.com
tele grey, RAL 7046
sheet steel
3HE x 19"
1. fire control panels
1.2 detect 3016 fire control panel and accessories
art. 40003
extinguishing control modul
CP ETB X2
plug in extinguishing control module for the detect 3016 fire panel
to control one extinguishing area
•
•
•
direct activation of the extinguishing area valves
4 monitored control lines for signal transmitter and solenoid valves
activation from loop or conventional interface
technical specification
operation voltage
quiesent current
alarm current
sounder output
external user output
operation temperature
dimensions (H x W x D)
approvals
20 up to 28 V DC
45 mA
60 mA + 1 A per output
4 x 24 V DC / 1 A monitored
4 x 24 V DC / 1 A monitored
-5°C up to +40°C
140 mm x 140 mm x 20 mm
VdS G 203 067
remarks: an additional extinguishing panel is not necessary
art. 31320
universal expansion housing
UZG-2
provides additional space for ancilary components
•
•
sheet steal housing compatible with fire control
panel detect 3016
lock for door
technical specification
protection class
housing colour
front color
material
weight
dimensions (H x W x D)
art. 30112
redundant main board processor
to plug in to the detect 3016 fire panel to duplicate the main board
processor
•
takes over the control in case of CPU-failure
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
10 kg
750 mm x 600 mm x 240 mm
CP CPU X2-R
technical specification
quiesent current
alarm current
operation temperature
50 mA
50 mA
-5°C up to +40°C
17
www.detectomat.com
1. fire control panels
1.3 detect 3004/3016 panel accessories
art. 30077
relay board 8 change over
to expand 8 relay outputs for
all fire control panels of the
system detect 3000
•
•
•
•
8 potential-free output relays,
change over contact
8 inputs controlled by the fire
control panel
8 LED´s to display the current
operation status
mountabel on C-rails 35mm in
the panel
art. 32066
monitored module for 4 outputs
RL 58
technical specification
operation voltage
quiesent current
alarm current
relay output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
SC 4
to expand 4 monitored outputs
for all kind of signalling devices
on the fire control panels of the
system detect 3000
•
•
operation voltage
quiesent current
alarm current
sounder output
•
•
•
•
•
•
external powered via fire
control panel
4 jumpers "acoustics on/off option"
to control the noise of the outputs
4 output channels with 24 V
for all kind of signalling devices
output current 400 - 600 mA choosable by jumper
monitorings for short circuit, broken wire, general fault and alarm
4 alarm inputs to activate the selected output
1 general alarm input to activate all outputs
art. 30118
monitored module for 8 outputs
21 up to 28 V DC
3,5 mA
25 mA per relay
8 x change over 250 V / 5 A
-5°C up to +40°C
IP 20
green
ABS
125 mm x 110 mm x 60 mm
VdS G 203 067
"Acoustics on / off" input to disable, set or reset all of the
outputs selected by the jumpers
technical specification
operation temperature
protection class
housing color
material
dimensions (H x W x D)
SC 8
•
•
•
21 up to 28 V DC
1,6 up to 2,5 mA
2,5 mA + 400/600 mA per output
4 x 24 V DC / 400 or 600 mA
monitored
-5°C up to +40°C
IP 20
green
ABS
125 mm x 130 mm x 50 mm
VdS G 203067
8 manual switched inputs
1 general alarm input to activate all outputs
external powered 24 V DC / maximum 3,2 A
technical specification
to expand 8 monitored outputs for all kind of signalling devices on
the fire control panels of the system detect 3000
•
•
•
8 monitored 24 V DC / 400 mA for signalling devices
(separate fused)
8 open collector outputs for LED indicators
8 alarm inputs to activate the selected output
operation voltage
quiesent current
alarm current
sounder output
open collector output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
21 up to 28 V DC
58 mA
58 mA + 400 mA per output
8 x 24 V DC / 400 mA monitored
12 outputs 24 V DC / 90 mA
-5°C up to +40°C
IP 20
green
ABS
125 mm x 175 mm x 60 mm
VdS G 203 067
remarks: it is essential to use the interface 31446 in the fire control panel
18
www.detectomat.com
1. fire control panels
1.3 detect 3004/3016 panel accessories
art. 30115
OC control module
CP AM 32
to expand 32 open collector outputs for all kind of control functions
on the fire control panels of the system detect 3000
•
•
•
•
32 open collector outputs 24 V DC / 90 mA
all outputs are free programmable for alarm events in the fire
control panel
up to 6 boards usable in detect 3016
up to 24 outputs usable in detect 3004
technical specification
operation voltage
quiesent current
alarm current
interfaces
open collector output
operation temperature
dimensions (H x W x D)
approvals
art. 30116
connection board
21 up to 28 V DC
3,5 mA
25 mA per relay
RS 232
32 outputs 24 V DC / 90 mA
-5°C up to +40°C
140 mm x 140 mm x 25 mm
VdS G 203 067
CP AM AP
•
•
connectable via housing on DIN rails 35 mm
usable as connecting box for the OC control module in
installations outside the fire control panel
technical specification
connection board for a separate installation of the CP AM 32
art. 30114
extinguishing interface
protection class
housing colour
material
dimensions (H x W x D)
IP 20
orange
ABS
88 mm x 175 mm x 70 mm
CP SIE
•
indication and control functions according VdS
technical specification
operation voltage
quiesent current
relay output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
interface to expand the fire control panel detect 3000 for connection
on an extinguishing control panel
•
connection of extinguishing control panels for several
areas possible
21 up to 28 V DC
30 mA
8 x change over 250 V / 5 A
-5°C up to +40°C
IP 20
green
ABS
125 mm x 110 mm x 60 mm
VdS G 203 067
remarks:
• it is essential to use a conventional interface to connect the
detector zones in the fire control panel
• maximum 4 extinguishing areas programmable
19
www.detectomat.com
1. fire control panels
1.3 detect 3004/3016 panel accessories
art. 31596
parallel indicator display
ZPA2002
•
•
•
•
•
•
•
•
simultaneous display of 2 messages
optional selection of RS 232 or RS 422
communication length max. 800 m
including buzzer
collectiv LED indicators for operation, alarm, fault and cut-off
powered via fire control panel
automatically data-transfer from the fire control panel
more than 4.000 texts programmable
technical specification
parallel indicator display unit to display the current status of the fire
control panels detect 3000
•
•
including an additional interface RS232/422 and ESPA 4.4.4
for nurse call systems
display with 4 x 20 characters
art. 30106
mount in printer
to expand the front of the fire control
panel detect 3000 with a printer
•
•
•
•
•
thermo printer with 24 characters
58 mm paper width
integrated printer memory of 8 k RAM
direct connectable on the fire
control panels interface RS 232
powered via fire control panel
remarks: by using the printer in the fire control panel detect 3004
are maximum 18 Ah batteries usable, it is essential to specify an CP
MP for the panel when ordering
art. 30099
mount in printer including paper storage
to expand the front of the 19" fire
control panel detect 3000 with a printer
•
•
•
•
•
thermo printer with 24 characters
58 mm paper width
integrated printer memory of 8 k RAM
direct connectable on the fire control
panels interface RS 232
powered via fire control panel
remarks: only usable for 19" housings, it is essential to specify a CP
MP for the panel when ordering
operation voltage
quiesent current
alarm current
interfaces
operation temperature
protection class
housing color
front colour
material
dimensions (H x W x D)
approvals
10 up to 30 V DC
35 mA
100 mA
RS232/422 ESPA 4.4.4
-5°C up to +40°C
IP 30
light grey, RAL 7035
black
ABS
273 mm x 223 mm x 54 mm
VdS G 203086
PIP 2
technical specification
operation voltage
quiesent current
alarm current
interfaces
operation temperature
protection class
front colour
material
dimensions (H x W x D)
approvals
21 up to 28 V DC
12 mA
100 mA
RS 232
-5°C up to +40°C
IP 30
black
ABS
115 mm x 115 mm x 80 mm
VdS G 203 067
PIP 1
technical specification
operation voltage
quiesent current
alarm current
interfaces
operation temperature
protection class
front colour
material
dimensions (H x W x D)
approvals
20
www.detectomat.com
21 up to 28 V DC
40 mA
460 mA
RS 232
-5°C up to +40°C
IP 30
silver
aluminium
130 mm x 107 mm x 165 mm
VdS G 203 067
1. fire control panels
1.3 detect 3004/3016 panel accessories
art. 30471
power supply 120 W
NT 5
usable as additional power supply for the detect 3000 system
technical specification
•
•
•
input voltage
frequency
operation voltage
power supply
external user output
operation temperature
protection class
housing color
front colour
material
weight
dimensions (H x W x D)
power supply 230 V AC, 24 V DC, 5 A
temperature compensated battery-loading
integrated LED indicators for operation and fault
art. 30131
power supply 192 W
NT 8
usable as additional power supply for the detect 3000 system
technical specification
•
•
•
input voltage
frequency
operation voltage
power supply
external user output
operation temperature
protection class
housing color
front colour
material
weight
dimensions (H x W x D)
power supply 230 V AC, 24 V DC, 8 A
temperature compensated battery-loading
integrated LED indicators for operation and fault
art. 40056
battery 12 V / 7,2 Ah
230 V AC
50 / 60 Hz
24 V DC
120 W
3 x 1,6 A separately fused
-5°C bis +40°C
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
13,0 kg
442 mm x 525 mm x 200 mm
230 V AC
50 / 60 Hz
24 V DC
155 W
4 x 1,6 A separately fused
-5°C bis +40°C
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
16,0 kg
442 mm x 525 mm x 200 mm
B 12/ 7,2Ah
•
plug-in connections: 4,8 mm
technical specification
weight
dimensions (H x W x D)
approvals
art. 30155
•
battery 12 V / 12 Ah
plug-in connections: 6,3 mm
2600 g
99 mm x 150 mm x 65 mm
VdS G 103061
B 12/ 12Ah
technical specification
weight
dimensions (H x W x D)
approvals
4200 g
98 mm x 151 mm x 98 mm
VdS G 103063
21
www.detectomat.com
1. fire control panels
1.3 detect 3004/3016 panel accessories
art. 30156
•
battery 12 V / 18 Ah
screw connections for M 5
B 12/ 18Ah
technical specification
weight
dimensions (H x W x D)
approvals
art. 40001
•
battery 12 V / 26 Ah
B 12/ 26Ah
technical specification
screw connections for M 5
weight
dimensions (H x W x D)
approvals
art. 30151
•
battery 12 V / 45 Ah
technical specification
weight
dimensions (H x W x D)
approvals
•
battery 12 V / 65 Ah
screw connections for M 6
base for overvoltage protection modules
14,5 kg
170 mm x 197 mm x 165 mm
VdS G 102002
B 12/ 65Ah
technical specification
weight
dimensions (H x W x D)
approvals
art. 30321
8,5 kg
125 mm x 176 mm x 166 mm
VdS G 103065
B 12/ 45Ah
screw connections for M 6
art. 30461
6,5 kg
167 mm x 81 mm x 76 mm
VdS G 103064
30,0 kg
174 mm x 350 mm x 174 mm
VdS G 102001
CT B
for connection of one protection module
•
•
overvoltage protection max. permanent voltage 250 V AC or 350 V DC
for two wires
technical specification
operation voltage
operation temperature
protection class
housing color
material
dimensions (H x W x D)
22
www.detectomat.com
250 V AC / 350 V AC
-40°C up to +80°C
IP 20
yellow
PA 6.6
90 mm x 12 mm x 44 mm
1. fire control panels
1.3 detect 3004/3016 panel accessories
art. 30335
loop protection module
CT ME 48
overvoltage protection for all loop3000 panel boards and open
collector outputs
•
•
art. 30336
conventional protection module
overvoltage protection for loop3000
nominal discharge current (8/20 µs): 10 kA
CT ME / C 24
overvoltage protection for conventional zones
•
•
art. 30337
bitbus protection module
overvoltage protection for conventional zones
nominal discharge current (8/20 µs): 10 kA
CT ME 5
overvoltage protection for BitBus data cables
•
•
art. 30138
modem
overvoltage protection for conventional zones
nominal discharge current (8/20 µs): 10 kA
RM MO
•
•
•
interface to connect the control panels detect 3000 via phone line
connectable via RS232 on the panel
powered via the rife control panel
technical specification
interface modem to control the fire control panels detect 3000
via phone line
input voltage
frequency
operation voltage
interfaces
housing color
front colour
material
dimensions (H x W x D)
230 V AC
50 / 60 Hz
9 up to 30 V AC or 9 up to 42 V DC
RS 232
grey
grey
aluminium
35 mm x 110 mm x 130 mm
23
www.detectomat.com
1. fire control panels
1.4 network components
art. 32118
remote display- and control panel
ABF
•
•
•
•
operation and event memory for 500 messages
(first in first out principle)
option to equip a redundant main board processor (second CPU)
external powered via fire control panel or power supply
wall mount housing
technical specification
to expand the detect 3000 fire detection network for an separate
remote display- and control panel, wall mount housing
•
•
•
•
•
•
•
•
•
•
•
display- and control panel DIN EN 54 part 2
including Bitbus interface for interlink connection
4 alphanumeric lines LCD- display with backlight
2 slots for fire brigade and network interface
128 programmable detector zones
possibility for integration of fire brigade interface, display panel,
transmission- and key-depot adapter interface
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V / 90 mA)
monitored signal transmitter 400 mA
2 RS 232 interfaces for personal computer, printer, modem,
building management system
network compatible via bitbus interface up to 32 fire control
panels or additional 63 bitbus components
art. 32039
language kit German
language kit integrates German software, German description,
German labelling
art. 32040
language kit English
language kit integrates English software, English description,
English labelling
operation voltage
power supply
emergency power
quiesent current
alarm current
interfaces
display
sounder output
external user output
relay output
open collector output
operation temperature
humidity
protection class
housing color
front color
material
weight
dimensions (H x W x D)
complies with
21,0 up to 29,2 V DC
72 W
max 2 x 12 V / 12 Ah
132 mA
192 mA
2 x RS 232/422 Bitbus (option)
LCD 4 x 20 characters
24 V DC / 400 mA monitored
24V DC / 800 mA
3 change over 250 V / 5 A
9 open collector 30 V DC / 90 mA
-5°C bis +40°C
up to 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
6 kg
262 mm x 420 mm x 83 mm
EN 54 - 2
remarks:
• it is essential to have a separate master display- and control
panel ABF in the BitBus network
• to create an display and control panel including power supply
you have to use an detect 3004 shallow with and language kit ABF
• it is essential to specify an language kit when ordering
for a master panel in the BitBus network
LK ABF D
remarks: it is essential to specify the language kit when ordering
for a master panel in the BitBus network
•
LK ABF GB
additional languages available on request
remarks: it is essential to specify the language kit when ordering
24
www.detectomat.com
1. fire control panels
1.4 network components
art. 32119
remote display- and control panel
ABF-19”
•
•
external powered via fire control panel or power supply
19" or mount in front
technical specification
to expand the detect 3000 fire detection network for an separate
remote display- and control panel, 19" or mount in version
•
•
•
•
•
•
•
•
•
•
•
•
•
display- and control panel DIN EN 54 part 2
including Bitbus interface for interlink connection
4 alphanumeric lines LCD- display with backlight
2 slots for fire brigade and network interface
128 programmable detector zones
possibility for integration of fire brigade interface, display panel,
transmission- and key-depot adapter interface
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V / 90 mA)
monitored signal transmitter 400 mA
2 RS 232 interfaces for personal computer, printer, modem,
building management system
network compatible via bitbus interface up to 32 fire panel
controls or additional 63 bitbus components
operation and event memory for 500 messages
(first in first out principle)
option to equip a redundant main board processor (second CPU)
art. 31315
LCD repeater panel
operation voltage
power supply
emergency power
quiesent current
alarm current
interfaces
display
sounder output
external user output
relay output
open collector output
operation temperature
humidity
protection class
housing color
front color
material
weight
dimensions (H x W x D)
complies with
21,0 up to 29,2 V DC
72 W
max 2 x 12 V / 12 Ah
132 mA
192 mA
2x RS 232/422 Bitbus (option)
LCD 4 x 20 characters
24 V DC / 400 mA monitored
24 V DC / 800 mA
3 change over 250 V / 5 A
9 open collector 30 V DC / 90 mA
-5°C bis +40°C
up to 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
6 kg
6 HE x 19” x 83 mm
EN 54 - 2
remarks:
• it is essential to have a separate master display- and control
panel ABF in the BitBus network
• to create an display and control panel including power supply
you have to use an detect 3004 shallow with and language kit ABF
• it is essential to specify an language kit when ordering
LCD-Tableau
•
•
•
•
•
•
•
•
maximum 61 repeater panels in one BitBus
network usable
4 lines with backlight LC-display
display character size 10 mm
integrated buzzer, with quiesent button
scroll-function of the display by buttons
flat design housing made of brushed stainless steel
automatic data-transfer from the fire control panel
external voltage supply 24 V DC
technical specification
remote display unit for communication with the fire detection
system detect 3000
•
•
displaying of the current status of all loop devices and zones
in the BitBus network
monitored interface to the BitBus network
operation voltage
interfaces
display
operation temperature
humidity
protection class
housing color
front color
material
dimensions (H x W x D)
21 up to 28 V DC
Bitbus
LCD 4 x 20 characters
-5°C bis +40°C
up to 95 %
IP 30
silver
grey
stainless steel
240 mm x 295 mm x 43 mm
25
www.detectomat.com
1. fire control panels
1.4 network components
art. 30087
bitbus interface
CP BBI
•
•
•
•
to build up a fire control panel network of up to 32 fire control
panels and up to 64 BitBus components
via 4-wired interface distances up to 1.200 m (3,900 feet) possible
via bitbus repeater a max. of 13.200 m can be realized in
one network
data rate max 375 kBd
technical specification
operation voltage
interfaces
operation temperature
dimensions (H x W x D)
21 up to 28 V DC
Bitbus
-5°C bis +40°C
25 mm x 50 mm x 59 mm
to expand the fire control panel detect 3000 to interlink several
fire control panels, control- and display panels and other bitbus
components
art. 30119
bitbus CPU
BB-CPU
•
•
•
maximum 61 units in one BitBus network usable
outputs free programmable
external powered 24 V DC
technical specification
seperate intellegent unit to control outputs in the BitBus network
without using fire control panels
operation voltage
quiesent current
alarm current
interfaces
operation temperature
protection class
housing color
material
dimensions (H x W x D)
•
•
remarks: it ist essential to programm the unit via bitbus modem
30139 together with the DPT3000 software
up to 8 extensions 30120 / 30122 connectable
housing for plug in on DIN rails
art. 30120
extension for BitBus CPU, 32 open collector outputs
21 up to 28 V DC
150 mA
150 mA
Bitbus
-5°C bis +40°C
IP 20
green
ABS
125mm x 133 mm x 58 mm
BB-32
•
•
housing for plug in on DIN rails
up to 8 units on one BitBus CPU usable
technical specification
to expand the BitBus CPU for 32 open collector outputs
•
32 open collector outputs 24 V DC / 90 mA
operation voltage
quiesent current
alarm current
open collector output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
26
www.detectomat.com
21 up to 28 V DC
5 mA
max. 320 mA
32 open collector 30 V DC / 90 mA
-5°C bis +40°C
IP 20
green
ABS
125 mm x 163 mm x 60 mm
1. fire control panels
1.4 network components
art. 30122
extension for BitBus CPU, 16 relay outputs
BB-16
•
•
•
16 relay outputs 30 V DC / 2 A
housing for plug in on DIN rails
upto 8 units on one BitBus CPU usable
technical specification
operation voltage
quiesent current
alarm current
relay output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
21 up to 28 V DC
5 mA
max. 320 mA
3 change over 30 V / 2 A
-5°C bis +40°C
IP 20
green
ABS
125 mm x 163 mm x 60 mm
to expand the BitBus CPU for 16 relay outputs
art. 30128
BitBus LED indicator extension
BB-LED
•
•
outputs free programmable
external powered 24 V DC
technical specification
seperate intellegent unit to control LED indicators in the BitBus network
without using fire control panels
•
•
•
for max. 192 LED indicators per interface
6 connection interfaces for LED indicator modul CP ZM 32
maximum 61 units in one BitBus network usable
art. 30124
BitBus amplifier
operation voltage
quiesent current
alarm current
interfaces
external user output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
21 up to 28 V DC
155 mA
max. 320 mA
Bitbus
6 x cable connection for CP ZM 32
-5°C bis +40°C
IP 20
green
ABS
125 mm x 275 mm x 75 mm
BB-R
•
including power supply
technical specification
booster for refreshing the BitBus-signals for cable length > 1200 m
•
•
•
each repeater increase the length of the BitBus network
up to 1.200 m
10 repeater units in one network usable (13.200 m)
the repeater needs no address in the BitBus network
input voltage
frequency
operation voltage
interfaces
emergency power
interfaces
protection class
operation temperature
protection class
housing color
material
dimensions (H x W x D)
230 V AC
50 / 60 Hz
5 V DC
2 x Bitbus
optional
2 x Bitbus
IP 52
-5°C bis +40°C
IP 20
grey
ABS
122 mm x 66 mm x 54 mm
27
www.detectomat.com
1. fire control panels
1.4 network components
art. 31024
BitBus computer interface ISA-Slot
BBI PC
•
•
•
interface for connection of the visual detect software to the
BitBus network
ISA slot plug-in card with integrated BitBus interface
maximum two usable in one BitBus network
technical specification
operation voltage
interfaces
operation temperature
to connect the computer to the fire control panel detect 3000
network
art. 31621
BitBus - fibre optical interface
5 V DC
ISA-Bitbus
-5°C up to +40°C
remarks: up to 99 computers can be connected in the detect 3000 system
via user extensions in the visual detect software via TCP/IP protocol
LCON-1
•
•
•
•
•
transmission rate max. 5 Mbit each second
maximum transmission distance per unit 2.600 m
wave length 820 mm
transmission half duplex
externally powered
technical specification
active interface modul to realize an fibre optical BitBus network for
the fire control panels detect 3000
•
•
converter with one fibre optical and one bitbus channel
fibre optical connector F-ST
art. 31622
fibre optical cable converter
operation voltage
quiesent current
interfaces
operation temperature
protection class
housing color
material
weight
dimensions (H x W x D)
18 up to 30 V DC
250 mA
Bitbus F-ST
0°C up to +70°C
IP 30
black
polyamid
250 g
82 mm x 93 mm x 22,5 mm
LCON-2
•
•
•
•
•
transmission rate max. 5 Mbit each second
optical budget 8 (4,2) dB
transmission path 2.600 (1.400) m
wave length 820 mm
transmission half duplex
technical specification
to active couple the bitbus to the fibre optical cable redundant
transmission path
•
•
LCON is a bitbus fibre optical cable converter with
two fibre optical cable channels and one bitbus channel
fibre optical cable connector F-ST
operation voltage
quiesent current
interfaces
operation temperature
protection class
housing color
material
weight
dimensions (H x W x D)
28
www.detectomat.com
18 up to 30 V DC
250 mA
Bitbus F-ST
0°C up to +70°C
IP 30
black
polyamid
250 g
82 mm x 93 mm x 40 mm
1. fire control panels
1.5 programming tools and software
art. 30501
I-Check 3000 software
I-Check 3000
loop configuration and test software
•
•
•
•
•
•
•
•
•
•
•
•
art. 30136
detectomat programming tool
configuration software for the fire control panels, the separate
remote display- and repeater panel and the BitBus CPU of the
system detect 3000
loop diagnostics and the location of failures are automatically
displayed in a graphic of the loop3000 devices
graphical representation of the loop structure via software
the loop devices are constantly analysed and the analogue values
are displayed
graphical display of the analogue values of smoke, contamination,
temperature, loop-voltage and temperature-compensation
display of detector-type, serial-number, detector-zone with number,
free customer text
all data can be exported in Excel or Word files
extensive print functions of graphics and charts
configuration for all loop devices (algorithms, sensitivities, etc.)
