MKC-03_04_A4946 Rev.1_A4947_rev_2_PK28.FH9

Transkript

MKC-03_04_A4946 Rev.1_A4947_rev_2_PK28.FH9
MOTOR (FAZ) KORUMA ve FAZ SIRASI RÖLELERÝ
MKC-03A, MKC-03L, MKC-04A
Genel
Sanayi tesislerimizde yayg›n olarak kullan›lan elektrik motorlar›n›n iki faza kalarak
aþ›r› ›s›nmas› ve yanmas› s›kça karþ›laþ›lan ar›za kaynaklar›ndan biridir. Motor
korumas›nda s›kça kullan›lan “termikmanyetik röle” gerek elektro-mekanik yap›s›,
gerekse demeraj ak›m›n›n karþ›lanabilmesi için ak›m ayar›n›n yüksek tutulmas›
nedeniyle, koruma iþleminde yetersiz kalmaktad›r.
Bu olumsuz etkileri ortadan kald›racak þekilde tasarlanm›þ olan “nötr’lü MKC 03A
ve “nötr’süz MKC-04A” Motor Koruma Röleleri aþa¤›daki koruma fonksiyonlar›n›
yerine getirir.
Baðlantý þemalarý Tip PK-25
(0.5 A, 125 V AC)
NC C NO
1 2 3
A1
1 2 3
T1
MKC-04A
Stop
MKC-03L
1- Gerilim Dengesizli¤i (Ayarlanamaz)
C1
Faz-Nötr aras› gerilim dengesizli¤i (sabit) %15’tan fazla oldu¤u anda ç›k›þ rölesi
motoru devreden ç›kart›r. Özel istek üzerine %5-%15 arasý sabit gerilim dengesizliðine
sahip cihazlar üretilebilir.
Üç fazlý sistemlerde gerilim dengesizliði (asimetri);
Yüklerin fazlara dengesiz baðlanmasý sonucu oluþabileceði gibi,
Üç fazlý motorlarda fazlardan birinin kesilmesi durumunda da oluþur. Bu durumda
kesilen faza ait motor sargý ucunda, motorun diðer sargýlarý üzerinden indüklenerek
dönen gerilim görülür. Bu gerilim deðeri motorun cinsine ve yük durumuna göre
deðiþir.
Start
T1
L1
A2 L1
Un
L2
N
L3
L1
A1
A2
L2
M
3~
L3
Sistem
L2
L3
1 2 3
T1
VL31
VL12
V’L31 - V’L12
VRef
x 100
MKC-03A
Stop
VRef = 380 VAC
V’L31
V’L12
VL23
L3
L1
Vin (L-L)
Faz yokluðu veya herhangi bir sebepten oluþabilecek faz-nötr arasý gerilim
dengesizliði cihaz için belirlenen asimetri deðerinden küçükse çýkýþ rölesi çekilidir.
Eðer gerilim dengesizliði cihazýn asimetri deðerini aþarsa çýkýþ rölesi býrakýr ve motor
devre dýþý kalýr.
Uygulamalarýnýzda; motorun iki faza kalmasý esnasýnda motorun diðer sargýlarýndan
indüklenen gerilim deðerini de göz önünde bulundurarak uygun cihazý kullanýnýz.
Asimetri % =
L2
C1
Start
T1
C1
N L1
L2
L3
N
L1
Gerilim dengesizli¤i motor sarg› s›cakl›¤›n›n belli bir miktar artmas›na ve dolay›s›yle
motor gücünün düþmesine neden olur.
2. Faz s›ras›
Faz s›ras›n›n ters oldu¤u durumlarda (yani L1, L2, L3, saat yönünde de¤il ise) motor
devreye al›nmaz. Herhangi bir nedenle faz s›ras› bozulursa motor gecikmesiz olarak
devreden ç›kar›l›r.
L2
M
L3
3~
N
Tip PK-28
1 2 3
Fonksiyon Diyagram›
Sabit Dengesizlik De¤eri
Histerisis
T1
C1
Start
Yukarýdaki önlemlerin uygulanmamasý sonucu doðabilecek
istenmeyen durumlardan üretici firma hiç bir þekilde sorumlu
tutulamaz.
Boyutlar
48 mm
34 mm
L2
M
L3
3~
L3
3~
32 mm
48 mm
: Lütfen cihaz etiketlerine bakýnýz.
: 3 faz ve nötr 220-230 VAC
4 kablo y›ld›z ba¤lant› (MKC-03A)
: 3 faz 380 VAC
3 kablo üçgen ba¤lant› (MKC-04A, MKC-03L)
: 3 faz 220 V AC
3 kablo üçgen baðlantý (MKC-04A)
Yardýmcý Besleme Gerilimi : 190-260 V AC (MKC-03L)
Ýþletme Aralýðý
: (0.9-1.1) x Un
Ýþletme Frekansý
: 50/60 Hz.