Windows based user interface
the software runs on required Windows 98, 2000 or XP
supports by loop Tester LT 3000
data medium CD-ROM
DPT 3000
•
•
•
•
•
•
art. 30137
software-expansion-dongle
software protection dongle for remote acces for all fire contraol
panels of the system detect 3000
D 3000
•
•
•
art. 30139
Bitbus programming tool
programming tool for the BitBus CPU
programming of the fire control panel
network-configuration
supported by remote maintenance
(software-expansion-dongle 30137)
Windows user interface
the software runs on required Windows 98, 2000 or XP
Data medium CD-ROM
protection for the software
activation of the features: remote diagnostics, status display
and remote control of the fire control panel detect 3004, 3016
and the separate display repeater via the fire control modem
dongle for 25 pole printer interface
BPT
•
including power supply connection and interface cables
29
www.detectomat.com
1. fire control panels
1.5 programming tools and software
art. 31482
EasyCheck
EC 3000
manual programming tool for all loop3000 devices
•
•
•
•
•
•
•
•
•
art. 31625
loop tester
manual addressing and programming tool for all loop3000
devices
battery-operated stand-alone unit
double-spaced lighted LC-display
keypad
Integrated detector base
separate connection for loop modules and manual call points
read-out and changing of the addresses and grades of sensitivity
of all loop3000 elements
copy-function for device replacement
transportation suitcase, 3 batteries type AA, interface-cable,
carrier-belt, cable to connect modules and manual call points are
included in the delivery
LT 3000
loop testing tool for the all loop3000 installations, usable without
panel installation
•
•
•
•
•
•
•
•
•
•
•
•
•
30
www.detectomat.de
test and programming tool for one loop
direct connection to the personal computer
independent operation without fire control panel
loop diagnostics and the location of failures are automatically
displayed in a graphic of the loop3000 devices
graphical representation of the loop structure via software
the loop devices are constantly analysed and the analogue
values are displayed
graphical display of the analogue values of smoke,
contamination, temperature, loop-voltage and temperaturecompensation
display of detector-type, serial-number, detector-zone with
number, free customer text
all datas can be exported in Excel or Word files
extensive print-functions of graphics and charts
configuration for all loop devices (algorithms, sensitivities, etc.)
Windows based user interface
the software runs on Windows 98, 2000 or XP
1. fire control panels
1.6 visualization
art. 31911
demo software for visual detect
VD DV
•
•
•
•
•
•
•
•
•
•
•
•
demonstration kit for visualization software for fire control panels
detect 3000 without active connection to a bitbus network
•
•
•
•
•
runs under Windows 2000/XP
network compatible (server-client principle)
modular structure of the software
full graphic visualization
simulation tool (to test the detectors and the programmed
system connections)
art. 30143
visual detect basic software
•
•
•
•
•
VD Basic 11
•
•
•
•
•
•
•
•
•
•
•
•
basic visualization software kit - basis software for one fire control
panel and one work-station
•
•
•
•
•
•
runs under Windows 2000/XP
network compatible (server-client principle)
modular structure of the software
full graphic visualization
simulation tool (to test the detectors and the programmed
system connections)
comprehensive operator and rights management, different
user-hierarchies can be created
comprehensive operator and rights management, different
user hierarchies can be created
free definable alarm management, procedure-plans
option for automatic execution of procedure-plans
German/English/Russian bilingual
print function (e.g. print of fire brigade routing card, unit
location plans)
system consists of a development and a runtime interface
help function for development and runtime interface
bitbus-connection via internal ISA-bitbus card
password can be modified in the log-on window
data-codification between server and clients
detector data can be generated and read-in via the import-tool
from the dpt-program
full functionality within the system in one host without an active
connection to a bitbus network
procedure-plan are freely defined
location plans, screenshots and routing cards can be printed
manual and automatically
all simulated messages and their execution are recorded and
can be analysed and retrieved with a filter
own projects are programmable, incl. scanning of unit location
plans, routing cards, places of addressed detectors and creation
of procedure-briefings
different user hierarchies can be created within the software by
assigning individual rights
•
•
•
•
•
•
free definable alarm management, procedure-plans
option for automatic execution of procedure-plans
German/English/Russian bilingual
print function (e.g. print of fire brigade routing card, unit
location plans)
system consists of a development and a runtime interface
help function for development and runtime interface
bitbus-connection via internal ISA-bitbus card
password can be modified in the log-on window
data-codification between server and clients
detector data can be generated and read-in via the import-tool
from the dpt-program
authorization for one work-station and one fire control panel
stand-alone system possible, as data-transmission between
server and client via TCP/IP protocol
free creation of announcements
route-plans readable in all common CAD formats
screenshots und route-cards can be printed manual or automatic
all simulated messages and their execution are recorded and
can be analysed and retrieved with a filter
own projects are programmable, incl. scanning of unit location
plans, routing cards, places of addressed detectors and creation
of procedure-briefings
different user hierarchies can be created within the software by
assigning individual rights
31
www.detectomat.de
1. fire control panels
1.6 visualization
art. 30144
Visual detect user expansion
VD UE 1
one workstation expansion kit - for the expansion of one
workstation / user in the TCP/IP network
art. 30145
•
•
•
•
Visual detect expansion panel
VD PE 1
one fire control panel expansion kit - for one fire control panel
in the BitBus network
art. 30146
multiple workstations-expandable by one
possibility to work in the network
messages notification and "send messages"
operator specific classificated messages and rights possible
•
•
•
Visual detect operation expansion
expandable by one fire control panel unit each
a maximum of 20 units can be managed
operator specific classificated messages and rights possible
VD CE 1
license kit - for the remote control function expansion via
visualization software
art. 31654
Visual detect interface management system
VD M I
license kit - interface to building management systems (BMS)
for data support
1.7 conventional panels
art. 30941
conventional fire control panel
BMZ 6
•
•
•
•
•
6 quiescent current monitored detector zones
maximum 30 automatic detector each zone
6 relay outputs for alarm and fault
2 monitored outputs for signalling devices 300 mA
space for battery 1 x 12 V / 7 Ah
technical specification
conventional fire control panel with 6 detector-zones
input voltage
frequency
operation voltage
emergency power
quiesent current
display
zone LED´s
sounder output
relay output
operation temperature
housing color
material
weight
dimensions (H x W x D)
32
www.detectomat.de
230 V AC
50 / 60 Hz
24 V DC
1 x 12 V / 7,5 Ah
190 mA
LED indications
for 6 zones
2x 24V 300mA monitored
1 relay per zone
-5°C up to +40°C
grey
ABS
2 kg
240 mm x 325 mm x 80 mm
2. detectors
2.1 loop3000 - adressable detectors
art. 30009
optical smoke detector
PL 3200 O
•
•
•
•
•
•
•
•
•
•
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
intelligent detector for loop3000, 2 optical sensors, complies with
EN 54 part 7 specification
•
•
•
•
•
•
loop3000 is a high functional detection-system
superior operational reliability from intelligent analysis of the
measuring chamber signal
a second independent optical measuring channel
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
art. 30011
optical smoke detector, isolator
PL 3300 O
intelligent detector for loop3000, 2 optical sensors and bidirectional
isolator, complies with EN 54 part 7 specification
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
< 0,15 dB / m
-10°C up to +60°C
max. 95 % RH / 40°C
IP 40
white
ABS
44 mm x 100 mm
VdS G 202003
EN 54 - 7
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
superior operational reliability from intelligent analysis of the
measuring chamber signal
a second independent optical measuring channel
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
•
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
< 0,15 dB / m
-10°C up to +60°C
max. 95 % RH / 40°C
IP 40
white
ABS
44 mm x 100 mm
VdS G 202002
EN 54 - 7
33
www.detectomat.com
2. detectors
2.1 loop3000 - adressable detectors
art. 30956
optical smoke detector, isolator, white
PL 3301 O white
intelligent detector for loop3000, 2 optical sensors and
bidirectional isolator, complies with EN 54 part 7 specification,
design 1, color white
•
features as PL 3300 O
technical specification
dimensions (H x Ø)
approvals
complies with
art. 30488
optical smoke detector, isolator, silver
42 mm x 95 mm
VdS G 205046
EN 54 - 7
PL 3301 O silver
intelligent detector for loop3000, 2 optical sensors and
bidirectional isolator, complies with EN 54 part 7 specification,
design 1, color silver
•
features as PL 3300 O
technical specification
dimensions (H x Ø)
approvals
complies with
art. 30525
optical smoke detector, isolator, black
42 mm x 95 mm
VdS G 205046
EN 54 - 7
PL 3301 O black
intelligent detector for loop3000, 2 optical sensors and
bidirectional isolator, complies with EN 54 part 7 specification,
design 1, color black
•
features as PL 3300 O
technical specification
dimensions (H x Ø)
approvals
complies with
art. 30555
optical smoke detector, isolator, white
42 mm x 95 mm
VdS G 205046
EN 54 - 7
PL 3304 O white
intelligent detector for loop3000, 2 optical sensors and
bidirectional isolator, complies with EN 54 part 7 specification,
design 4, color white
•
features as PL 3300 O
technical specification
dimensions (H x Ø)
approvals
complies with
34
www.detectomat.com
47 mm x 110 mm
VdS G 204088
EN 54 - 7
2. detectors
2.1 loop3000 - adressable detectors
art. 30556
optical smoke detector, isolator, silver
PL 3304 O silver
intelligent detector for loop3000, 2 optical sensors and
bidirectional isolator, complies with EN 54 part 7 specification,
design 4, color silver
•
features as PL 3300 O
technical specification
dimensions (H x Ø)
approvals
complies with
art. 30567
optical smoke detector, isolator, white
47 mm x 110 mm
VdS G 204088
EN 54 - 7
PL 3305 O white
intelligent detector for loop3000, 2 optical sensors and
bidirectional isolator, complies with EN 54 part 7 specification,
design 5, color white
•
features as PL 3300 O
technical specification
dimensions (H x Ø)
approvals
complies with
art. 30568
optical smoke detector, isolator, silver
47 mm x 110 mm
VdS G 204089
EN 54 - 7
PL 3305 O silver
intelligent detector for loop3000, 2 optical sensors and
bidirectional isolator, complies with EN 54 part 7 specification,
design 5, color silver
•
features as PL 3300 O
technical specification
dimensions (H x Ø)
approvals
complies with
47 mm x 110 mm
VdS G 204089
EN 54 - 7
35
www.detectomat.com
2. detectors
2.1 loop3000 - adressable detectors
art. 32045
optical smoke detector
PL 3200 O/K
•
•
•
•
•
•
•
•
•
•
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
intelligent detector for loop3000, specifically for the detection in air
streams and in aspirating smoke systems (<20 m/sec.),
2 optical sensors, complies with EN 54 part 7 specification
•
•
•
•
•
•
loop3000 is a high functional detection-system
superior operational reliability from intelligent analysis of
the measuring chamber signal
a second independent optical measuring channel
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
art. 30092
optical smoke detector, isolator
intelligent detector for loop3000, specifically for the detection in air
streams and in aspirating smoke systems (<20 m/sec.),
2 optical sensors and bidirectional isolator,
complies with EN 54 part 7 specification
•
•
•
•
•
•
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
superior operational reliability from intelligent analysis of
the measuring chamber signal
a second independent optical measuring channel
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
air speed
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
< 0,15 dB / m
-10°C up to +60°C
max. 95 % RH / 40°C
up to 20m/sec
IP 40
white
ABS
44 mm x 100 mm
VdS G 206 035
EN 54 - 7
PL 3300 O/K
•
•
•
•
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
air speed
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
36
www.detectomat.com
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
< 0,15 dB / m
-10°C up to +60°C
max. 95 % RH / 40°C
up to 20m/sec
IP 40
white
ABS
44 mm x 100 mm
VdS G 202 107
EN 54 - 7
2. detectors
2.1 loop3000 - adressable detectors
art. 30008
heat detector
PL 3200 T
•
•
•
•
•
•
•
•
•
•
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
intelligent detector for loop3000, 2 thermal sensors,
complies with EN 54 part 5 specification
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
superior operational reliability from intelligent analysis of
the thermo sensor
temperature measurement via high sensitiv sensor
maximum and rate of rise analysis with thermal sensor technology
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
art. 30010
heat detector, isolator
•
•
•
•
•
•
•
•
•
•
•
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
60°C or rate of rise
-10°C up to +60°C
max. 95 % RH / 40°C
up to 20m/sec
IP 43
white
ABS
52 mm x 100 mm
VdS G 203038
EN 54 - 5
PL 3300 T
intelligent detector for loop3000, 2 thermal sensors,
complies with EN 54 part 5 specification
•
•
•
•
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
air speed
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
superior operational reliability from intelligent analysis of
the thermo sensor
temperature measurement via high sensitiv sensor
maximum and rate of rise analysis with thermal sensor
technology
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
•
•
•
•
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
air speed
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
60°C or rate of rise
-10°C up to +60°C
max. 95 % RH / 40°C
up to 20m/sec
IP 43
white
ABS
52 mm x 100 mm
VdS G 203037
EN 54 - 5
37
www.detectomat.com
2. detectors
2.1 loop3000 - adressable detectors
art. 30007
optical smoke and heat detector
PL 3200 OT
•
•
•
•
•
•
•
•
•
•
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
intelligent detector for loop3000, 2 optical and 2 thermal sensors,
complies with EN 54 part 5 and 7 specification
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
superior operational reliability from intelligent analysis of
the thermo sensor and the optical measuring chamber signal
temperature measurement via high sensitiv sensor
maximum and rate of rise analysis with thermal sensor technology
a second independent optical measuring channel
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
art. 30021
optical smoke and heat detector, isolator
intelligent detector for loop3000, 2 optical and 2 thermal sensors and
bidirectional isolator, complieswith EN 54 part 5 and 7 specification
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
superior operational reliability from intelligent analysis of
the thermo sensor and the optical measuring chamber signal
temperature measurement via high sensitiv sensor
maximum and rate of rise analysis with thermal sensor technology
a second independent optical measuring channel
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
air speed
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
< 0,15 dB / m 60°C or rate of rise
-10°C up to +60°C
max. 95 % RH / 40°C
up to 20m/sec
IP 40
white
ABS
52 mm x 100 mm
VdS G 205052
54 - 7, 54 - 5
PL 3300 OT
•
•
•
•
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case of
contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
air speed
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
38
www.detectomat.com
15 up to 30 V loop powered
250 µA
5 mA
10 mA for LED indicators
< 0,15 dB / m 60°C or rate of rise
-10°C up to +60°C
max. 95 % RH / 40°C
up to 20m/sec
IP 40
white
ABS
52 mm x 100 mm
VdS G 205051
54 - 7, 54 - 5
2. detectors
2.1 loop3000 - adressable detectors
art. 30079
CO gas and heat detector, isolator
PL 3300 CDBT
•
•
•
•
•
•
•
•
•
•
different sensitivities are programmable for day and night periods
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
automatic fault monitoring of the measuring chamber electronics
self learning mode in respect of environmental conditions
recognition of the exact contamination-status
automatic adjustment of the alarm sensitivity in case
of contamination
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
intelligent detector for loop3000, with carbon monoxid gas and
2 thermal sensors and bidirectional isolator, complies with EN 54
part 5 specification
•
•
•
•
•
•
•
•
•
•
•
operation voltage
quiesent current
alarm current
noise
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
superior operational reliability from intelligent analysis of
the thermo sensor and the carbon monoxid sensor signal
temperature measurement via high sensitiv sensor
maximum and rate of rise analysis with thermal sensor technology
carbon monoxid measurement via industrial detection sensor
pre alarm and alarm level for carbon monoxid
a dedicated thermal-sensor provides a display of the detector
temperature profile at the fire control panel
real sensor-tests are carried out on a periodical basis
detector-sensitivity is freely programmable
open collector output
sensitivity
operation temperature
humidity
air speed
protection class
housing color
material
dimensions (H x Ø)
complies with
15 up to 30 V loop powered
600 µA
5 mA
integreated buzzer for gas alarm
and pre alarm
10 mA for LED indicators
60°C or rate of rise
pre alarm 30 ppm CO
alarm 60 ppm CO
-10°C up to +60°C
max. 95 % RH / 40°C
up to 20m/sec
IP 43
white
ABS
58 mm x 100 mm
54 - 7, 54 - 5
2.2 CT 3000 - conventional detectors
art. 30015
optical smoke detector
CT 3000 O
technical specification
conventional optical smoke detector,
complies with EN 54 part 7 specification
•
•
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
9 up to 33 V Dc
100 µA
20 mA
15 mA for LED indicators
< 0,15 dB / m
-10°C bis +60°C
max. 95 % RH / 40°C
IP 43
white
ABS
44 mm x 100 mm
VdS G 203036
54 - 7
high functional detection-system
intelligent analysis of the measuring chamber signal
39
www.detectomat.com
2. detectors
2.2 CT 3000 - conventional detectors
art. 30977
optical smoke detector
CT 3000 O/K
technical specification
conventional detector, especially fot the detection in air streams
and aspirating smoke systems (<20 m/sec.), with 2 optical sensors,
complies with EN 54 part 7 specification
•
•
high functional detection-system
intelligent analysis of the measuring chamber signal
art. 31929
optical smoke detector, white
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
9 up to 33 V Dc
100 µA
20 mA
15 mA for LED indicators
< 0,15 dB / m
-10°C bis +60°C
max. 95 % RH / 40°C
IP 43
white
ABS
44 mm x 100 mm
VdS G 203035
54 - 7
CT 3001 O white
conventional detector, complies with EN 54 part 7 specification,
design 1
•
features as CT 3000 O
technical specification
dimensions (H x Ø)
art. 31589
optical smoke detector, silver
42 mm x 95 mm
CT 3001 O silver
conventional detector, complies with EN 54 part 7 specification,
design 1
•
features as CT 3000 O
technical specification
dimensions (H x Ø)
art. 31926
optical smoke detector, black
42 mm x 95 mm
CT 3001 O black
conventional detector, complies with EN 54 part 7 specification,
design 1
•
features as CT 3000 O
technical specification
dimensions (H x Ø)
40
www.detectomat.com
42 mm x 95 mm
2. detectors
2.2 CT 3000 - conventional detectors
art. 30552
optical smoke detector, silver
CT 3005 O silver
conventional detector, complies with EN 54 part 7 specification,
design 5
•
•
features as CT 3000 O
low profile available
Technische Daten
dimensions (H x Ø)
low profile version
art. 30551
optical smoke detector, white
47 mm x 110 mm
design mount in version: art. 31684
CT 3005 O white
conventional detector, complies with EN 54 part 7 specification,
design 5
•
•
features as CT 3000 O
low profile available
Technische Daten
dimensions (H x Ø)
art. 30546
optical smoke detector, silver
47 mm x 110 mm
CT 3004 O silver
conventional detector, complies with EN 54 part 7 specification,
design 4
•
•
features as CT 3000 O
low profile available
Technische Daten
dimensions (H x Ø)
47 mm x 110 mm
41
www.detectomat.com
2. detectors
2.2 CT 3000 - conventional detectors
art. 30545
optical smoke detector, white
CT 3004 O white
conventional detector, complies with EN 54 part 7 specification,
design 4
•
features as CT 3000 O
technical specification
dimensions (H x Ø)
art. 30014
heat detector
47 mm x 110 mm
CT 3000 T
•
•
high functional detection-system
intelligent analysis of the thermal sensor
technical specification
conventional heat detector, complies with EN 54 part 5 specification
art. 30022
multisensor detector
operation voltage
quiesent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
housing color
material
dimensions (H x Ø)
complies with
9 up to 33 V DC
100 µA
20 mA
15 mA for LED indicators
60°C rate of rise
-10°C up to +60°C
max. 95 % RH / 40°C
IP 43
white
ABS
52 mm x 100 mm
EN 54 - 5
CT 3000 OT
•
•
•
high functional detection-system
intelligent analysis of the thermal sensor
intelligent analysis of the measuring chamber signal
technical specification
operation voltage
quiesent current
alarm current
open collector output
sensitivity
conventional optical smoke and heat detector,
complies with EN 54 part 5 and 7 specification
operation temperature
humidity
protection class
housing color
material
dimensions (H x Ø)
complies with
42
www.detectomat.com
9 up to 33 V DC
100 µA
20 mA
15 mA for LED indicators
< 0,15 dB / m
60° rate of rise
-10°C up to +60°C
max. 95 % RH / 40°C
IP 43
white
ABS
52 mm x 100 mm
EN 54 - 7, EN 54 - 5
2. detectors
2.3 detector accessoires
art. 30301
detector base
SDB 3000
usable for all detectors of the series loop3000 and CT, colour: white
•
•
•
standard base for all detectors of the series loop3000 and CT
including LED indicator connection
space for additional modules
technical specification
operation temperature
housing color
material
dimensions (H x Ø)
art. 30926
detector base, silver
similar to detector base SBD 3000
art. 30523
detector base, black
similar to detector base SBD 3000
art. 31959 detector base, bridged
base for all loop3000 detectors including a bridge if the detector
should be removed from the socket, colour: white
•
•
•
usable for loop3000 detectors
including LED indicator connection
space for additional cage clambs and modules
art. 32084
detector base, bridged
similar to detector base SDBB 3000
art. 32083
detector base, bridged
similar to detector base SDBB 3000
art. 32114
diode base
SDB 3000 silver
colour: silver
SDB 3000 black
colour: black
SDBB 3000
technical specification
operation temperature
housing color
material
dimensions (H x Ø)
-10°C up to +60°C
white
ABS
20 mm x 95 mm
SDBB 3000 silver
colour: silver
SDBB 3000 black
colour: black
CDBD 3000
usable for all detectors of the series loop3000 and CT, colour: white
technical specification
•
•
•
operation temperature
housing color
material
dimensions (H x Ø)
standard base for all detectors of the series loop3000 and CT
including LED indicator connection
space for additional modules
-10°C up to +60°C
white
ABS
20 mm x 95 mm
-10°C up to +60°C
white
ABS
20 mm x 95 mm
43
www.detectomat.com
2. detectors
2.3 detector accessoires
art. 30469
detector relay base
DRB 3000
detector base with integreated relay to connect to external devices
colour: white
•
•
•
detector relays base to connect to external devices
the relay will be activated directly from the detector alarm output
potential-free change over contact
technical specification
relay output
operation temperature
housing color
material
dimensions (H x Ø)
approvals
art. 32086
detector relay base
similar to detector relay base DRB 3000
art. 32085
detector relay base
similar to detector relay base DRB 3000
art. 32091
piezo buzzer for detectors
change over 30 V / 1 A
-10°C up to +60°C
white
ABS
20 mm x 95 mm
BMA 06/0363-A = pending
DRB 3000 silver
colour: silver
DRB 3000 black
colour: black
Sockel Piezo
•
•
•
•
additional buzzer for detectors of the series loop3000 and CT
activated by open collector output
noise volume 85 dB - distance 0,3 meter
powered by the detector
technical specification
operation voltage
noise
operation temperature
housing color
material
dimensions (H x W x D)
44
www.detectomat.com
15 up to 33 V DC
85 dB / 0,3 m
-10°C up to +60°C
white
ABS
8 mm x 45 mm x 35 mm
2. detectors
2.3 detector accessoires
art. 31698
wall mount base adapter
APS
usable as wall mount kit for all detector bases for on wall
wire installations
•
•
wire entries at the side
internal space for additional modules
technical specification
operation temperature
housing color
material
dimensions (H x Ø)
-10°C up to +60°C
white
ABS
28 mm x 110 mm
remarks:
• it is essential to specifying the right base for this kit
• no socket included
art. 31181
base for humid areas
FRS
•
•
•
universally applicable for damp locations
wire entries at the side
M25 screw fitting included
technical specification
operation temperature
housing color
material
dimensions (H x Ø)
usable as wall mount kit for all detector bases for difficult
and humid envirements
art. 31191
housing for air ducts
-10°C up to +60°C
white
ABS
40 mm x 110 mm
remarks:
• it is essential to specifying the right base for this kit
• no socket included
LKMG
•
•
•
•
•
including pipe for ingress and outlet air sampling
ingress of air pipe length: 210 mm
for air ducts up to 350 mm length
special lengths for ingress of air pipes possible
without detector base
technical specification
operation temperature
air speed
housing colour
material
dimensions (H x W x D)
housing with test-box and sensor-pipe to monitore air streams with
optical detectors of the series loop3000 and CT
-10°C up to +60°C
1 up to 25m/s
grey
ABS
200 mm x 110 mm x 92 mm
remarks:
• it is essential to specifying the right base for this kit
• no socket included
45
www.detectomat.com
2. detectors
2.3 detector accessoires
art. 31875
base with heating
APSB
usable as wall mount kit with monitored heating for all detector
bases for difficult and humid envoirements
•
•
additional on-wall base with temperature controlled heating
usable in installations up to - 30°C
technical specification
operation voltage
quiesent current
external user output
operation temperature
housing color
material
weight
dimensions (H x Ø)
24 V DC
160 mA
4W heating
-30°C up to +60°C
white
ABS
335 g
55 mm x 110 mm
remarks:
• it is essential to specifying the right base for this kit
• no socket included
art. 31684
flush-mounting adapter silver
DR45
usable as mount in kit to semi-recess detectors of the design 4 and
5 in ceilings, color silver
•
•
•
flush mounting base kit for detectors design 4 and 5 of the
series loop3000 and CT
usable in installations in lower ceilings
ceiling hole diameter 120mm
technical specification
operation temperature
housing color
material
dimensions (H x Ø)
-10°C up to +60°C
silver
sheet steel
35 mm x 165 mm
remarks: it is essential to specifying the right base for this kit
art. 32070
flush-mounting adapter white
usable as mount in kit to semi-recess detectors of the design 4 and
5 in ceilings, color white
•
•
•
flush mounting base kit for detectors design 4 and 5 of the
series loop3000 and CT
usable in installations in lower ceilings
ceiling hole diameter 120mm
DR45W
technical specification
operation temperature
housing color
material
dimensions (H x Ø)
-10°C up to +60°C
white
sheet steel
35 mm x 165 mm
remarks: it is essential to specifying the right base for this kit
46
www.detectomat.com
2. detectors
2.3 detector accessoires
art. 30479
labelling tag for detector base
MBC
usable for all detector bases of the series loop3000 and CT
colour: white
•
•
fixing via plug in
selling-packages at 30 pieces
technical specification
operation temperature
colour
material
dimensions (H x W)
art. 30187
detector mounting adapter
-10°C up to +60°C
white
ABS
28 mm x 45 mm
MKBD
for an distanced installation of all detector bases to ceilings or walls
•
•
infinitely adjustable 270 to 480 mm
detector mounting-plate infinitely inclinable 0° until 110°
technical specification
colour
material
dimensions (H x W x D)
art. 30188
detector flap-mounting adapter
light grey, RAL 7035
sheet steel
135 mm x 100 mm x 270 - 480 mm
MKK
for an distanced installation of all detector bases to ceilings or walls
•
inclinable 0° until 110°
technical specification
colour
material
dimensions (H x W x D)
light grey, RAL 7035
sheet steel
150 mm x 117 mm x 13 - 154 mm
47
www.detectomat.com
2. detectors
2.3 detector accessoires
art. 30189
detector distance-mounting adapter
MAK
for an distanced installation of all detector bases to ceilings or walls
•
•
panel for mounting automatic fire detectors in lowered ceilings
ceiling distance 80 mm
technical specification
colour
material
dimensions (H x W x D)
art. 30190
wall bracket
light grey, RAL 7035
sheet steel
80 mm x 138 mm x 100 mm
WA4
for an distanced installation of all detector bases to ceilings or walls
•
•
for mounting of automatic fire detectors, for example over fire
protected doors
distance to the wall: 400 mm
technical specification
colour
material
dimensions (H x W x D)
art. 30191
wall bracket
light grey, RAL 7035
sheet steel
50 mm x 100 mm x 400 mm
WA2
for an distanced installation of all detector bases to ceilings or walls
•
•
for mounting of automatic fire detectors, for example over fire
protected doors
distance to the wall: 200 mm
technical specification
colour
material
dimensions (H x W x D)
48
www.detectomat.de
light grey, RAL 7035
sheet steel
50 mm x 100 mm x 200 mm
3. manual call points
3.1 loop3000 - addressable manual call points
art. 31669
manual call point, ABS
PL 3300 PBDH-ABS-R
intelligent manual call point for loop3000, ABS, red,
with bidirectional isolator
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
multicolour-LED for alarm
technical specification
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
art. 31059
manual call point, ABS
15 up to 30 V loop powered
250 µA
5 mA
-10°C up to +60°C
IP 42
red, RAL 3000
ABS
125 mm x 125 mm x 35 mm
VdS G 203021
EN 14655
PL 3300 PBD-ABS-B
intelligent manual call point for loop3000, ABS, blue,
with bidirectional isolator
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
multicolour-LED for alarm
technical specification
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
15 up to 30 V loop powered
250 µA
5 mA
-10°C up to +60°C
IP 42
blue
ABS
125 mm x 125 mm x 35 mm
VdS G 203021
EN 14655
49
www.detectomat.de
3. manual call points
3.1 loop3000 - addressable manual call points
art. 31060
manual call point, ABS
PL 3300 PBD-ABS-Y
intelligent manual call point for loop3000, ABS, yellow,
with bidirectional isolator
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
multicolour-LED for alarm
technical specification
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
art. 31668
manual call point, ALU
15 up to 30 V loop powered
250 µA
5 mA
-10°C up to +60°C
IP 42
yellow
ABS
125 mm x 125 mm x 35 mm
VdS G 203021
EN 14655
PL 3300 PBDH-ALU-R
intelligent manual call point for loop3000, ALU, red,
with bidirectional isolator
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
multicolour-LED for alarm
technical specification
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
50
www.detectomat.com
15 up to 30 V loop powered
250 µA
5 mA
-10°C up to +60°C
IP 42
red, RAL 3000
aluminium
125 mm x 125 mm x 34 mm
VdS G 203021
EN 14655
3. manual call points
3.1 loop3000 - addressable manual call points
art. 31061
manual call point, ALU
PL 3300 PBD-ALU-B
intelligent manual call point for loop3000, ALU, blue,
with bidirectional isolator
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
multicolour-LED for alarm
technical specification
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
complies with
art. 31062
manual call point, ALU
15 up to 30 V loop powered
250 µA
5 mA
-10°C up to +60°C
IP 42
blue
aluminium
125 mm x 125 mm x 34 mm
EN 14655
PL 3300 PBD-ALU-Y
intelligent manual call point for loop3000, ALU, yellow,
with bidirectional isolator
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
multicolour-LED for alarm
technical specification
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
complies with
15 up to 30 V loop powered
250 µA
5 mA
-10°C up to +60°C
IP 42
yellow
aluminium
125 mm x 125 mm x 34 mm
EN 14655
51
www.detectomat.com
3. manual call points
3.1 loop3000 - addressable manual call points
art. 32065
manual call point
PL 3300 MCP-kit
•
•
•
•
•
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
technical specification
intelligent manual call point for loop3000, ABS red, labeled symbol:
"burning house", with bidirectional isolator
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
art. 30569
manual call point, chinese
intelligent manual call point for loop3000, ALU red, labeled symbol:
"Fire Alarm", with bidirectional isolator
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
15 up to 30 V loop powered
370 µA
5 mA
-10°C up to +60°C
IP 42
red, RAL 3000
ABS
88 mm x 88 mm x 54 mm
LPCB 166b/8
EN 54
PL 3300 MCP-kit
•
multicolour-LED for alarm
technical specification
•
•
•
•
•
•
•
•
•
•
chinese version
2 LED displays for operation and alarm
1 output for evacuation systems
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
a log of the last maintenance date is stored
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
outputs for alarm and fault condition indication at the detector
operation voltage
quiesent current
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
complies with
15 up to 30 V loop powered
250 µA
5 mA
-10°C up to +60°C
IP42
red, RAL 3000
ABS
125 mm x 125 mm x 34 mm
CCC
3.2 CT 3000 - conventional call points
art. 31675
manual call point, ABS, red
CT 3000 PBDH-ABS-R
conventional manual call point for the series CT3000
•
LED indicator for alarm, housing ABS
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
52
www.detectomat.com
12 up to 24 V DC
27 mA
-10°C up to +60°C
IP 42
red, RAL 3000
ABS
125 mm x 125 mm x 34 mm
VdS G296033
EN 54
3. manual call points
3.2 CT 3000 - conventional call points
art. 31651
manual call point, ABS, blue
CT 3000 PBD-ABS-B
conventional manual call point for the series CT3000
•
LED indicator for alarm, housing ABS
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
complies with
art. 31676
manual call point, ALU, red
12 up to 24 V DC
27 mA
-10°C up to +60°C
IP 42
blue
ABS
125 mm x 125 mm x 34 mm
EN 54
CT 3000 PBDH-ALU-R
conventional manual call point for the series CT3000
•
LED indicator for alarm, housing aluminium
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
art. 31087
manual call point, ALU, blue
12 up to 24 V DC
27 mA
-10°C up to +60°C
IP 42
red, RAL 3000
aluminium
125 mm x 125 mm x 34 mm
VdS G 202034
EN 54
CT 3000 PBD-ALU-BD
conventional manual call point for the series CT3000
•
LED indicator for alarm, housing aluminium
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
complies with
12 up to 24 V DC
27 mA
-10°C up to +60°C
IP 42
blue
aluminium
125 mm x 125 mm x 34 mm
EN 54
53
www.detectomat.com
3. manual call points
3.2 CT 3000 - conventional call points
art. 31088
manual call point, ALU, yellow
CT 3000 PBD-ALU-YD
conventional manual call point for the series CT3000
•
LED indicator for alarm, housing aluminium
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
art. 31083
manual call point, IP 66, red
12 up to 24 V DC
27 mA
-20°C up to +70°C
IP 42
yellow
aluminium
125 mm x 125 mm x 34 mm
VdS G 205 018
EN 54
CT 3000 PDB-IP66-R
conventional manual call point for the series CT3000,
IP 66 protected for critical envoirements
•
•
•
•
LED indicator for alarm
housing ABS waterdust and proof IP 66
two switching contacts
connectable on loop3000 via AMD3311
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
art. 32082
manual call point, ABS, red
19 up to 28 V DC
20 mA
-20°C up to +80°C
IP 66
red, RAL 3000
aluminium
135 mm x 145 mm x 70 mm
VdS G 295025
EN 54
SBDH-ABS-R
conventional manual call point for the series CT3000
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
54
www.detectomat.com
9 up to 33 V DC
27 mA
-10°C up to +60°C
IP 42
red, RAL 3000
ABS
88 mm x 88 mm x 54 mm
LPCB 166b/8
EN 54
3. manual call points
3.3 accessoires for manual call points
art. 31091
weatherproof housing
WG-R
in red for aluminium manual call points
•
•
usable to reach protection level IP 54
including fitting kit
technical specification
housing color
material
dimensions (H x W x D)
art. 31092
weatherproof housing
red, RAL 3000
aluminium
145 mm x 131 mm x 55 mm
WG-B
in blue for aluminium manual call points
•
•
usable to reach protection level IP 54
including fitting kit
technical specification
housing color
material
dimensions (H x W x D)
•
art. 40054
key for manual call point
HFM-SCH-M
art. 31910
glass for manual call point
HFM EG
art. 31069
•
glass for manual call point
labeled with blue circle
art. 30026
•
dimensions (H x W)
unlabeled
glass for manual call point
labeled with yellow circle
blue
aluminium
145 mm x 131 mm x 55 mm
80 mm x 80 mm
HFM EG-B
dimensions (H x W)
80 mm x 80 mm
HFM EG-G
dimensions (H x W)
80 mm x 80 mm
55
www.detectomat.com
4. loop3000 modules
art. 30200
in-/output module
IOM 3311
intelligent input output module for loop3000 with bidirectional
isolator in a housing
•
•
•
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