Kontak Tipi
:1 C/O, 8A, 250 V AC, 2000 VA, Cosj=1
1 C/O, 0.5A, 125 V AC, 62.5 VA, Cosj=1 (MKC-03L)
Uyarý Iþýklarý
: ON Iþýðý: Besleme gerilimi varsa yanar
(MKC-03A, MKC-03L, MKC-04A)
OUT Iþýðý: Röle çekili iken yanar. Röle býraktýðý zaman
(hata durumunda) söner.
Gecikme Zamaný
: 0.2 sn
Ortam Sýcaklýðý
: -5 °C ; +50 °C
Koruma Sýnýfý
: IP 20
Boyutlar
: Tip PK 25 (MKC-03A, MKC-03L, MKC-04A)
Tip PK 28 (MKC-03A, MKC-04A)
Baðlantý Þekli
: Pano içine dikey veya klemens ray›na.
Aðýrlýk
: 0.2 kg.
Klemens Kablo Kesitleri
: (PK-28 için)
4mm² (12AWG) stranded/örgülü rijit kablo
6mm² (10AWG) solid/som iletken kablo
2x2.5mm² (14AWG) solid/som iletken kablo
(PK-25 için)
4mm² (12AWG) solid/som iletken kablo
2,5mm² (14AWG) stranded/örgülü rijit kablo
2x1,5mm2 (2x16AWG) solid/som iletken kablo
45 mm
62 mm
TiP PK25
90 mm
35 mm
61.8 mm
58 mm
45.4 mm
M
Ýþletme Gerilimi (Un)
Güvenli Kullaným ve Kurulum Ýçin Uyarýlar
90 mm
N
L1
L2
N
Aþaðýdaki talimatlara uyulmamasý halinde yaralanma veya ölümle
sonuçlanabilecek durumlar ortaya çýkabilir.
Cihaz üzerindeki herhangi bir iþlemden önce tüm besleme gerilimlerini
kesiniz.
Cihaz þebekeye baðlý iken ön paneli çýkarmayýnýz.
Cihazý solvent veya benzeri maddelerle temizlemeyiniz. Cihazý temizlemek
için sadece kuru bez kullanýnýz.
Cihazý çalýþtýrmadan önce baðlantýlarýnýn doðru olduðunu kontrol ediniz.
Cihazý panoya monte ediniz.
Cihazýnýzdaki herhangi bir sorunda yetkili satýcýnýzla temas kurunuz.
35.3 mm
T1
C1
L1 L2 L3
Teknik Bilgi
TD = Zaman Gecikmesi
36 mm
C1
Start
N
Yanl›þ Faz S›ras›
Ǜk›þ Rölesi
59.7 mm
T1
C1
N L1 L2 L3
L1
L3
TiP PK28
MKC-04A
Stop
L2
TD
T1
MKC-03A
Stop
L1
TD
1 2 3
35 mm
“Bu ürün, 30.05.2008 tarih ve 26891 sayýlý resmi gazetede yayýnlanan
EEE Yönetmeliðinin Madde 2 ve Ek-1A madde 9 kapsamýndadýr.”
A4946 / Rev.2
PHASE FAILURE and PHASE SEQUENCE DEVICES
MKC-03A, MKC-03L, MKC-04A
Connection Diagrams PK-25
General
One of the common faults faced in industrial plants is over-heating and burning of
3 phase motors due to the phase failure. “Thermic-magnetic device” which is an
essential element in motor protection is generally too slow due to both its electromechanical structure and the use of high current setting range to assure demarrage
without tripping. Being designed to eliminate the above disadvantages, MKC-03A
(with neutral connection ), MKC-04A (without neutral connection) Phase Failure
Devices react within 0.2 seconds (fixed) against the following faults and take the
motor out of service.
(0.5 A, 125 V AC)
NC C NO
1 2 3
A1
1 2 3
T1
MKC-04A
Stop
MKC-03L
C1
Start
1. Voltage Unbalance (Not Adjustable)
MK-04 includes no neutral connection.
When the neutral-phase voltage unbalance is greater than 40% (fixed), the output
relay is activated and switched OFF the motor. Devices that have fixed voltage
unbalance between 5%-15% can be producted for special order.
Unbalanced voltage may occured when;
The mains are loaded with unbalanced distribution,
One of the 3-phase of motor has lost. In this case, some amount of voltage which
produced by other phases will be inducted on the lost phase. Amount of this value
depends on both the motor type and amount of load.