1 monitored input to connect external devices to the loop3000
1 potential-free output to control external devices
in- and output are freely programmable
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
operation voltage
quiesent current
alarm current
relay output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
art. 32073
extension module
15 up to 30 V loop powered
500 µA
5 mA
change over 30 V / 1 A
-10°C up to +60°C
IP 54
grey, RAL 7035
ABS
93 mm x 93 mm x 55 mm
VdS G 205029
EN 54
UBW 3311
extension module for the realisation of controlled outputs via the
IOM3311 or the OMS3301
•
•
•
•
•
1 monitored output with broken wire- and short circuit
monitoring
maximum current 1 A via external supply
convenient for the monitored connection of signaling devices
directly connectable in the housing of the IOM3311 or OMS3301
external powered
technical specification
operation voltage
quiesent current
alarm current
sounder output
operation temperature
dimensions (H x W x D)
approvals
complies with
56
www.detectomat.com
24V DC
11 mA
up to 1A
up to 1A
-10°C up to +60°C
20 mm x 38 mm x 35 mm
pending
EN 54
4. loop3000 modules
art. 30211
output module
OMS 3301
•
•
•
•
•
1 potential-free output to control external devices
the relays can be reset at the fire control panel via
"external sounder on/off"
output is freely programmable
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
technical specification
operation voltage
quiesent current
alarm current
relay output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
intelligent sounder-control-module for loop3000 including
bidirectional isolator
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
art. 30513
mini in-/output module
15 up to 30 V loop powered
500 µA
5 mA
change over 30 V / 1 A
-10°C up to +60°C
IP 54
grey, RAL 7035
ABS
93 mm x 93 mm x 55 mm
VdS G 205030
EN 54
AMD 3311
•
•
•
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
poured ciruit board version
technical specification
intelligent input output module for loop3000 with bidirectional isolator
in mini version
•
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
1 monitored input to connect external devices to the loop3000
1 open collector output to control external devices
in- and output are freely programmable
art. 31640
mini output module
operation voltage
quiesent current
alarm current
open collector output
operation temperature
housing color
dimensions (H x W x D)
approvals
complies with
15 up to 30 V loop powered
370 µA
5 mA
500 mA
-10°C up to +60°C
blue
27 mm x 73 mm x 15 mm
VdS G 206047
EN 54
OMS 3301mini
•
•
•
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
poured ciruit board version
technical specification
intelligent sounder-control-module for loop3000 including bidirectional
isolator
•
•
•
•
•
loop3000 is a high functional detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
1 open collector output to control external devices
output is freely programmable
operation voltage
quiesent current
alarm current
open collector output
operation temperature
housing color
dimensions (H x W x D)
complies with
15 up to 30 V loop powered
370 µA
5 mA
500 mA
-10°C up to +60°C
blue
27 mm x 73 mm x 15 mm
EN 54
57
www.detectomat.com
4. loop3000 modules
art. 32074
in-/output module mini
AOM 3301
intelligent module for loop3000 including bidirectional isolator
•
•
•
•
•
•
•
•
•
loop3000 is a high functionality detection-system
including bidirectional short circuit isolator
addressable spur connection via T-branch
1 monitored input to connect external devices to the loop3000
1 monitored output to control external devices
in- and output are freely programmable
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
ciruit board version
technical specification
operation voltage
quiesent current
alarm current
external user output
operation temperature
dimensions (H x W x D)
complies with
art. 30205
conventional zone module
15 up to 30 V loop powered
370 µA
5 mA
5 mA monitored
-10°C up to +60°C
27 mm x 73 mm x 15 mm
EN 54
TCM 3300
intelligent module for loop3000 for connection of 1 zone of conventional detectors, including bidirectional isolator
•
•
•
•
•
•
•
•
detector zone interface with high functionality for loop3000
integrated bidirectional short circuit isolator
addressable spur connection via T-branch
variable adjustable of short circuit-, break wire-, pre-alarm- and
alarm threshold
external power supply of 12 / 24 volt
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
multicolour-LED for alarm- (red) and fault-display (yellow)
technical specification
operation voltage
quiesent current
alarm current
external user output
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
58
www.detectomat.com
15 up to 30 V loop powered
500 µA
5 mA per zone
12 / 24 V 10 mA + zone current
-10°C up to +60°C
IP 54
grey, RAL 7035
ABS
93 mm x 93 mm x 55 mm
VdS G 206048
EN 54
5. loop3000 - radio extension
art. 30025
wireless gateway
WGW 3300
•
•
•
•
•
•
•
•
•
5 radio-channels and 2 emergency-channels 433/868 MHz
with changeover operation
up to 32 wireless devices can be connected per gateway
analogue values of the detectors can be shown via the
detectomat fire control panel
the detectomat fire control panel can allocate the plaintext
and zones of the devices
meets the requirements of BS 5839, EN 54 and VdS
common alarm and fault relays for stand alone operation
separate current supply and emergency power supply
integrated emergency power supply by commercial standard
AA-batteries
up to 10 gateways in one radio nit can be integrated without
quality loss
technical specification
frequency
operation voltage
emergency power
quiesent current
display
relay output
intelligent wireless gateway for loop3000 to connect wireless
detectors/-modules, including bidirectional isolators
•
•
•
•
•
a high functionality wireless extention to the loop3000
for the integration of wireless detectors and -modules
including bidirectional short circuit isolator as loop-module
programming and status is displayed by a 4 x 20 character display
keyboard consists of 16 keys for controlling and programming
art. 30003
wireless optical smoke detector
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
2 x 433 MHz, 5 x 868 MHz
24 V DC external
batteries 8 x AA Mignon
20 mA
4 x 20 characters
alarm 30 V / 1 A
fault 30 V / 1 A
-10°C up to +60°C
IP 65
grey, RAL 7035
ABS
200 mm x 120 mm x 77 mm
VdS pending, LPCB,
E 120684/1.1, TE 226593
EN 54 - 25
WL 3200 O
intelligent wireless optical smoke detector for loop3000
•
•
•
•
•
high functionality detection system for loop3000
equivilant to loop-device in conjunction with gateway WGW 3300
power supplied by 2 pieces of commercial standard C-batteries
battery lifetime approximatley 3 years
a programmable piezo-sounder is included
technical specification
frequency
operation voltage
operation temperature
protection class
housing color
material
dimensions (H x Ø)
approvals
complies with
2 x 433 MHz, 5 x 868 MHz
3 V, 2 x MX1400 LR 14 Duracell
-10°C up to +60°C
IP 42
white
ABS
65 mm x 100 mm
VdS pending, LPCB,
E 120684/1.1, TE 226593
EN 54 - 7
59
www.detectomat.com
5. loop3000 - radio extension
art. 32005
antenna for extended range
WGA 3200
external antenna for the wireless gateway WGW 3300
•
antenna for the improvement of the radio-field quality and
range in intricate area conditions
technical specification
dimensions (H x W x D)
art. 31627
wireless input module
490 mm x 270 mm x 330 mm
WL 3210 EM
•
•
•
•
•
•
•
equivilant to loop-device in conjunction with gateway WGW 3300
stand-alone addressed during universal operation
power supplied by commercial standard A mignon
battery lifetime approximatley 3 years
1 monitored input, freely programmable via the detectomat fire
control panel
integrated alarm-sound
an activation-module, e.g. a manual call point or a similar device
can be separated up to 5 m
technical specification
intelligent input module for loop3000
•
high functionality detection system for loop3000
frequency
operation voltage
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
60
www.detectomat.com
2 x 433 MHz, 5 x 868 MHz
3 V, 2 x MX1400 LR 14, Duracell
-10°C up to +60°C
IP 54
grey, RAL 7035
ABS
93 mm x 93 mm x 55 mm
LPCB, E 120684/1.1, TE 226593
EN 54
5. loop3000 - radio extension
art. 31626
radio field analyzer
RFA 3000
with the possibility to switch between sending and receiving-mode
•
•
•
•
•
•
•
radio filed intensity analyzer (1 pair)
to identify the best installation area of the detectomat
wireless devices
battery operated unit 2 x AA-batteries)
separate antenna for 433 and 868 MHz
LED signal strength gage-display
the measurements can be transferred to a personal computer
via a serial interface (optional)
LED display for sending, receiving and frequency-band
technical specification
frequency
operation voltage
protection class
housing color
material
dimensions (H x W x D)
20 x 433 MHz, 4 x 868 Hz
3 V, 2 x AA
IP 30
grey, RAL 7035
ABS
195 mm x 66 mm x 27 mm
61
www.detectomat.com
6. special detectors
6.1 aspiration smoke detectors
art. 31114
Stratos HSSD-2 standard detector
HSSD-2 M
•
•
•
•
•
•
•
sensitivity adjustable: 0,002 - 25 % obs/m
max. 1600 mÇ (one fire compartment) can be monitored
max. length of aspiration-pipes: 200 m with 100 bore holes or
250 m with 80 bore holes
LC display 2 x 16 characters, cursor key control panel
integrated dust filter meets the requirements of the VdS
up to 127 STRATOS devices can be connected in a network
by the integrated RS 485
uninterruptible external current supply 24 V DC
technical specification
operation voltage
quiesent current
interfaces
display
relay output
sensitivity
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
intelligent smoke detector for building a highly sensitive asirating
smoke system for earliest fire detection
•
•
•
Stratos HSSD-2 standard detector without display
intelligent smoke detector for building a highly sensitive asirating
smoke system for earliest fire detection, without display
•
•
•
•
•
•
•
•
•
•
remarks:
• the project engineering guidelines of the manufacturer has
to be considered by the planning of the system
• all project engineering documents have to be signed
by detectomat GmbH
for the earliest detection of fire by a laser-detector-chamber with
patented artificial intelligence "classifire"
to monitor clean-rooms as well as contaminated areas and also
in areas, which are used by vehicles with combustion motor
highest sensitivity, optimal alarm threshold and low false alarm
rates are ensured by the automatic adjustment to the respective
area conditions
art. 31867
for the earliest detection of fire by a laser-detector-chamber with
patented artificial intelligence "classifire"
to monitor clean-rooms as well as contaminated areas and also
in areas, which are used by vehicles with combustion motor
highest sensitivity, optimal alarm threshold and low false alarm
rates are ensured by the automatic adjustment to the respective
area conditions
sensitivity adjustable: 0,002 - 25 % obs/m
max. 1600 mÇ (one fire compartment) can be monitored
max. length of aspiration-pipes: 200 m with 100 bore holes or
250 m with 80 bore holes
LC display for operation, alarm and fault
integrated dust filter meets the requirements of the VdS
up to 127 STRATOS devices can be connected in a network by
the integrated RS 485
uninterruptible external current supply 24 V DC
24 V DC
400 mA
RS 485
2 x 16 characters
3 (alarm, pre-alarm, fault)
(0,002 - 25) % obs / m
(0,0003 - 10) µm
-10°C up to +60°C
IP 50
light grey
aluminium
372 mm x 427 mm x 95 mm
VdS G 203024, LPCB, CCC
EN 54 - 13
HSSD-2 MOD
technical specification
operation voltage
quiesent current
interfaces
zone LED´s
relay output
sensitivity
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
62
www.detectomat.com
24 V DC
400 mA
RS 485
4 x LED indicators for operation,
alarm, fault
3 (alarm, pre-alarm, fault)
(0,002 - 25) % obs / m
(0,0003 - 10) µm
-10°C up to +60°C
IP 50
light grey
sheet steel
372 mm x 427 mm x 105 mm
VdS G 203 024
EN 54 - 13
6. special detectors
6.1 aspiration smoke detectors
art. 31115
Stratos HSSD-2 standard detector and control module
technical specification
intelligent smoke detector for building a highly sensitive asirating
smoke system for earliest fire detection, including command module
•
•
•
•
•
•
•
•
•
•
•
for the earliest detection of fire by a laser-detector-chamber with
patented artificial intelligence "classifire"
with the command module all networking STRATOS devices of
one system can be programmed as well as there status can be
displayed
to monitor clean-rooms as well as contaminated areas and also
in areas, which are used by vehicles with combustion motor
highest sensitivity, optimal alarm threshold and low false alarm
rates are ensured by the automatic adjustment to the respective
area conditions
sensitivity adjustable: 0,002 - 25 % obs/m
max. 1600 mÇ (one fire compartment) can be monitored
max. length of aspiration-pipes: 200 m with 100 bore holes or
250 m with 80 bore holes
LC display 8 x 16 characters, cursor key control panel
integrated dust filter meets the requirements of the VdS
up to 127 STRATOS devices can be connected in a network by
the integrated RS 485
uninterruptible external current supply 24 V DC
art. 31117
Stratos HSSD-2 control module
command module for programming and displaying all in the network
connected STRATOS components
•
•
•
LC display 8 x 16 characters, cursor key control panel
up to 127 STRATOS devices can be connected in a network by
the integrated RS 485
uninterruptible external current supply 24 V DC
art. 31953
Stratos HSSD-2 control module 19"
command module in 19" for programming and displaying all in the
network connected STRATOS components
•
•
•
LC display 8 x 16 characters, cursor key control panel
up to 127 STRATOS devices can be connected in a network by
the integrated RS 485
uninterruptible external current supply 24 V DC
HSSD-2 M-S
operation voltage
quiesent current
interfaces
display
relay output
sensitivity
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
24 V DC
400 mA
RS 485
8 x 16 characters
3 (alarm, pre-alarm, fault)
(0,002 - 25) % obs / m
(0,0003 - 10) µm
-10°C up to +60°C
IP 50
grey
aluminium
372 mm x 427 mm x 95 mm
VdS G 203024, LPCB, CCC
EN 54 - 13
remarks:
• the project engineering guidelines of the manufacturer has
to be considered by the planning of the system
• all project engineering documents have to be signed
by detectomat GmbH
HSSD-2 S
technical specification
operation voltage
quiesent current
interfaces
display
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
24 V DC
450 mA
RS 485
8 x 16 Zeichen
-10°C up to +60°C
IP 50
grey
aluminium
372 mm x 427 mm x 95 mm
VdS G 203024, LPCB, CCC
EN 54 - 13
HSSD-2 S 19"
technical specification
operation voltage
quiesent current
interfaces
display
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
24 V DC
450 mA
RS 485
8 x 16 Zeichen
-10°C up to +60°C
IP 50
grey
aluminium
3HE mm x 19“ x 95 mm
VdS G 203024, LPCB, CCC
EN 54 - 13
remarks: without housing
63
www.detectomat.com
6. special detectors
6.1 aspiration smoke detectors
art. 31476
Stratos Micra 100 including mounting base
Micra 100
•
•
•
•
•
•
max. length of aspiration-pipes: 100 m
(2 x 50 m, each with max. 25 bore holes)
LC display for operation, alarm, fault
integrated dust filter
up to 127 STRATOS devices can be connected in a network by
the integrated RS 485
uninterruptible external current supply 24 V DC
mounting base including connecting flange to ensure the
recirculation
technical specification
operation voltage
quiesent current
interfaces
zone LED´s
intelligent aspirating smoke system for building a highly sensitive
asirating smoke system for earliest detection, without display
•
•
•
•
for the earliest detection of fire by a laser-detector-chamber with
patented artificial intelligence "classifire"
to monitor clean-rooms as well as contaminated areas and also
in areas, which are used by vehicles with combustion motor
highest sensitivity, optimal alarm threshold and low false alarm
rates are ensured by the automatic adjustment to the respective
area conditions
sensitivity adjustable: 0,002 - 25 % obs/m
art. 31118
Stratos Micra 25 including mounting base
relay output
sensitivity
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
26 V DC
400 mA
RS 485
4 x LED indicators for operation,
alarm, fault
3 (alarm, pre-alarm, fault)
(0,002 - 25) % obs/m
(0,0003 - 10) µm
-10°C up to +60°C
IP 51
grey
aluminium
180 mm x 300 mm x 85 mm
LPCB
EN 54 - 13
Micra 25
•
•
•
•
•
•
max. length of aspiration-pipes: 50 m
(25 m at highest sensitivity)
LC display for operation, alarm, fault
integrated dust filter
up to 127 STRATOS devices can be connected in a network by
the integrated RS 485
uninterruptible external current supply 24 V DC
mounting base including connecting flange to ensure the
recirculation
technical specification
operation voltage
quiesent current
interfaces
zone LED´s
intelligent aspirating smoke system for building a highly sensitive
asirating smoke system for earliest detection, without display
•
•
•
•
for the earliest detection of fire by a laser-detector-chamber with
patented artificial intelligence "classifire"
to monitor clean-rooms as well as contaminated areas and also
in areas, which are used by vehicles with combustion motor
highest sensitivity, optimal alarm threshold and low false alarm
rates are ensured by the automatic adjustment to the respective
area conditions
sensitivity adjustable: 0,002 - 25 % obs/m
relay output
sensitivity
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
complies with
64
www.detectomat.com
26 V DC
250 mA
RS 485
3 x LED indicators for operation,
alarm, fault
3 (alarm, pre-alarm, fault)
(0,002 - 25) % obs/m
(0,0003 - 10) µm
-10°C up to +60°C
IP 51
grey
aluminium
175 mm x 135 mm x 80 mm
LPCB
EN 54 - 13
6. special detectors
6.1 aspiration smoke detectors
art. 30078
aspiration smoke detector
aspiration housing to insert one or two conventional or addressable
optical smoke detectors
•
•
•
•
•
•
•
•
applicable in the serial loop3000 and CT 3000
directly connectable to the loop3000 with IOM 3311
2 outputs for alarm and one fault relays
pipe system with 25 mm pipe connectable, maximum length 100 m
the aspiration pipe is permanent monitored
LED display for operation, alarm and fault
dust filter is included in the delivery
uninterruptible external current supply 24 V DC
ASD-20
technical specification
input voltage
operation temperature
stock temperature
humidity
housing color
weight
material
dimensions (H x W x D)
24 V DC
-10°C up to +60°C
-10°C up to +70°C
< 95 %
grey, RAL9999
4000 g
polycarbonat
314 mm x 254 mm x 115 mm
remarks: apirating pipe systems made of PVC are applicable and can
be ordered by the local wholesalers
art. 32076
aspiration smoke detector
ASD-01
aspiration housing to insert one or two conventional or automatic
detectors
•
•
•
•
•
•
•
•
applicable in the serial loop3000 and CT 3000
directly connectable to the loop3000 with IOM 3311
2 outputs for alarm and one fault relays
pipe system with 25 mm pipe connectable, maximum length 50 m
the aspiration pipe is permanent monitored
LED display for operation, alarm and fault
dust filter is included in the delivery
uninterruptible external current supply 24 V DC
technical specification
input voltage
operation temperature
humidity
dimensions (H x W x D)
24 V DC
-10°C up to +60°C
10 up to 95 % RH
165 mm x 250 mm x 240 mm
remarks: apirating pipe systems made of PVC are applicable and can
be ordered by the local wholesalers
6.2 accessoires for smoke detectors
art. 31133
Stratos asirating pipe 3/4"
STR-R
halogen-free aspiration-pipe for STRATOS aspiration smoke system
•
•
•
•
•
3 m pipe
material plastic, halogen-free, red
low coefficient of thermal expansion
great flexibility at high capacity
refractiveness against chemicals
technical specification
colour
material
dimensions (H x Ø)
rot
ABS,
3 m x 3/4"
65
www.detectomat.com
6. special detectors
6.2 accessoires for smoke detectors
art. 31135
Stratos 45° deg elbow pipe
STR-W45
technical specification
colour
material
dimensions (Ø)
art. 31136
Stratos 90° bend
red
ABS
3/4"
STR-B90
technical specification
colour
material
dimensions (Ø)
art. 31138
Stratos socket
red
ABS
3/4"
STR-M
technical specification
colour
material
dimensions (Ø)
art. 31140
Stratos T-piece
red
ABS
3/4"
STR-T
technical specification
colour
material
dimensions (Ø)
art. 31141
Stratos socket union
red
ABS
3/4"
STR-V
technical specification
colour
material
dimensions (Ø)
art. 31143
Stratos end cap
red
ABS
3/4"
STR-E
technical specification
colour
material
dimensions (Ø)
66
www.detectomat.com
red
ABS
3/4"
6. special detectors
6.2 accessoires for smoke detectors
art. 31948
Stratos adapter 3/4" female to 25 mm male
STR-R3/4”-25
technical specification
colour
material
dimensions (Ø)
art. 31949
Stratos 25 mm female to 3/4" male adapter
red
ABS
3/4" x 25 mm
STR-R26-3/4”
technical specification
colour
material
dimensions (Ø)
art. 31950
Stratos socket 3/4" to 25 mm female
red
ABS
25 mm x 3/4"
STR-RM5
technical specification
colour
material
dimensions (Ø)
art. 32050
Stratos ABS-socket 3/4" to 25 mm
red
ABS
3/4" x 25 mm
STR-RH
technical specification
colour
material
dimensions (Ø)
approvals
art. 31613
Stratos plug sampling point assembly
black
ABS
3/4" x 25 mm
VdS G 206 034
STR-SK
technical specification
colour
material
dimensions (Ø)
white
ABS
3/4"
67
www.detectomat.com
6. special detectors
6.2 accessoires for smoke detectors
art. 31155
Stratos in-line smapling point
STR-KK
technical specification
colour
material
dimensions (Ø)
art. 31156
Stratos patress sampling point
white
ABS
3/4"
STR-KB
Mit Befestigungsflasch
technical specification
colour
material
dimensions (Ø)
art. 31153
Stratos in-line remote sampling point adapter
white
ABS
3/4"
STR-MK
technical specification
colour
material
dimensions (Ø)
art. 31154
Stratos end cap adaptor
red
ABS
3/4" - 10 mm
STR-EK
technical specification
colour
material
dimensions (Ø)
art. 31151
Stratos nylon tube, red
red
ABS
3/4" - 10 mm
STR-KR
technical specification
housing color
material
dimensions (Ø)
68
www.detectomat.de
red
Nylon
10 mm - 3/4"
6. special detectors
6.2 accessoires for smoke detectors
art. 31152
Stratos nylon tube, white
STR-KW
technical specification
color
material
dimensions (Ø)
art. 31145
Stratos pipe clip, red
white
nylon
10 mm
STR-C
technical specification
color
material
art. 31146
Stratos pipe clip black
STR-CA
art. 31960
Stratos flange nut
STR-CM
art. 31148
Stratos pipe cleaner
STR-RE
Stratos ABS solvent cement
STR-SK
red
ABS
M8 x 60 mm
500 ml
art. 31147
for ABS-pipe, 250 ml
art. 31149
Stratos sampling hole warning stickers
STR-WA
to mark the aspiration drilling points, Selling-packages at 100 pieces
69
www.detectomat.com
6. special detectors
6.3 infrared beam detectors
art. 30473
infrared beam detector
SPB-E IR BD
•
•
•
•
range 5 - 100 m
monitored area and mounting meets DIN VDE 0833
potential-free relays for alarm and fault
three sensitivities: 25, 50 and 70 %
technical specification
operation voltage
quiesent current
alarm current
relay output
operation temperature
humidity
housing color
material
weight
dimensions (H x W x D)
approvals
sender- and receiver unit
•
•
connectable on the loop3000 via IOM3311
light and dark smoke can be detected
art. 31096
reset module
reset-board for the use in the loop to control the SB-E IR BD
RM95
•
•
by voltage supply interruption the external detectors can be reset
for a system compatible resetting of the detector after abrogate
the alarm criterion
to connect to the opto-output of the input-module
circuit board with connectin clamp included in delivery
•
•
art. 31095
infrared beam detector
15 up to 33 V DC
280 µA
20 mA
2
-10°C up to +50 °C
max. 95 %
white
ABS
transmitter 450 g, reciever 450 g
145 mm x 100 mm x 86 mm
VdS G 295004
FR 2000
•
•
•
•
•
light and dark smoke can be detected
range 5 - 100 m
monitored area and mounting meets DIN VDE 0833
potential-free relays for alarm and fault
three sensitivities: 25, 35 and 50 %
technical specification
sender, receiver and separate analyser
•
connectable on the loop3000 via IOM3311
operation voltage
quiesent current
alarm current
relay output
operation temperature
stock temperature
protection class
housing color
colour Frontfolie
material
weight control unit
dimensions (H x W x D)
approvals
complies with
70
www.detectomat.com
11,5 up to 28 V DC
14 mA
22 mA
2 x 30 V DC / 1 A
-20°C up to +55° C
-25°C up to +60°C
IP 50
grey
grey
sheet steel
2140 g
265 mm x 210 mm x 85 mm
VdS G 297058
EN 54 - 12
6. special detectors
6.3 infrared beam detectors
art. 30474
infrared beam detector
SRA-ET IR BD-R
•
•
monitored area and mounting meets DIN VDE 0833
conventional detector (current increase)
technical specification
sender and receiver in a single housing including reflector
•
•
•
connectable on the loop3000 via TCM3300
light and dark smoke can be detected
range 5 - 30 m
art. 31861
infrared beam detector
operation voltage
quiesent current
alarm current
operation temperature
humidity
housing color
material
weight
dimensions (H x W x D)
approvals
15 up to 30 V DC
350 µA
50 mA
-10°C up to +50°C
max. 95 %
white
ABS
700 g
125 mm x 122 mm x 80 mm
VdS G 200080
FR 50 RV
•
•
•
•
range 5 - 50 m
monitored area and mounting meets DIN VDE 0833
potential-free relays for alarm and fault
three sensitivities: 25, 35 and 50 %
technical specification
sender and receiver in a single housing including one prism
•
•
connectable on the loop3000 via IOM3311
light and dark smoke can be detected
art. 31486
infrared beam detector
operation voltage
quiesent current
alarm current
relay output
operation temperature
stock temperature
protection class
housing color
material
weight
dimensions (H x W x D)
approvals
complies with
FR 100 RV
sender and receiver in a single housing including four prism
technical specification
•
•
•
•
•
•
operation voltage
quiesent current
alarm current
relay output
operation temperature
stock temperature
protection class
housing color
material
weight
dimensions (H x W x D)
approvals
connectable on the loop3000 via IOM3311
light and dark smoke can be detected
range 5 - 100 m
monitored area and mounting meets DIN VDE 0833
potential-free relays for alarm and fault
three sensitivities: 25, 35 and 50 %
(picture similar to art. 31861)
10,2 up to 30 V DC
4 mA
15 mA
2 x 30 V DC / 1 A
-30°C up to +55°C
-35°C up to +60°C
IP 50
grey
ABS
670 g
117 mm x 210 mm x 120 mm
VdS G 203070
EN 54 - 12
10,2 up to 30 V DC
4 mA
15 mA
2 x 30 V DC / 1 A
-30°C up to +55°C
-35°C up to +60°C
IP 50
grey
ABS
670 g
117 mm x 210 mm x 120 mm
VdS G 203070
71
www.detectomat.com
6. special detectors
6.4 sensor cable detectors
art. 30503
sensor cable detector
SKM-03.01
•
•
•
•
•
•
connectable on the loop3000 via IOM3311
display unit to connect up to 300 m sensor cable
appropriate to use in adverse surroundings or restricted
circumstances (underground car parks, cable channels, etc.)
potential-free alarm -and fault output
delivery including cable installation box
alarm display meets DIN 14623
technical specification
sensor cable detector for the earliest detection of fire oder overheat
in critical envoirements
art. 30980
sensor cable red
to connect to sensor cable detector SKM 03
•
•
appropriate in normal surrounding conditions without
aggressive atmosphere
tensile strength: < 200 N
art. 30981
sensor cable black
to connect to sensor cable detector SKM 04
•
•
appropriate in surrounding conditions with
aggressive atmosphere
tensile strength: < 200 N
operation voltage
quiesent current
alarm current
relay output
operation temperature
protection class
housing color
material
weight
dimensions (H x W x D)
approvals
SKM-KRT
•
•
•
design: synthetic-coaxial wire,
diameter Ø 3,25 mm,
color red
approvals
fanstening clamp
VdS G 203067, VdS G 203 077
SKM-KSW
•
•
•
•
design: synthetic-coaxial wire,
diameter Ø 4 mm,
color black
protected against acids and bases
approvals
art. 31620
24 V DC
28 mA
58 mA
2 x 30 V DC / 1 A
-25°C up to +50°C
IP 65
grey
ABS
370 g
105 mm x 105 mm x 65 mm
VdS G 203067
VdS G 203067, VdS G 203 077
SK-LS
for sensor cable detector
•
•
•
•
to connect the sensor cable
time-saving and simple start-up mounting
hole diameter Ø 6mm
selling-packages at 100 pieces
72
www.detectomat.com
6. special detectors
6.5 flame detectors
art. 31897
ultraviolet flame detector
FL 80/1A
ultraviolet flame detector for an earliest fire detection in the
industrial areas and in difficult envoirements
•
•
•
•
•
for the detection of open fire without smoke development
integrated test-unit to check the detector function during operation
sikh angle 90°-100°
sensibility meets EN 54-10 class 1
high speed capability
technical specification
input voltage
operation voltage
quiesent current
alarm current
relay output
operation temperature
protection class
housing color
material
weight
dimensions (H x W x D)
approvals
intriscally safe class
art. 31896
ultraviolet flame detector
24 V DC ± 25 %
24 V DC
45 mA
70 mA
2 x 30 V / 1A
-20°C up to +80°C
IP 54
red
aluminium
1400 g
155 mm x 120 mm x 110 mm
VdS G 28425
Germanischer Loyd
FL 800/24V-K-N
ultraviolet flame detector for an earliest fire detection in the
industrial areas and in difficult envoirements
•
•
•
•
for the detection of open fire without smoke development
sikh angle variable 30°, 60° and 90°
sensibility meets EN 54-10 class 1
high speed capability
technical specification
input voltage
operation voltage
quiesent current
alarm current
relay output
operation temperature
housing color
protection class
material
weight
dimensions (H x W x D)
19,2 up to 28,8 V
24 V DC
26 mA
46 mA
2 x 30 V / 1A
-25°C up to +70°C
grey
IP 54
PC-LEXAN
800 g
200 mm x 150 mm x 150 mm
73
www.detectomat.com
6. special detectors
6.5 flame detectors
art. 32075
infrared flame detector
X 9800
technical specification
operation voltage
quiesent current
alarm current
interfaces
relay output
sensitivity
infrared flame detector to ensure the detection of hydrocarbon fires in
industrial applications such as turbines, petrochemie, automotive
industry, projects with high contamination
operation temperature
stock temperature
humidity
•
•
•
protection class
housing color
material
weight
dimensions (H x W x D)
approvals
intriscally safe class
•
•
•
•
•
•
•
•
automatic, optical self-testing
microprocessor controlled heated optics
reliable detection even in case of more than one fault at
the same time
detects a n-heptane fire of 0,1m2 size until a distance of 15 metres
high speed capability - 40 milliseconds
sikh angle 90°
tricolour LED indicates normal operation, fire and fault conditions
mounting plate vibration-free after MIL
event monitoring over built-in data logging
maintenance mode over magnet
modular housing design
art. 30477
ultraviolet flame detector
18 up to 30 V DC
87,5 µA
550 mA
RS485, 4-20mA
2x alarm, 1x fault
N-Heptan: 0,1 mÇ in 15 m
distance: less than 15 sec
Methan: 30 inch flame in 10,5 m
distance: less than 10 sec
-40°C up to +75°C
-55°C up to +85°C
0 up to 95 % - shortly 100 %
humidity in air
IP 66
red
Aluminium
2700 g
119 mm x 122 mm x 246 mm
VdS G 203084
0538 Ex II 2 GD, ATEX 132195,
FM3260
remarks: a shielded cable with a conductor cross section of 0,5mm2
to 2,5mm2 is recommended
X 2200
technical specification
operation voltage
quiesent current
alarm current
interfaces
relay output
sensitivity
ultraviolet flame detector to ensure the detection of non-hydrocarbon
fires in industrial applications such as turbines, hydrogen,
ammunition, silane
operation temperature
stock temperature
humidity
•
•
protection class
housing color
material
weight
dimensions (H x W x D)
approvals
intriscally safe class
•
•
•
•
•
•
•
•
automatic, optical self-testing
reliable detection even in case of more than one fault at
the same time
detects a n-heptane fire of 0,1m2 size until a distance of 18 metres
high speed capability
sikh angle 90°
tricolour LED indicates normal operation, fire and fault conditions
mounting plate vibration-free after MIL
event monitoring over built-in data logging
maintenance mode over magnet
modular housing design
18 up to 30 V DC
104 µA
253 mA
RS485, 4-20mA
2x alarm, 1x fault
N-Heptan: 0,1 mÇ in 18 m
distance: 1 sec
Methan: 30 inch flame in 21 m
distance: 1 sec
-40°C up to +75°C
-55°C up to +85°C
0 up to 95 % - shortly 100 %
humidity in air
IP 66
red
aluminium
2700 g
119 mm x 122 mm x 246 mm
VdS G 203083
0538 Ex II 2 GD, ATEX 132195,
FM3260
remarks: a shielded cable with a conductor cross section of 0,5mm2
to 2,5mm2 is recommended
74
www.detectomat.com
6. special detectors
6.5 flame detectors
art. 32077
ultraviolet/infrared flame detector
Eye 20/20 L
•
•
•
•
•
•
environment-specific programming
high speed capability
sikh angle 90° horizontal and vertically
manual and automatic inserting test mode
high false alarm security
modular housing design
technical specification
operation voltage
quiesent current
alarm current
interfaces
relay output
sensitivity
ultraviolet/infrared flame detector with combined analysis on UV and
IR basis for the safe and failure-free detection of fires
•
•
ultraviolet-infraret dual sensor
reliable detection even in case of more than one fault at
the same time
18 up to 32 V DC
100 mA
150 mA
4-20mA
2x alarm, 1x fault
N-Heptan 15m, Methan 5m,
Benzin 15m, Diesel 11m,
Kerosin 11m, 5 sec.
-40°C up to +70°C
-55°C up to +85°C
up to 95 %
IP 66
grey
aluminium
3700 g
132 mm x 132 mm x 120 mm
pending
ATEX EX II 2G, EExd IIB, FM, CSA,
ATEX, Gost R und GostK
operation temperature
stock temperature
humidity
protection class
housing color
material
weight
dimensions (H x W x D)
approvals
intriscally safe class
6.6 intrisically safe detectors
art. 31163
ex-ionisation smoke detector
IRM Ex S60
•
•
radiation 33,3 kBq
wind speed 10 m per second
technical specification
conventional ionisation smoke detector in ex-proof design
•
•
two-chamber principle
Am 241 as radioactive source
operation voltage
quiesent current
operation temperature
humidity
housing color
material
dimensions (H x Ø)
Ex
approvals
intriscally safe class
17 up to 28 V DC
30 µA by 20 V DC
-10°C up to +60°C
0 - 95 %
white
ABS
42 mm x 100 mm
BAS02, ATEX1288
VdS G 298 044
BAS02, ATEX1288
75
www.detectomat.com
6. special detectors
6.6 intrisically safe detectors
art. 31164
ex-heat detector
WM Ex S60
•
•
two temperature sensors
maximal und differentiated triggering
technical specification
conventional thermal detector in ex-proof design, class 1
art. 31169
base for ex-detector
operation voltage
quiesent current
operation temperature
humidity
housing color
material
dimensions (H x Ø)
approvals
intriscally safe class
17 up to 28 V DC
30 µA by 20 V DC
-10°C up to +60°C
0 - 95 %
white
ABS
42 mm x 100 mm
VdS G 298 047
BAS02, ATEX1288
Meldersockel Ex
detector base in ex-proof design
technical specification
operation temperature
housing colour
material
dimensions (H x Ø)
intriscally safe class
art. 31174
ex-barrier
-10°C up to +60°C
white
ABS
20 mm x 95 mm
BAS02, ATEX1288
Ex-B1
designed for ex-detectors in one ex detector zone
•
•
including reverse battery protection
for top hat rail mounting
technical specification
quiesent current
operation temperature
housing color
material
dimensions (H x W x D)
76
www.detectomat.com
6 mA
-10°C up to +60°C
green
ABS
93 mm x 20 mm x 110 mm
6. special detectors
6.6 intrisically safe detectors
art. 31170
ex manual call point
HFM S65 , Ex
•
•
for ex-areas until zone 0
for using without ex-barrier
technical specification
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x W x D)
approvals
intriscally safe class
19 up to 28 V DC
20 µA
-20°C up to +80°C
IP 66
red
ABS
145 mm x 135 mm x 70 mm
VdS G 295026
BAS02, ATEX1288
conventional ex-proof manual call point
art. 30217
ex multiple tone sounder
DB 5
conventional ex-proofen sounder
•
•
•
included DIN tone meets DIN 33404
26 different tones adjustable
usable with ex barrier only
technical specification
operation voltage
alarm current
sounder output
operation temperature
protection class
housing color
dimensions (H x Ø)
intriscally safe class
art. 30219
ex-barrier
SB SE/24 Ex
designed for ex-sounder DB 5
technical specification
•
operation temperature
housing colour
material
quiesent current
dimensions (H x W x D)
•
•
electrically particularly designed for ex multiple tone
sounder DB5
DIN top hat rail mounting in housing Ex-H
each sounder needs one barrier
24 V DC
12 mA
100 dB
-10°C up to +60°C
IP 65
red
102 mm x 90 mm
BASEEFA-No. 92C2014
Klasse: Eex ia II C
-10°C up to +60°C
green
ABS
6 mA
93 mm x 20 mm x 110 mm
77
www.detectomat.com
6. special detectors
6.6 intrisically safe detectors
art. 31222
ex-beacon, red
BE 24 R EEx
conventional ex-proofen beacon, red
technical specification
•
•
•
•
•
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x Ø)
intriscally safe class
beacon Ex, 24 V DC, red
with yellow aluminium housing and red cover
all purposes beacon with high light performance
stainless steel to protect the cover
flash energy: 15 Joule
art. 31223
ex-beacon, yellow
BE 24 Y EEx
conventional ex-proofen beacon, yellow
technical specification
•
•
•
•
•
operation voltage
alarm current
operation temperature
protection class
housing color
material
dimensions (H x Ø)
intriscally safe class
beacon Ex, 24 V DC, yellow
with yellow aluminium housing and yellow cover
all purposes beacon with high light performance
stainless steel to protect the cover
flash energy: 15 Joule
art. 30218
housing for ex-modules
24 V DC
1,0 A
-20°C up to +40°C
IP 67
red
aluminium
243 mm x 110 mm
II 2G EEx de IIC T6
24 V DC
1,0 A
-20°C up to +40°C
IP 67
yellow
aluminium
243 mm x 110 mm
II 2G EEx de IIC T6
M-1
to integrate ex-barriers, overload protection components and
modules for top had rail mounting
•
•
•
•
to integrate ex-barriers and protocol-interfaces
on-wall mounting
including 35 mm norm rail, which meets DIN EN 50022
up to 5 barriers can be included
technical specification
protection class
housing color
material
dimensions (H x W x D)
78
www.detectomat.com
IP 65
grey
ABS
220 mm x 125 mm x 162 mm
7. home smoke detectors
art. 30458
optical home detector
HDv 3000 O
•
•
•
•
•
•
•