Output relay is activated when a phase has lost or an unbalanced phase-neutral
value, which is occured with any reason, is smaller than the Asymetrical value which
is defined for the device. If this unbalanced voltage exceeds the adjusted Asymetrical
value, output will release itself and motor will be Switched-off.
In Applications; a proper device must be used regarding to the inducted voltage
value in two-phase which are remained after the other one has lost.
T1
L1
A2 L1
Un
L2
L2
L3
N
L3
L1
A1
A2
L2
M
3~
L3
System
L1
Vin (L-L)
L2
L3
1
T1
2
3
MKC-03A
Stop
asymmetry % =
VL31
VL12
-
x 100
VRef
C1
Start
L1
L2
L1
The voltage asymmetry causes the rise in motor temperature and a reduction of
the rated motor power.
2. Phase Sequence
When the phase sequence is correct (L1, L2, L3 in clockwise direction) the output
relay is activated; however, if the sequence is changed by any reason, the output
relay switches OFF immediately.
L2
M
L3
3~
N
Connection Diagrams PK-28
1 2 3
Function Diagram
1 2 3
T1
Fixed unbalance value
Hysterisis
T1
Stop
MKC-04A
MKC-03A
Stop
C1
L1
T1
Start
N
L1
L1
L2
Wrong Phase sequence
M
3~
L3
Sistem
Output Relay
TD = Tripping time
L2
M
L3
3~
N
Technical Data
Rated Voltage (Un)
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Failure to follow those instructions will result in death or serious injury.
Disconnect all power before working on equipment.
When the device is connected to the network, do not remove the front panel.
Do not try to clean the device with solvent or the like. Only clean the device
with a dried cloth.
Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by your compedent seller.
Mount device to the panel.
No responsibility is assured by the manufacturer or any of its subsidiaries
for any consequences arising out of the use of this material.
Dimensions
48 mm
32 mm
59.7 mm
36 mm
45 mm
62 mm
TYPE PK25
90 mm
35 mm
61.8 mm
TYPE PK28
58 mm
45.4 mm
90 mm
35.3 mm
34 mm
T1
C1
N L1 L2 L3
N
L3
TD
C1
Start
L1 L2 L3
L2
TD
L3
N
VRef = 380 VAC
V’L31
V’L12
VL23
T1
C1
N
: Please look at labels on the device.
: 3 phase and neutral 220-230 VAC
4 wire star connection (for MK-03/03P, MKC-03/03A/03P)
: 3 phase 380 VAC
3 wire delta connection (for MK-04/04P, MKC-04/04A/04P, MKC-03L)
: 3 phase 220 V AC
3 wire delta connection (for MKC-04/04P)
Auxiliary Supply Voltage : 190-260 V AC (for only MKC-03L)
Operating Range
: (0.9-1.1) x Un
Rated Frequency
: 50/60 Hz
Output Contacts
: 1 C/O with 8A, 250 VAC, 2000 VA, Cosj=1
1 C/O with 0.5A, 125 V AC, 62.5 VA, Cosj=1 (for only MKC-03L)
Warning LEDs
: LED Output, normally ON (OFF for any fault)
*LED PTC turns ON when motor winding temperature exceeds 110 oC
Tripping Time
: 0.2 s
Ambient Temperature :-5 °C to +50 °C
Protection Class
: IP 20
Dimensions
: Type PK 25 (MKC-03A, MKC-03L, MKC-04A)
Type PK 28 (MKC-03A, MKC-04A)
Installation
: Surface mounting or on the
mounting rails
Weight
: 0.2 kg
Terminal Cable Crosssections: (for PK-28)
4mm² (12AWG) solid conductor
6mm² (10AWG) stranded rigid conductor
2x2.5mm² (14AWG) solid conductor
35 mm
48 mm
A4946 / Rev.2
(for PK-25)
4mm² (12AWG) solid conductor
2,5mm² (14AWG) stranded rigid conductor
2x1,5mm² (2x16AWG) solid conductor
PHASE FAILURE and PHASE SEQUENCE DEVICES
MKC-03A, MKC-03L, MKC-04A
Connection Diagrams PK-25
General
One of the common faults faced in industrial plants is over-heating and burning of
3 phase motors due to the phase failure. “Thermic-magnetic device” which is an
essential element in motor protection is generally too slow due to both its electromechanical structure and the use of high current setting range to assure demarrage
without tripping. Being designed to eliminate the above disadvantages, MKC-03A
(with neutral connection ), MKC-04A (without neutral connection) Phase Failure
Devices react within 0.2 seconds (fixed) against the following faults and take the
motor out of service.
(0.5 A, 125 V AC)
NC C NO
1 2 3
A1
1 2 3
T1
MKC-04A
Stop
MKC-03L
C1
Start
1. Voltage Unbalance (Not Adjustable)
MK-04 includes no neutral connection.