automatic fault monitoring of the measuring chamber as well as
the battery voltage
the acoustic alert is made by an integrated piezo alarm-sounder
(> 85 dB)
a visual and audiable low battery condition is signalled for
30 days
up to 40 detectors can be interlinked for reporting fault and
alarm conditions
the optional plug-in radio module interface offers radio
interlinking for reporting fault and alarm conditions via
(433 MHz and/or. 868 MHz)
the average life span with a 9 V alkaline battery is approximatly
2 years (without interlinking or alarms at 20°C ambient
temperature)
the pack includes the detector base, battery, screws and anchors
technical specification
battery powerd optical home detector for detection and
alarming in domestic applications
•
•
optical smoke detector for the early detection of smoke
private living areas
integreated pre alarm levels for an early smoke verification
art. 30023
optical home detector
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
complies with
9V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
white
ABS
160 g
51 mm x 100 mm
VdS G 202042
DIN 14604
remarks: for the usage of radio modules a lithium ion battery is
recommended
HD 3001 O white
technical specification
battery powerd optical home detector for detection and
alarming in domestic applications
•
features as HDv 3000 O
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
9V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
white
ABS
140 g
42 mm x 95 mm
VdS G 202054 EN 14604
79
www.detectomat.com
7. home smoke detectors
art. 30024
optical home detector
HD 3001 O silver
technical specification
simlilar to HDv 3000 O, design 1, silver
•
features as HDv 3000 O
art. 30123
optical home detector
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
9 V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
silver
ABS
140 g
42 mm x 95 mm
VdS G 202054 EN 14604
HD 3001 O black
technical specification
simlilar to HDv 3000 O, design 1, black
•
features as HDv 3000 O
art. 31837
optical home detector
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
9 V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
black
ABS
140 g
42 mm x 95 mm
VdS G 202054 EN 14604
HD 3004 O white
technical specification
simlilar to HDv 3000 O, design 4, white
•
features as HDv 3000 O
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
80
www.detectomat.com
9 V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
white
ABS
140 g
56 mm x 110 mm
VdS G 202090 EN 14604
7. home smoke detectors
art. 31914
optical home detector
HD 3004 O silver
technical specification
simlilar to HDv 3000 O, design 4, silver
•
features as HDv 3000 O
art. 32015
optical home detector
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
9 V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
silver
ABS
160 g
56 mm x 110 mm
VdS G 202090 DIN 14604
HD 3005 O white
technical specification
simlilar to HDv 3000 O, design 5, white
•
features as HDv 3000 O
art. 32004
optical home detector
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
9 V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
white
ABS
160 g
56 mm x 110 mm
VdS G 202091 DIN 14604
HD 3005 O silver
technical specification
simlilar to HDv 3000 O, design 5, silver
•
features as HDv 3000 O
operation voltage
quiesent current
alarm current
interfaces
sensitivity
operation temperature
humidity
air speed
housing colour
material
weight
dimensions (H x Ø)
approvals
9 V DC
< 16 µA
5 mA
radio link and wire link interface
< 0,15 dB / m
-10°C up to +60°C
95 % RH / 40°C
max. 20 m / s
silver
ABS
160 g
56 mm x 110 mm
VdS G 202091 EN 14604
81
www.detectomat.com
7. home smoke detectors
art. 30933
radio link module
FM 868
•
•
with the module the detectors can be cascade interlinked
without a panel
automatic amplifying of the radio signal via the integrated
repeater function
technical specification
bidirectional radio module to interlink home detectors in cascaded
networks in the transmitting frequency of 868MHz
•
•
working area in frequency band 868 MHz
bidirectional controlling function in case of alarm, signalising of
all connected detectors
art. 31674
wireless fire control panel
alarm current
interfaces
operation temperature
humidity
weight
37 mA
radio link interface to the
home detector
-10°C bis +60°C
95 % RH / 40°C
100 g
RCP 6
•
•
•
•
4 potential-free outputs, freely programmable
a separate 230 V plug power-pack is included in the delivery
emergency batteries 8 x 1,5 V are included
LCD display
technical specification
microprcessor controlled radio panel to control home detetectors by
wireless network over 433 MHz
•
•
•
working area in frequency band 433 MHz
6 zones
connection up to 100 home smoke detectors via the module
433 MHz
art. 30947
radio link module
input voltage
frequency
operation voltage
emergency power
quiesent current
alarm current
display
zone LED´s
relay output
operation temperature
stock temperature
humidity
protection class
housing colour / front colour
material
weight
dimensions (H x W x D)
230 V AC
50 / 60 Hz
12 V AC
8 x 1,5 V batteries
30 mA
50 mA
LCD
6 zones
4 x change over contact
0°C up to +60°C
-10°C up to +60°C
max. 70 %
IP 20
grey / silver
ABS
1000 g
170 mm x 170 mm x 55 mm
FM 433
•
with the module the home smoke detectors can be connected to
the fire control panel RCP6
technical specification
alarm current
interfaces
wireless module to connect home detectors to the wireless fire
control panel RCP6 in the transmitting frequency of 433 MHz
•
working area in frequency band 433 MHz
operation temperature
humidity
weight
82
www.detectomat.com
37 mA
radio link interface to the
home detector
-10°C up to +60°C
95 % RH / 40°C
100 g
8. signalling devices
8.1 signalling devices for loop3000
art. 31836
loop sounder, red
LS 3300 R
•
•
•
2 different tones adjustable (including DIN tone)
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
technical specification
low current multiple tone sounder
directly powered by the loop3000, red
•
•
•
direct addressable via the loop3000
integrated bidirectional short circuit isolator
addressable spur connection via T-branch
art. 32012
loop sounder, white
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
15 up to 30 V loop powered
5 mA
max. 97 dB
-10°C up to +60°C
IP 43
red
ABS
340 g
100 mm x 101 mm
LS 3300 W
•
•
•
2 different tones adjustable (including DIN tone)
automatic addressing (soft-addressing)
manual addressing (EasyCheck)
technical specification
low current multiple tone sounder
directly powered by the loop3000, white
•
•
•
direct addressable via the loop3000
integrated bidirectional short circuit isolator
addressable spur connection via T-branch
art. 32060
loopsounder kit
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
15 up to 30 V loop powered
5 mA
max. 97 dB
-10°C up to +60°C
IP 43
white
ABS
340 g
100 mm x 101 mm
LS 3300 VLC
•
shallow base for lateral and rear cable entry
technical specification
low current multiple tone
sounder directly powered
by the loop3000 via control
modul, white
•
•
•
•
direct addressable via the loop3000
multiple tone sounder with 32 different tones
(including DIN tone) adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
complies with
440 up to 2900 Hz
15 up to 30 V loop powered
5 mA
max. 97 dB
-10°C up to +60°C
IP 43
white
ABS
250 g
27 mm x 117 mm
EN 54
83
www.detectomat.com
8. signalling devices
8.1 signalling devices for loop3000
art. 32067
cover for sounder, color red
AD R
art. 32068
cover for sounder, color white
AD W
art. 32061
loopsounder base kit
LS 3300 SBK
low current multiple tone sounder
directly powered by the loop3000
via control modul, integreated base
for addressable detectors of the
series loop3000, white
•
•
•
•
•
•
direct addressable via the loop3000
including detector base for all
detectors of the series loop3000
multiple tone sounder with 32 different
tones (including DIN tone) adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
shallow base for lateral and rear cable entry
art. 30204
sound unit
•
detector not included
technical specification
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
complies with
440 up to 2900 Hz
15 up to 30 V loop powered
5 mA
max. 97 dB
-10°C up to +60°C
IP 43
white
ABS
250 g
45 mm x 117 mm
EN 54
SDM 3300 R
•
shallow base for lateral and rear cable entry
technical specification
sounder to use in the loop3000,
low powered multiple-tone sounder
with sound-module, according to
DIN 33404 addressable connection
with external voltage
•
•
•
•
•
•
direct connection to the loop3000
integrated automatic addressing-unit
integrated bidirectional short circuit isolator
addressable spur connection via T-branch
external voltage supply 24 V necessary
internal sound levels adjustable
art. 32058
loop beacon, red
frequency
operation voltage
quiesent current
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
complies with
500 up to2850 Hz
15 up to 30 V
250 µA
9 up to 29 mA
111 dB
-10°C up to +60°C
IP 54
red
ABS
340 g
93 mm x 93 mm
EN 54
LB-3300-VXB-R
technical specification
low current beacon unit directly
powered by the loop3000 via
control modul
•
•
•
low current beacon
white housing with red light cover
brightness at 5 mA 0,7 watt and at 3 mA 0,4 watt
frequency
operation voltage
alarm current
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
complies with
84
www.detectomat.com
1 Hz
15 up to 30 V loop powered
5 mA
-10°C up to +60°C
IP 43
white
ABS
145 g
60 mm x 95 mm
EN 54
8. signalling devices
8.1 signalling devices for loop3000
art. 32090
loop beacon, orange
LB 3300 VXB O
technical specification
low current beacon unit directly
powered by the loop3000 via
control modul
•
•
•
low current beacon
white housing with orange light cover
brightness at 5 mA 0,7 watt and at 3 mA 0,4 watt
frequency
operation voltage
alarm current
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
complies with
1 Hz
15 up to 30 V loop powered
5 mA
-10°C up to +60°C
IP 43
white
ABS
145 g
60 mm x 95 mm
EN 54
8.2 conventional signalling devices
art. 32051
multiple tone sounder, red
VTG-32-SB R
•
shallow base for lateral and rear cable entry
technical specification
low powered multiple-tone sounder,
colour: red, modern technology with
32 different tones
•
•
•
multiple tone sounder with 32 different tones (including DIN tone)
adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
art. 32053
multiple tone sounder, white
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
approvals
complies with
440 up to 2900 Hz
15 up to 35 V DC
9 up to 36 mA
max. 111 dB
-20°C up to +70°C
IP 43
red
ABS
220 g
85 mm x 94 mm
VdS G 205137
EN 54
VTG-32-SB W
•
shallow base for lateral and rear cable entry
technical specification
low powered multiple-tone sounder,
colour: white, modern technology with
32 different tones
•
•
•
multiple tone sounder with 32 different tones (including DIN tone)
adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
approvals
complies with
440 up to 2900 Hz
15 up to 35 V DC
9 up to 36 mA
max. 111 dB
-20°C up to +70°C
IP 43
white
ABS
220 g
85 mm x 94 mm
VdS G 205137
EN 54
85
www.detectomat.com
8. signalling devices
8.2 conventional signalling devices
art. 32052
multiple tone sounder, red, IP 65
VTG-32-DB R
•
shallow base for lateral and rear cable entry
technical specification
low powered multiple-tone sounder
colour: red, modern technology with
32 different tones, class of protection: IP 65
•
•
•
multiple tone sounder with 32 different tones
(including DIN tone) adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
art. 32054
multiple tone sounder, white, IP 65
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
approvals
complies with
440 up to 2900 Hz
15 up to 35 V DC
9 up to 36 mA
max. 111 dB
-20°C up to +70°C
IP 65
red
ABS
250 g
102 mm x 94 mm
VdS G 205137
EN 54
VTG-32-DB W
•
shallow base for lateral and rear cable entry
technical specification
low powered multiple-tone sounder
colour: white, modern technology with
32 different tones, class of protection: IP 65
•
•
•
multiple tone sounder with 32 different tones
(including DIN tone) adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
art. 32055
base sounder
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
approvals
complies with
440 up to 2900 Hz
15 up to 35 V DC
9 up to 36 mA
max. 111 dB
-20°C up to +70°C
IP 65
white
ABS
250 g
102 mm x 94 mm
VdS G 205137
EN 54
Verso 32 Tone
•
shallow base for lateral and rear cable entry
technical specification
low powered multiple-tone sounder,
colour: white, modern technology with
32 different tone
•
•
•
multiple tone sounder with 32 different tones (including DIN tone)
adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
complies with
86
www.detectomat.com
440 up to 2900 Hz
15 up to 35 V DC
9 up to 36 mA
max. 111 dB
-20°C up to +70°C
IP 43
white
ABS
250 g
27 mm x 117 mm
EN 54
8. signalling devices
8.2 conventional signalling devices
art. 32067
cover for sounder, color red
AD R
art. 32068
cover for sounder, color white
AD W
art. 30216
symphony tone sounder
SYS 120 R
technical specification
multiple-tone sounder,
colour: red, modern technology
with 32 different tones
•
•
•
•
multiple tone sounder with
32 different tones (including DIN tone)
adjustable via DIP button
tones in the frequency-band of 500 Hz
up to 2850 Hz are synchronizable
3 sound levels adjustable
strong sound with up to 120 dB
art. 31664
voice sounder
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
weight
dimensions (H x W x D)
approvals
complies with
500 up to 2850 Hz
9 up to 28 V DC
230 up to 290 mA
max. 120 dB
-25°C up to +55°C
IP 43
red
340 g
106 mm x 106 mm x 95 mm
VdS G 206026
EN 54
CLA R
technical specification
sounder with voice-announcement,
high voice quality, standard
announcement stored
•
•
•
•
•
•
•
•
sounder with voice announcement
multifunction alarm sounder
adjustable volume
base is compatible to sounders and beacons
high quality of the sound rendition
standard announcements are stored in the database
automatic synchronization
low current consumption
art. 31665
voice sounde
input voltage
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
weight
dimensions (H x Ø)
complies with
18 up to 30 V DC
18 up to 30 V DC
20 mA
102 dB
-10°C up to +55°C
IP 65
red
265 g
83 mm x 95 mm
EN 54
CLA W
technical specification
sounder with voice-announcement,
high voice quality, standard
announcement stored
•
•
•
•
•
•
•
•
sounder with voice announcement
multifunction alarm sounder
adjustable volume
base is compatible to sounders and beacons
high quality of the sound rendition
standard announcements are stored in the database
automatic synchronization
low current consumption
input voltage
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
weight
dimensions (H x Ø)
approvals
complies with
18 up to 30 V DC
18 up to 30 V DC
20 mA
102 dB
-10°C up to +55°C
IP 65
white
265 g
83 mm x 95 mm
pending
EN 54
87
www.detectomat.com
8. signalling devices
8.2 conventional signalling devices
art. 31193
LED indicator
PA
•
•
•
alarm indicator for flush mounted detectors
connection to the detector base
on-wall mounting
technical specification
LED indicator for alarm display of the automatic detectors
series loop3000 and CT
art. 31195
LED indicator
alarm current
housing colour
material
dimensions (H x W x D)
4 mA
white
ABS
84 mm x 84 mm x 35 mm
PA2-VdS
•
•
connection to the detector base
on-wall mounting
technical specification
LED indicator for alarm display of the
automatic detectors series loop3000 and CT
•
alarm indicator for flush mounted detectors
art. 30178
LED indicator, flush-mounting
alarm current
housing colour
material
dimensions (H x W x D)
approvals
2,5 mA
white
ABS
86 mm x 86 mm x 45 mm
VdS G 294052
PA-uP
•
•
•
alarm indicator for flush mounted detectors
connection to the detector base
flush mounting, installation hole 22 mm diameter
technical specification
LED indicator for alarm display of the automatic detectors
series loop3000 and CT
art. 40100
beacon, red
alarm current
housing colour
material
dimensions (H x Ø)
3 mA
white
ABS
52 mm x 26 mm
BE 24
technical specification
conventional beacon unit, red
•
•
•
available in the colours red, orange, green and blue
brightness 2 joule at 24 V and 1 joule at 12 V
IP rating 65 will be achieved with base 40059 red or 40060 white
frequency
operation voltage
alarm current
operation temperature
protection class
material
dimensions (H x Ø)
approvals
1 Hz
12 / 24 V DC
155 mA
-10°C up to +60°C
IP 54, with additional base IP 65
ABS
72 mm x 93 mm
VdS G 296014
remarks: when ordering please indicate the color and the operation
voltage of the calotte
88
www.detectomat.com
8. signalling devices
8.2 conventional signalling devices
art. 30228
round beacon
RBE 24
technical specification
conventional round beacon unit, red
frequency
operation voltage
alarm current
operation temperature
protection class
housing colour
material
dimensions (H x Ø)
•
•
remarks: when ordering please indicate the color of the calotte
available in the colours red and orange
brightness 5 joule at 24 V
art. 32056
beacon, red
1 Hz
24 V DC
200 mA
-10°C up to +60°C
IP 54
white
ABS
135 mm x 108 mm
VXB-1-SB-WB-RL
•
brightness at 5 mA 0,7 watt and at 3 mA 0,4 watt
technical specification
low current beacon unit, red housing, red light
frequency
operation voltage
alarm current
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
•
•
remarks: when ordering please indicate the color of the calotte
low current beacon
available in the colours red and orange
art. 32057
beacon IP 65
1 Hz
20 up to 35 V
3 up to 5 mA
-20°C up to +70°C
IP 43
white
ABS
145 g
60 mm x 95 mm
VXB-1-DB-WB-RL
•
brightness at 5 mA 0,7 watt and at 3 mA 0,4 watt
technical specification
low current beacon unit, white housing, red light, IP 65
frequency
operation voltage
alarm current
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
•
•
remarks: when ordering please indicate the color of the calotte
low current beacon
available in the colours red and orange
1 Hz
20 up to 35 V
3 up to 5 mA
-20°C up to +70°C
IP 65
white
ABS
165 g
80 mm x 95 mm
89
www.detectomat.com
8. signalling devices
8.2 conventional signalling devices
art. 32062
sounder beacon combination, white
VTB-32-SB W
low powered multiple-tone sounder with 32 different tones,
colour: white, combined with beacon red
•
•
•
•
multiple tone sounder with 32 different tones (including DIN tone)
adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
brightness at 5 mA 0,7 watt and at 3 mA 0,4 watt
technical specification
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
art. 32063
sounder beacon combination, white, IP 65
440 up to 2900 Hz
15 up to 35 V DC
14 up to 41 mA
max. 109 dB
-20°C up to +70°C
IP 43
white
ABS
233 g
90 mm x 94 mm
VTB-32-DB W
low powered multiple-tone sounder with 32 different tones,
colour: white, combined with beacon red, IP 65
•
•
•
•
multiple tone sounder with 32 different tones (including DIN tone)
adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz are
synchronizable
3 sound levels adjustable
brightness at 5 mA 0,7 watt and at 3 mA 0,4 watt
technical specification
frequency
operation voltage
alarm current
noise
operation temperature
protection class
housing colour
material
weight
dimensions (H x Ø)
90
www.detectomat.com
440 up to 2900 Hz
15 up to 35 V DC
14 up to 41 mA
max. 109 dB
-20°C up to +70°C
IP 65
white
ABS
258 g
107 mm x 94 mm
9. door magnets and accessoires
art. 30411
power supply 450 mA
SV 04
•
LED indicator for operation display
technical specification
power supply 450 mA for door magnets
•
integreated short circuit protection
art. 30412
power supply 800 mA
input voltage
frequency
operation voltage
external user output
operation temperature
protection class
housing colour
material
dimensions (H x W x D)
approvals
230 V AC
50 Hz +/- 10 %
24 V DC
400mA
-10 up to +40°C
IP 20
silver
sheet steel
115 mm x 80 mm x 50 mm
DIBT Z6.5-1335, VdS approved
SV 08
•
LED indicator for operation display
technical specification
power supply 800 mA for door magnets
•
integreated short circuit protection
art. 30410
door control panel
input voltage
frequency
operation voltage
external user output
operation temperature
protection class
housing colour
material
dimensions (H x W x D)
approvals
230 V AC
50 Hz +/- 10 %
24 V DC
max 800mA
-10 up to +40°C
IP 20
white
sheet steel
160 mm x 105 mm x 55 mm
DIBT Z6.5-1335, VdS approved
TSZ 0400
•
•
•
•
•
•
up to 3 panels linkable
integreated short circuit protection
LED indicators for operation, alarm and fault display
up to 10 detectors connectable
up to 12 door magnets connectable
usable in ex-areas with accessoires
technical specification
microprcessor controlled panel to control fire doors, door magnets
and detectors
•
•
•
•
integreated power supply for detectors and door magnets
alarm evaluation and controlling functions
integreated reset function
additional external output for connection of signalling devices
input voltage
frequency
operation voltage
relay output
external user output
operation temperature
protection class
housing colour
material
dimensions (H x W x D)
approvals
230 V AC
50 Hz +/- 10 %
24 V DC
2 change over 30V / 1A
max 800mA
0 up to +40°C
IP 42
greywhite, RAL 9002
ABS
185 mm x 233 mm x 93 mm
DIBT Z6.5 - 1646, VdS approved
91
www.detectomat.com
9. door magnets and accessoires
art. 31236
optical detector with relay base
RM3000
conventional optical smoke detector, complies with EN 54 part 7
specification and relay base for connection on door control panels
•
•
•
integreated relay base
3 times alarm evaluation for controlling function
LED indicator for operation, alarm and fault display
technical specification
operation voltage
quiesent current
alarm current
relay output
operation temperature
protection class
housing colour
material
dimensions (H x Ø)
approvals
art. 30417
manual activation button
18 up to 28 V DC
24 mA
62 mA
1 change over 50V / 1A
-20°C up to +60°C
IP 43
white
ABS
50 mm x 100 mm
DIBT Z6.5-1335, VdS G 200 107
HT aP
for door control units with on-wall mounting
technical specification
operation temperature
housing colour
material
dimensions (H x W x D)
art. 30418
manual activation button
-20°C up to +60°C
red
ABS
63 mm x 63 mm x 37 mm
HT uP
for door control units with flush-mounting
technical specification
operation temperature
housing colour
material
dimensions (H x W x D)
92
www.detectomat.com
-20°C up to +60°C
red
ABS
80 mm x 80 mm x 33 mm
9. door magnets and accessoires
art. 30428
door magnet
EM GD 60 F 26
•
•
•
•
•
input protection via diode
polarisation protected
peel adhesion 700N
power on time 100%
magnet diameter 60 mm
technical specification
door magnet for wall mounting, for door holding
•
integrated activation button
art. 30422
door magnet
operation voltage
alarm current
operation temperature
protection class
colour
material
dimensions (H x W x D)
approvals
24 V DC ± 10 %
67 mA
-20°C up to +60°C
IP 40
grey
steel
30 mm x 55 mm x 93 mm
DIBT Z6.5 1335, VdS approved
EM GD 60 K 70
•
•
•
•
•
input protection via diode
polarisation protected
peel adhesion 700N
power on time 100%
magnet diameter 60 mm
technical specification
door magnet for wall mounting with plastic-bottom, for door holding
•
integrated activation button
art. 30423
door magnet
operation voltage
alarm current
operation temperature
protection class
colour
material
dimensions (H x Ø)
approvals
24 V DC ± 10 %
67 mA
-20°C up to +60°C
IP 40
grey
steel/ABS
70 mm x 82 mm
DIBT Z.6.5-1335, VdS approved
EM GD 60 S 175
•
•
•
•
•
•
input protection via diode
polarisation protected
peel adhesion 700N
power on time 100%
magnet diameter 60mm
length 175mm, 90° deviated 137 mm
technical specification
panning-head magnet with turnable
head to mount at walls, ceilings or floors
•
integrated activation button
operation voltage
alarm current
operation temperature
protection class
colour
material
dimensions (H x Ø)
approvals
24 V DC ± 10 %
67 mA
-20°C up to +60°C
IP 40
grey
steel
175 mm x 96 mm
DIBT Z.6.5-1335, VdS approved
93
www.detectomat.com
9. door magnets and accessoires
art. 30424
door magnet
EM GD 60 S 325
•
•
•
•
peel adhesion 700N
power on time 100%
magnet diameter 60 mm
length 325mm, 90° deviated 287 mm
technical specification
panning-head magnet
with turnable head to mount
at walls, ceilings or floors
•
•
•
integrated activation button
input protection via diode
polarisation protected
art. 30425
door magnet
operation voltage
alarm current
operation temperature
protection class
colour
material
dimensions (H x Ø)
approvals
24 V DC ± 10 %
67 mA
-20 up to +60°C
IP 40
light grey
steel
325 mm x 96 mm
DIBT Z.6.5-1335, VdS approved
EM GD 60 S 475
•
•
•
•
peel adhesion 700N
power on time 100%
magnet diameter 60 mm
length 475mm, 90° deviated 437 mm
technical specification
panning-head magnet
with turnable head to
mount at walls, ceilings
or floors
•
•
•
integrated activation button
input protection via diode
polarisation protected
art. 30434
door magnet
operation voltage
alarm current
operation temperature
protection class
colour
material
dimensions (H x Ø)
approvals
24 V DC ± 10 %
67 mA
-20 up to +60°C
IP 40
light grey
steel
475 mm x 96 mm
DIBT Z.6.5-1335, VdS approved
EM GD 60 FB
•
•
•
•
•
integrated activation button
input protection via diode
polarisation protected
peel adhesion 700N
power on time 100%
technical specification
door magnet with a robust housing of aluminium for base-mounting
operation voltage
alarm current
operation temperature
protection class
colour
material
dimensions (H x W x D)
approvals
94
www.detectomat.com
24 V DC ± 10 %
67mA
-20 up to +60°C
IP 40
black
aluminium
100 mm x 165 mm x 107 mm
DIBT Z.6.5-1335, VdS approved
9. door magnets and accessoires
art. 30436
door magnet
EM GD 70 Ex
technical specification
ex-proof door magnet
usable in ex areas with
protection class zone 1 and 2
•
•
•
•
•
•
ex proof housing
connectable via
terminal blocks
input protection via diode
polarisation protected
peel adhesion 1450N
power on time 100%
art. 30437
anchor plate
operation voltage
alarm current
operation temperature
protection class
colour
material
dimensions (H x W x D)
approvals
complies with
intriscally safe class
24 V DC
70mA
-20°C up to +40°C
IP 66
grey
steel
110 mm x 75 mm x 43 mm
DIBT Z-6.5-1335,
Ex II 2G Eex m II T6, IP 66
Ex II 2G EExem II T6
Eex m/e IIT6
AP GD 60 G 16
•
•
•
up to 10° movable
zinc housing
plate diameter 64 mm
technical specification
flexible anchor plate with rubber bearing usable for the connection
between door magnet and fire door
art. 30438
anchor plate
colour
material
dimensions (H x W x D)
zinc
steel
65 mm x 65 mm x 16 mm
AP GD 60 W 50
•
•
•
up to 60° movable
zinc housing
plate diameter 64 mm
technical specification
colour
material
dimensions (H x W x D)
black
steel
65 mm x 65 mm x 51 mm
flexible anchor plate with rubber bearing and angle joint usable for
the connection between door magnet and fire door
art. 30439
anchor plate
AP GD 60 T 80
•
•
•
•
for heavy doors and gates
robust black housing
flexible anchor plate diameter 64 mm
elasticity strength approximately 100 N at 20 mm lift
technical specification
telescope anchor plate with damper usable for the connection
between door magnet and fire door
colour
material
dimensions (H x Ø)
black
steel
85 mm x 80 mm
95
www.detectomat.com
10. detector testing devices
art. 31956
smoke detector test & removal set
SOLO 812
kit includes the following:
•
•
•
•
•
art. 14008
aerosol smoke dispenser
1 fibreglass telescopic extension pole 4,50 metres
1 fibreglass extension pole 1,13 metres
1 universal removal tool
1 aerosol smoke dispenser
1 protective carrying / storage bag
SOLO 330
smoke dispenser for the release of smoke test aerosol for efficient
activation of detectors
•
•
•
art. 30398
heat detector tester
clear cup - allows view of detector LED
spring loaded mechanism for effectiv, economic aerosol delivery
touch sensitiv - ideal for suspended ceilings
SOLO 461
wire free test set for heat detectors including:
•
•
•
art. 14007
detector removal tool
cordless heat detector tester
2 battery batons
1 fast charger
SOLO 200
detector removal tool for easy replacement of all detectors
96
www.detectomat.com
10. detector testing devices
art. 14006
telescope pole
SOLO 100
telescope pole, expandable in 4 sections
•
art. 30193
extension pole
fibreglass extension pole 1,13 metres
art. 14010
bag for test-set
4 section fibreglass telecope pole expandable from
1,20m up to 4,50m
SOLO 101
•
maximum applicable 2 pieces each telescope bar
SOLO 610
carrying / storage bag for test equipment
•
•
designed to fit all test equipment
separate pole bag included
technical specification
dimensions (H x W x D)
art. 40055
testaerosol
460 mm x 45 mm x 180 mm
TA 300
for smoke detectors, 300 ml
art. 31845
testaerosol
SOLO A3
for smoke detectors, 250 ml
97
www.detectomat.com
Article index
art.
Typ
Description
14006
telescope pole
SOLO 100
14007
14008
14010
30003
30007
30008
30009
30010
30011
30014
30015
30021
30022
30023
30024
30025
30026
30077
30078
30079
30087
30088
30092
30096
30097
30098
30099
30106
30111
30112
30113
30114
30115
30116
30118
30119
30120
30122
30123
30124
30128
30131
30136
30137
30138
30139
30143
30144
30145
30146
30151
30155
30156
30164
30167
30168
30169
30178
30187
30188
30189
30190
30191
30193
30200
30201
30204
30205
30209
30210
detector removal tool
aerosol smoke dispenser
bag for test-set
wireless optical smoke detector
optical smoke and heat detector
heat detector
optical smoke detector
heat detector, isolator
optical smoke detector, isolator
heat detector
optical smoke detector
optical smoke and heat detector, isolator
multisensor detector
optical home detector
optical home detector
WGW 3300
WGW 3300
Relay board 8 change over
aspiration smoke detector
CO gas and heat detector, isolator
bitbus interface
LED indicator modul
optical smoke detector, isolator
conventional interface redundant 8 fire zones
extension module
LED indicator modul
mount in printer including paper storage
mount in printer
Extinguishing control modul
Redundant main board processor
Redundant main board processor
extinguishing interface
OC control module
connection board
monitored module for 8 outputs
bitbus CPU
extension for BitBus CPU, 32 open collector outputs
extension for BitBus CPU, 16 relay outputs
optical home detector
BitBus amplifier
BitBus LED indicator extension
power supply 192 W
detectomat programming tool
software-expansion-dongle
modem
Bitbus programming tool
Visual detect basis software
Visual detect user expansion
Visual detect expansion panel
Visual detect operation expansion
battery 12 V / 45 Ah
battery 12 V / 12 Ah
battery 12 V / 18 Ah
mounting plate
19" front panel 64
19" front panel 128
19" front panel 192
LED indicator, flush-mounting
detector mounting adapter
detector flap-mounting adapter
detector distance-mounting adapter
wall bracket
wall bracket
extension pole
in-/output module
2-loop interface redundant
sound unit
conventional zone module
2-loop interface
conventional interface for 8 fire zones
SOLO 200
SOLO 330
SOLO 610
WL 3200 O
PL 3200 OT
PL 3200 T
PL 3200 O
PL 3300 T
PL 3300 O
CT 3000 T
CT 3000 O
PL 3300 OT
CT 3000 OT
HD 3001 O white
HD 3001 O silver
wireless gateway
HFM EG-Gx
RL 58
ASD-20
PL 3300 CDBT
CP BBI
CP ZM 8
PL 3300 O/K
CP CLI X2-R
CP ECB
CP ZM 32
PIP 1
PIP 2
CP ETB X1
CP CPU X2-R
CP CPU X1-R
CP SIE
CP AM 32
CP AM AP
SC 8
BB-CPU
BB-32
BB-16
HD 3001 O black
BB-R
BB-LED
NT 8
DPT 3000
D 3000
RM MO
BPT
VD Basic 11
VD UE 1
VD PE 1
VD CE 1
B 12/ 45Ah
B 12/ 12Ah
B 12/ 18Ah
MP
19" FP-1
19" FP-2
19" FP-3
PA-uP
MKBD
MKK
MAK
WA4
WA2
SOLO 101
IOM 3311
DLI 3240 X2-R
SDM 3300 R
TCM 3300
DLI 3240 X1-2L
CP CLI X1
98
www.detectomat.com
page
97
96
96
97
59
38
37
33
37
33
42
39
38
42
79
80
59
55
18
65
39
26
9, 10
36
15
15
15, 16
10, 16, 20
4, 10, 12, 16, 20
10
17
11
19
19
19
18
26
26
26, 27
80
27
27
21
29
29
23
26, 29
31
32
32
32
22
21
22
16
16
16
16
88
47
47
48
48
48
97
56
14
84
58
7
9
Article index
art.
Typ
Description
30211
30216
30217
30218
30219
30228
30301
30321
30335
30336
30337
30386
30398
30410
30411
30412
30417
30418
30422
30423
30424
30425
30428
30434
30436
30437
30438
30439
30458
30461
30469
30471
30473
30474
30477
30479
30488
30501
30503
30513
30523
30525
30545
30546
30551
30552
30555
30556
30567
30568
30569
30926
30927
30933
30941
30947
30956
30977
30980
30981
31024
31059
31060
31061
31062
31069
31083
31087
31088
31091
31092
output module
SYS 120 R
ex multiple tone sounder
housing for ex-modules
ex-barrier
round beacon
detector base
base for overvoltage protection modules
Loop protection module
Conventional protection module
Bitbus protection module
Adapter for LED indicator modul
heat detector tester
door control panel
power supply 450 mA
power supply 800 mA
manual activation button
manual activation button
door magnet
door magnet
door magnet
door magnet
door magnet
door magnet
door magnet
anchor plate
anchor plate
anchor plate
optical home detector
battery 12 V / 65 Ah
detector relay base
power supply 120 W
infrared beam detector
infrared beam detector
ultraviolet flame detector
labelling tag for detector base
optical smoke detector, isolator, silver
I-Check 3000 software
sensor cable detector
mini in-/output module
detector base, black
optical smoke detector, isolator, black
optical smoke detector, white
optical smoke detector, silver
optical smoke detector, white
optical smoke detector, silver
optical smoke detector, isolator, white
optical smoke detector, isolator, silver
optical smoke detector, isolator, white
optical smoke detector, isolator, silver
manual call point, chinese
detector base, silver
ground circuit module
radio link module
conventional fire control panel
radio link module
optical smoke detector, isolator, white
optical smoke detector
sensor cable red
sensor cable black
BitBus computer interface ISA-Slot
manual call point, ABS
manual call point, ABS
manual call point, ALU
manual call point, ALU
glass for manual call point
manual call point, IP 66
manual call point, ALU, blue
manual call point, ALU, yellow
weatherproof housing
weatherproof housing
OMS 3301
symphony tone sounder
DB 5
M-1
SB SE/24 Ex
RBE 24
SDB 3000
CT B
CT ME 48
CT ME / C 24
CT ME 5
CP ADB 48
SOLO 461
TSZ0400
SV 04
SV 08
HT aP
HT uP
EM GD 60 K 70
EM GD 60 S 175
EM GD 60 S 325
EM GD 60 S 475
EM GD 60 F 26
EM GD 60 FB
EM GD 70 Ex
AP GD 60 G 16
AP GD 60 W 50
AP GD 60 T 80
HDv 3000 O
B 12/ 65Ah
DRB 3000
NT 5
SPB-E IR BD
SRA-ET IR BD-R
X 2200
MBC
PL 3301 O silver
I-Check 3000
SKM-03.01
AMD 3311
SDB 3000 black
PL 3301 O black
CT 3004 O white
CT 3004 O silver
CT 3005 O white
CT 3005 O silver
PL 3304 O white
PL 3304 O silver
PL 3305 O white
PL 3305 O silver
PL 3300 MCP-kit
SDB 3000 silver
CP EM
FM 868
BMZ 6
FM 433
PL 3301 O white
CT 3000 O/K
SKM-KRT
SKM-KSW
BBI PC
PL 3300 PBD-ABS-B
PL 3300 PBD-ABS-Y
PL 3300 PBD- ALU-B
PL 3300 PBD-ALU-Y
HFM EG-B
CT 3000 PDB-IP66-R
CT 3000 PBD-ALU-BD
CT 3000 PBD-ALU-YD
WG-R
WG-B
page
57
87
77
78
77
89
43
22
23
23
23
9, 10
96
91
91
91
92
92
93
93
94
94
93
94
95
95
95
95
79
22
44
21
70
71
74
47
34
29
72
57
43
34
42
41
41
41
34
35
35
35
53
43
9
82
32
82
34
40
72
72
28
49
50
51
51
55
54
53
54
55
55
99
www.detectomat.com
Article index
art.
Typ
Description
31095
31096
31114
31115
31117
31118
31133
31135
31136
31138
31140
31141
31143
31145
31146
31147
31148
31149
31151
31152
31153
31154
31155
31156
31163
31164
31169
31170
31174
31181
31191
31193
31195
31222
31223
31236
31312
31315
31318
31320
31476
31482
31486
31589
31596
31613
31620
31621
31622
31625
31626
31627
31640
31651
31654
31664
31665
31668
31669
31674
31675
31676
31684
31698
31817
31836
31837
31845
31861
31867
31875
infrared beam detector
reset module
Stratos HSSD-2 standard detector
Stratos HSSD-2 standard detector and control module
Stratos HSSD-2 control module
Stratos Micra 25 including mounting base
Stratos asirating pipe 3/4"
Stratos 45° deg elbow pipe
Stratos 90° bend
Stratos socket
Stratos T-piece
Stratos socket union
Stratos end cap
Stratos pipe clip, red
Stratos pipe clip black
Stratos ABS solvent cement
Stratos pipe cleaner
Stratos sampling hole warning stickers
Stratos nylon tube, red
Stratos nylon tube, white
Stratos in-line remote sampling point adapter
Stratos end cap adaptor
Stratos in-line smapling point
Stratos patress sampling point
ex-ionisation smoke detector
ex-heat detector
base for ex-detector
ex manual call point
ex-barrier
base for humid areas
housing for air ducts
LED indicator
LED indicator
ex-beacon, red
ex-beacon, yellow
optical detector with relay base
2-loop interface redundant
LCD repeater panel
universal expansion housing
universal expansion housing
Stratos Micra 100 including mounting base
EasyCheck
infrared beam detector
optical smoke detector, silver
parallel indicator display
Stratos plug sampling point assembly
fanstening clamp
BitBus - fibre optical interface
fibre optical cable converter
loop tester
radio field analyzer
wireless input module
mini output module
manual call point, ABS, blue
Visual detect interface management system
voice sounder
voice sounder
manual call point, ALU
manual call point, ABS
wireless fire control panel
manual call point, ABS, red
manual call point, ALU, red
flush-mounting adapter silver
wall mount base adapter
1-loop interface
loop sounder, red
optical home detector
testaerosol
infrared beam detector
Stratos HSSD-2 standard detector without display
base with heating
FR 2000
RM95
HSSD-2 M
HSSD-2 M-S
HSSD-2 S
Micra 25
STR-R
STR-W45
STR-B90
STR-M
STR-T
STR-V
STR-E
STR-C
STR-CA
STR-SK
STR-RE
STR-WA
STR-KR
STR-KW
STR-MK
STR-EK
STR-KK
STR-KB
IRM Ex S60
WM Ex S60
Meldersockel Ex
HFM S65, Ex
Ex-B1
FRS
LKMG
PA
PA2-VdS
BE 24 R EEx
BE 24 Y EEx
RM3000
DLI 3240 X1-R
LCD-Tableau
UZG-1
UZG-2
Micra 100
EC 3000
FR 100 RV
CT 3001 O silver
ZPA2002
STR-SK
SK-LS
LCON-1
LCON-2
LT 3000
RFA 3000
WL 3210 EM
OMS 3301mini
CT 3000 PBD-ABS-B
VD M I
CLA R
CLA W
PL 3300 PBD-ALU-R
PL 3300 PBDH-ABS-R
RCP 6
CT 3000 PBDH-ABS-R
CT 3000 PBDH-ALU-R
DR45
APS
DLI 3240 X1-1L
LS 3300 R
HD 3004 O white
SOLO A3
FR 50 RV
HSSD-2 MOD
APSB
100
www.detectomat.com
page
70
70
62
63
63
64
65
66
66
66
66
66
66
69
69
69
69
69
68
69
68
68
68
68
75
76
76
77
76
45
45
88
88
78
78
92
8
25
11
17
64
7, 8, 14, 30
71
40
20
67
72
28
28
30
61
60
57
53
32
87
87
50
49
82
52
53
41, 46
45
7
83
80
97
71
62
46
Article index
art.
Typ
Description
page
31896
31897
31910
31911
31914
31926
31929
31946
31947
31948
31949
31950
31953
31956
31959
31960
31972
31973
31974
31975
31989
31990
31991
31992
32004
32005
32012
32015
32039
32040
32045
32049
32050
32051
32052
32053
32054
32055
32056
32057
32058
32060
32061
32062
32063
32066
32067
32068
32070
32073
32074
32075
32076
32077
32082
32083
32084
32085
32086
32090
32091
32098
32099
32118
32119
40001
40003
40054
40055
40056
40100
ultraviolet flame detector
ultraviolet flame detector
glass for manual call point
demo software for visual detect
optical home detector
optical smoke detector, black
optical smoke detector, white
mounting plate
mounting plate
Stratos adapter 3/4" female to 25 mm male
Stratos 25 mm female to 3/4" male adapter
Stratos socket 3/4" to 25 mm female
Stratos HSSD-2 control module 19"
smoke detector test kit
detector base, bridged
Stratos flange nut
fire control panel shallow
fire control panel
language kit German
language kit English
fire control panel
fire control panel 19" rack mount
language kit German
language kit English
optical home detector
antenna for extended range
loop sounder, white
optical home detector
language kit German for a master panel in the BitBus network
language kit English for a master panel in the BitBus network
optical smoke detector
fire control panel 19" rack mount
Stratos ABS-socket 3/4" to 25 mm
multiple tone sounder, red
multiple tone sounder, red, IP 65
multiple tone sounder, white
multiple tone sounder, white, IP 65
base sounder
beacon
beacon IP 65
loop beacon, red
loopsounder kit
loopsounder base kit
sounder beacon combination, white
sounder beacon combination, white, IP 65
monitored module for 4 outputs
cover for base sounder
cover for base sounder
flush-mounting adapter white
extension module
in-/output module mini
infrared flame detector
aspiration smoke detector
ultraviolet/infrared flame detector
manual call point, ABS, red
detector base, bridged
detector base, bridged
detector relay base
detector relay base
loop beacon, orange
piezo buzzer for detectors
2-loop interface active
2-loop interface active, redundant
remote display- and control panel
remote display- and control panel
battery 12 V / 26 Ah
Extinguishing control modu
key for manual call point
testaerosol
battery 12 V / 7,2 Ah
beacon
FL 800/24V-K-N
FL 80/1A
HFM EG
VD DV
HD 3004 O silver
CT 3001 O black
CT 3001 O white
CP MP 3004
CP MP 3016
STR-R3/4"-25
STR-R26-3/4"
STR-RM5
HSSD-2 S 19"
SOLO 812
SDBB 3000
STR-CM
detect 3004 - shallow
detect 3004
LK 3004 D
LK 3004 GB
detect 3016
detect 3016-19"
LK 3016 D
LK 3016 GB
HD 3005 O silver
WGA 3200
LS 3300 W
HD 3005 O white
LK ABF D
LK ABF GB
PL 3200 O/K
detect 3004-19"
STR-RH
VTG-32-SB R
VTG-32-DB R
VTG-32-SB W
VTG-32-DB W
Verso 32 Tone
VXB-1-SB-WB-RL
VXB-1-DB-WB-RL
LB-3300-VXB-R
LS 3300 VLC
LS 3300 SBK
VTB-32-SB W
VTB-32-DB W
SC 4
AD R
AD W
DR45W
UBW 3311
AOM 3301
X 9800
ASD-01
Eye 20/20 L
SBDH-ABS-R
SDBB 3000 black
SDBB 3000 silver
DRB 3000 black
DRB 3000 silver
LB 3300 VXB O
Sockel Piezo
DLI 3240 P X1
DLI 3240 P X2-R
ABF
ABF 19"
B 12/ 26Ah
CP ETB X2l
HFM-SCH-M
TA300
B 12/ 7,2Ah
BE 24
73
73
55
31
81
40
40
10
16
67
67
67
63
96
43
69
5
4
6
6
12
13
13
13
81
60
83
81
24
24
36
6
67
85
86
85
86
86
89
89
84
83
84
90
90
18
84, 87
84, 87
46
56
58
74
65
75
54
43
43
44
44
85
44
8
14
24
25
22
17
55
97
24
89
101
www.detectomat.com
Terms & Conditions of Sale detectomat GmbH
1
General – Controlling Provisions
4
Delivery – Delayed Acceptance – Delayed Delivery
1.
No terms and conditions other than our Terms and Conditions of Sale
contained herein shall apply unless expressly approved in writing by us.
Our Terms and Conditions of Sale shall also apply in the event we make
delivery to the customer without objection although aware of the existence of terms and conditions of the customer that differ from our Terms
and Conditions of Sale.
All agreements made between us and the customer in connection with
the execution of this agreement are contained herein in writing. This
agreement may not be altered, supplemented or amended unless agreed
to in writing.
Our Terms and Conditions of Sale shall apply to transactions with businessmen (“Unternehmer”) in the sense of Section 14 German Civil Code,
legal entities and public institutions.
Our Terms and Conditions of Sale shall also apply to all present and
future commercial relations with the customer.
1.
Delivery dates are subject to timely receipt by us of all documentation to
be supplied by the customer, required permits and approvals, including
but not necessarily limited to plans, and are also subject to performance
of other obligations by the customer. If these conditions are not fulfilled
in due time, delivery shall be delayed accordingly. This shall not apply in
the event of delays for which we are responsible.
Our obligation to make delivery is contingent upon timely and proper
performance of the customer’s obligations. We reserve the right at our
option to consider failure to perform (Section 320 German Civil Code - BGB)
and impairment of performance (Section 321 German Civil Code - BGB)
as events of default.
We may make partial delivery if no undue convenience is caused to the
customer.
In the event delivery or shipment is delayed by the customer by more
than one month from the date of announcement to the effect that the
merchandise is ready for delivery or shipment, we may invoice the
customer for storage charges in the amount of 0.5% of the price of the
respective merchandise per month or any fraction thereof, in which case
such charges may not exceed a total of 5%. The parties to the agreement may claim higher or lower storage costs if any difference can be
documented.
In the event the customer delays acceptance or fails to perform other
obligations, we may at our option claim reimbursement for any related
damages sustained by us, including but not necessarily limited to
reimbursement for additional expenses, without prejudice to further
claims.
In the event of a situation pursuant to Section 5 above, risk of loss or
damage shall pass to the customer upon the occurrence of any such
dlay or default on the part of the latter.
All acts of God (e.g. mobilization, war, insurrection, strikes, lockout or
similar events) beyond our control shall release us from performance of
our contractual obligations for the duration of any such occurrences. We
will immediately inform the customer of our inability to perform our
obligations under the agreement and promptly refund to the customer
any corresponding payment received by us . In the event the duration of
such an occurrence exceeds a period of three months, we may cancel
the agreement.
In the event delivery is delayed by us, our liability is limited to that
prescribed by law if the underlying purchase agreement specifies a firm
delivery date in the sense of Section 286 (2) 4 German Civil Code (BGB)
or Section 376 German Commercial Code (HGB) pertaining to non-fulfillment. We are also liable as prescribed by law in the sense that the
customer may claim that it is no longer interested in further performance
due to a delay in delivery caused by us.
We are also liable as prescribed by law for any delivery delay due to
breach of the agreement due to willful or gross negligence. We assume
responsibility for acts of negligence on the part of our representatives or
agents. In the event the delivery delay is not due to breach of the agreement through willful negligence by us, our liability is limited to claims for
damage that normally could have been anticipated.
We are also liable as prescribed by law in the event delivery is delayed
through breach of a material obligation under the agreement through
negligence. In such cases, however, liability is limited to claims for
damages normally could have been anticipated.
In addition, we are liable for a flatrate penalty for delayed delivery in the
amount of 0.5% of the price of the respective merchandise per entire
week, which penalty may, however, not exceed a total of 5%.
Any other legal rights and remedies the customer may have shall remain
in effect.
2.
3.
4.
2
Acceptance of Orders
1.
Our offers are subject to change. We reserve the right to make reasonable technical changes or changes in design, color and/or weight.
In the case of orders pursuant to Section 145 German Civil Code (BGB),
we may at our option accept such orders within 2 weeks of receipt.
Unless specified otherwise in these Terms and Conditions of Sale or in
our written confirmation, the INCOTERMS shall apply in the version
effective as of the date of this agreement.
Delivery is contingent upon correct and timely delivery of necessary
materials or merchandise to us (“Obtaining supplies oneself clause”). We
will inform the customer without delay in the event of non-availability and
promptly refund any payment received.
All rights to illustrations, drawings, calculations and other documents
shall remain our property. This shall also apply to any written materials
designated as “confidential”. The customer shall obtain our express
approval in writing before making any such materials available to other
parties.
2.
3.
4.
5.
3
Prices – Terms of Payment
1.
Unless specified otherwise in our written confirmation, our prices are “ex
works“ (exw) and exclusive of packing, which will be invoiced separately.
We reserve the right to modify our prices accordingly in the event of
increases or decreases in costs, including but not necessarily limited to
increases or decreases due to wage agreements or changes in the
prices of materials. We will document any such changes at the customer’s request.
In the event delivery is to be made more than four months from the date
of acceptance of the order or cannot be made earlier for reasons for
which the customer is exclusively responsible, we reserve the right to
invoice the appropriate price as of the date of delivery instead of the
original price agreed upon.
Our prices are exclusive of applicable value added tax (VAT). Applicable
value added tax will be included separately in the invoice on the billing
day.
Unless specified otherwise in our written confirmation, the customer
shall pay the net purchase price (with no deductions) within 10 days of
receipt of the invoice, at which time the invoice shall become due and
payable. Legal remedies shall apply in the case of past due accounts.
The customer may offset amounts due to the customer only if the
corresponding counterclaims are unappealable or undisputed or recognized by us. In addition, the customer may exercise the right to withhold
payment only in the case of counterclaims in connection with the same
transaction.
2.
3.
4.
5.
6.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
102
www.detectomat.com
Terms & Conditions of Sale detectomat GmbH
5
Cancellation
1.
The customer may cancel the agreement as allowed by law only in the
event of culpable default by us. However, in the case of defects (Section
7 below), legal remedies shall apply.
The customer shall in the event of default by us inform us within a
reasonable period after being asked to do so by us whether it intends to
cancel the agreement due to the event of the default or whether it insists
upon delivery.
2.
6
Transfer of Risk of Loss or Damage
1.
Unless specified otherwise in our written confirmation, our prices are understood to be “ex works“ (exw).
We reserve the right to ship merchandise from locations other than the
place of delivery. At the request of the customer, we will have the merchandise insured during transport, in which case the customer shall bear the
corresponding costs.
2.
7
Claims for defects
1.
Claims for defects may not be made in the event of insignificant deviations from the agreed upon characteristics, insignificant impairment of
functionality, normal wear and tear or damage resulting from improper or
negligent treatment after risk of loss or damage passes to the customer,
excessive use, unsuitable operating consumables, improper site preparation or unusual external factors not provided for in the agreement or in
the event of intermittent software problems. In the event of improper
modifications or maintenance by the customer, we can assume no
responsibility for such modifications or maintenance or the ramifications
thereof.
The customer’s rights in the case of a defect are dependent upon proper
inspection and notification in compliance with Section 377 German
Commercial Code (HGB). Notification of defects must be made in writing.
The customer shall bear the burden of proof in connection with all such
claims, including but not necessarily limited to proof of the existence of
the defect, the time of occurrence of the defect and timely notification of
the defect.
In the event of notification of a defect, the customer may withhold
payment only in a reasonable amount with respect to the extent of the
defect. The customer may not refuse to accept delivery in the event of
insignificant defects.
In the event of a defect, we may at our option repair the defective
merchandise or deliver new merchandise free of defects to replace the
original merchandise.
In the event the repair is unsuccessful, the customer may at its option
cancel the agreement or request a reduction in price. In the event of
negligible defaults, including but not necessarily limited to negligible
defects, the customer may not cancel the agreement.
We are liable as prescribed by law for claims made by the customer
based on willful or gross negligence on the part of our representatives or
agents. In cases other than intentional breach of the agreement, our
liability for damages is limited to claims for damages that normally could
have been anticipated.
We are liable as prescribed by law in the event we commit a material
breach of the agreement. In such cases, however, our liability for
damages is limited to claims for damages that normally could have been
anticipated.
We assume liability for injury to the life, body or health through
negligence on our part. This also applies to compulsory liability pursuant
to product liability legislation (“Produkthaftungsgesetz”).
Any other form of liability not specified above is excluded.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Claims for defects must be reported within 12 months. In the event the
newly manufactured product is a structure or is on the basis of its
normal function used for a structure and has caused a defect in such a
structure, an exception will be made and the period for reporting claims
will be extended to 36 months. Our legal liability pursuant to Sections 6
and 8 and in the case of willful deceit shall not be affected.
The period for reporting claims pursuant to Sections 478 and 479
German Civil Code (BGB) shall not be affected and shall extend for a
period of five years from the date of delivery of the defective item.
Recourse against us pursuant to Section 478 German Civil Code – BGB
– (recourse of customer) is only possible in the event the customer has
not made any agreement with its customer that goes beyond legal
liability for defects.
8
General Liability
1.
Liability for damages other than that provided for in Section 7 is excluded, regardless of the legal nature of the claim, including but not
necessarily limited to claims for damages due to negligence in connection with the acceptance of the order, other breaches of obligations or
claims for damages to property pursuant to Section 823 German Civil
Code (BGB).
The exclusion pursuant to Section 8.1 above also applies in the event
the customer claims reimbursement for needlessly incurred expenses
instead of damages.
Insofar as liability for damages is excluded or limited, this shall also apply
to claims for damages against our employees, representatives and
agents.
2.
3.
9
Usage of software and firmware – industrial property rights
1.
The customer has the non-exclusive right to use the standard software
and firmware, with the agreed performance characteristics, in an
unmodified form and within the agreed devices. The customer may make
a backup copy of the standard software without the need for an express
agreement.
The goods supplied by us are subject to industrial property rights (e.g.
patent rights, trademark rights and ownership rights). The customer
shall, in the case of applying or using the goods, respect our industrial
property rights, as well as the industrial property rights of third parties.
2.
10
Retention of Title
1.
We retain title to the merchandise until all payments from business with
the customer are made in full. In the event the customer has an account
with us, our reservation of title also applies to any acknowledged
outstanding balance, and the same applies in the event a balance is not
acknowledged and a “balance is made for cause”, for example, in the
event of bankruptcy or insolvency by the customer.
In the event of breach of this agreement by the customer, including but
not necessarily limited to failure to make payment when due, we may
retake possession of the merchandise sold without canceling the agreement beforehand. The customer hereby agrees to allow us to enter its
business premises during normal business hours to retake possession of
the items in question in any such situation. After retaking possession of
the items sold, we may dispose of them and credit the proceeds, less
appropriate disposal costs, to the outstanding balance due us.
The customer shall take proper care of the merchandise and shall have
the merchandise adequately insured at new value at its own expense
against fire damage, flood damage and theft. In the event maintenance
and inspections are necessary, the customer shall have such work
caried out on a timely basis at its own expense.
2.
3.
103
www.detectomat.com
Terms & Conditions of Sale and references detectomat GmbH
4.
5.
6.
7.
8.
9.
10.
11
In the event of attachment or any other such proceeding initiated by
third parties, the customer shall inform us in writing so that we can
take action pursuant to Section 771 Code of Civil Procedure (ZPO). In
the event any such third party is not in a position to reimburse us for
legal and extrale-gal expenses resulting from such an action pursuant
to Section 771 Code of Civil Procedure (ZPO), the customer shall bear
any such expenses.
The customer may resell the merchandise in the normal course of its
business. However, the customer shall assign the full invoiced amount
(including VAT) due from its customer or other parties from the sale to
the outstanding balance due to us; and this condition shall apply whether
or not the merchandise purchased from us is sold without or after
processing. The customer shall remain authorized to collect the
amount due after assignment to us. Our right to make collection
ourselves remains unaffected. However, we agree to refrain from
making collection as long as the customer applies the proceeds from
the sale to meet its payment obligations toward us, is not in arrears
and, in particular, no insolvency proceeds have been opened against
the customer and the customer has not suspended payment. In any
such event, we may demand that the customer make known to us the
assigned receivables and the corresponding debtors, provide all information required for collection, make available the corresponding
documents and inform the debtors (third parties) of the assignment.
The processing or modification by the customer of the merchandise is
in all cases performed for us. In the event the merchandise is processed with other objects that are not our property, we acquire partial
ownership of the object in proportion to the value of the merchandise
(total invoice amount, including VAT) as compared with that of the
other processed objects at the time of the processing. In addition, the
same reservation of title that applies for the merchandise also applies
for the object that results from the processing.
In the event the merchandise is inextricably combined with objects
that are not our property, we acquire partial ownership of the new
object in proportion to the value of the merchandise (total invoice
amount, includ-ing VAT) as compared with that of the other combined
objects at the time they are combined. In the event the combination is
such that the property of the customer is to be considered the main
product, it is agreed that the customer shall transfer proportionate
ownership rights to us. The cutomer shall then hold the resultant sole
or partial property for us.
The customer shall also assign to us those amounts due from third
parties as a result of the attachment of the merchandise to real estate property to secure amounts due to us.
In the event the reservation of title or assignment is not effective in the
jurisdiction in which the object is located, it is agreed that the security
corresponding to reservation of title or assignment in that jurisdiction
shall obtain. If the creation of this security requires actions on the part
of the customer, the latter shall at our request take any and all
measures required to create and maintain such rights at its own
expense.
We agree to release securities in our favor at the request of the customer in the event the realizable value of sure securities exceeds the
value of the secured amounts due by more than 10%. We may determine at our own discretion which securities to release.
12 Venue – Place of Delivery – Governing Law
Support and Assistance
President:
If, in addition to supplying merchandise, we also provide the customer
with support and/or assistance with the installation/start-up of the
merchandise, the limitation of liability described in Sections 7 and 8
shall apply accordingly.
Dipl.-Ing. Eduard J. Job
1.
2.
3.
4.
This agreement shall be subject to the exclusive jurisdiction of the
courts of our principal place of business in the event the customer is
a businessman in the sense of Section 14 German Civil Code (BGB), a
legal entity or a public institution. We may, however, file suit against
the customer before the courts of the customer’s principal place of
business.
In the event the customer is a businessman in the sense of Section 14
German Civil Code (BGB), a legal entity or a public institution and nothing is specified to the contrary in our written confirmation, our principal place of business shall be the place of delivery.
This agreement shall be governed by the laws of the Federal Republic
of Germany. Application of the United Nations Convention on Contracts for
the International Sale of Goods (1980) – CISG – is expressly excluded.
In the event of differences of opinion arising from these Terms and
Conditions of Sale or in the case of doubt, the original German-language
version and it alone shall be legal and binding.
Terms & Conditions of Sale detectomat GmbH, revised 15. August 2006
Technical Modifications
Due to continuous development of our products, together with altering
manufacturing methods, the descriptions and data provided are for information only and subject to changes without notice.
Information given in the catalogue
We accept no responsibility for the accuracy of the information and prices
given in the catalogue. Our prices are exclusive of applicable value added tax
(VAT). Applicable value added tax will be included separately in the invoice on
the billing day.
Updates you will find at www.detectomat.com
detectomat GmbH
An der Strusbek 5, 22926 Ahrensburg, Germany
Amtsgericht Lübeck, HR B 4645 AH
CFO:
Dipl.-Ing. Bodo Müller
104
www.detectomat.com
detectomat GmbH
An der Strusbek 5
D-22926 Ahrensburg
Germany
detectomat GmbH
Werk Bielefeld
Elpke 106–108
D-33605 Bielefeld, Germany
JOB GmbH
Kurt-Fischer-Straße 30
D-22926 Ahrensburg
Germany
Tel.: +49 (0) 4102 – 2114 – 60
Tel.: +49 (0) 521 – 924 31 – 0
Tel.: +49 (0) 4102 – 2114 – 0
Fax: +49 (0) 4102 – 2114 – 670
Fax: +49 (0) 521 – 924 31 – 50
Fax: +49 (0) 4102 – 2114 – 70
E-Mail: [email protected]
E-Mail: [email protected]
E-Mail: [email protected]
Web: www.detectomat.com
Web: www.detectomat.com
Web: www.Job-Bulbs.com
The
Group
www.detectomat.com

Benzer belgeler

Discovery Datasheet 2006.qxp

Discovery Datasheet 2006.qxp the maximum number of loop devices/components and mix

Detaylı

conventional wisdom

conventional wisdom 2 slots for fire brigade and network interface 128 programmable detector zones up to 4 x 126 loop3000 components up to 16 inputs for conventional detector zones maximum loop length 3.000 m (using i...

Detaylı