When the neutral-phase voltage unbalance is greater than 40% (fixed), the output
relay is activated and switched OFF the motor. Devices that have fixed voltage
unbalance between 5%-15% can be producted for special order.
Unbalanced voltage may occured when;
The mains are loaded with unbalanced distribution,
One of the 3-phase of motor has lost. In this case, some amount of voltage which
produced by other phases will be inducted on the lost phase. Amount of this value
depends on both the motor type and amount of load.
Output relay is activated when a phase has lost or an unbalanced phase-neutral
value, which is occured with any reason, is smaller than the Asymetrical value which
is defined for the device. If this unbalanced voltage exceeds the adjusted Asymetrical
value, output will release itself and motor will be Switched-off.
In Applications; a proper device must be used regarding to the inducted voltage
value in two-phase which are remained after the other one has lost.
T1
L1
A2 L1
Un
L2
L2
L3
N
L3
L1
A1
A2
L2
M
3~
L3
System
L1
Vin (L-L)
L2
L3
1
T1
2
3
MKC-03A
Stop
asymmetry % =
VL31
VL12
-
x 100
VRef
C1
Start
L1
L2
L1
The voltage asymmetry causes the rise in motor temperature and a reduction of
the rated motor power.
2. Phase Sequence
When the phase sequence is correct (L1, L2, L3 in clockwise direction) the output
relay is activated; however, if the sequence is changed by any reason, the output
relay switches OFF immediately.
L2
M
L3
3~
N
Connection Diagrams PK-28
1 2 3
Function Diagram
1 2 3
T1
Fixed unbalance value
Hysterisis
T1
Stop
MKC-04A
MKC-03A
Stop
C1
L1
T1
Start
N
L1
L1
L2
Wrong Phase sequence
M
3~
L3
Sistem
Output Relay
TD = Tripping time
L2
M
L3
3~
N
Technical Data
Rated Voltage (Un)
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Failure to follow those instructions will result in death or serious injury.
Disconnect all power before working on equipment.
When the device is connected to the network, do not remove the front panel.
Do not try to clean the device with solvent or the like. Only clean the device
with a dried cloth.
Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by your compedent seller.
Mount device to the panel.
No responsibility is assured by the manufacturer or any of its subsidiaries
for any consequences arising out of the use of this material.
Dimensions
48 mm
32 mm
59.7 mm
36 mm
45 mm
62 mm
TYPE PK25
90 mm
35 mm
61.8 mm
TYPE PK28
58 mm
45.4 mm
90 mm
35.3 mm
34 mm
T1
C1
N L1 L2 L3
N
L3
TD
C1
Start
L1 L2 L3
L2
TD
L3
N
VRef = 380 VAC
V’L31
V’L12
VL23
T1
C1
N
: Please look at labels on the device.
: 3 phase and neutral 220-230 VAC
4 wire star connection (for MK-03/03P, MKC-03/03A/03P)
: 3 phase 380 VAC
3 wire delta connection (for MK-04/04P, MKC-04/04A/04P, MKC-03L)
: 3 phase 220 V AC
3 wire delta connection (for MKC-04/04P)
Auxiliary Supply Voltage : 190-260 V AC (for only MKC-03L)
Operating Range
: (0.9-1.1) x Un
Rated Frequency
: 50/60 Hz
Output Contacts
: 1 C/O with 8A, 250 VAC, 2000 VA, Cosj=1
1 C/O with 0.5A, 125 V AC, 62.5 VA, Cosj=1 (for only MKC-03L)
Warning LEDs
: LED Output, normally ON (OFF for any fault)
*LED PTC turns ON when motor winding temperature exceeds 110 oC
Tripping Time
: 0.2 s
Ambient Temperature :-5 °C to +50 °C
Protection Class
: IP 20
Dimensions
: Type PK 25 (MKC-03A, MKC-03L, MKC-04A)
Type PK 28 (MKC-03A, MKC-04A)
Installation
: Surface mounting or on the
mounting rails
Weight
: 0.2 kg
Terminal Cable Crosssections: (for PK-28)
4mm² (12AWG) solid conductor
6mm² (10AWG) stranded rigid conductor
2x2.5mm² (14AWG) solid conductor
35 mm
48 mm
A4947 / Rev.1
(for PK-25)
4mm² (12AWG) solid conductor
2,5mm² (14AWG) stranded rigid conductor
2x1,5mm² (2x16AWG) solid conductor

Benzer belgeler

motor (faz) koruma röleleri

motor (faz) koruma röleleri Cihazý solvent veya benzeri maddelerle temizlemeyiniz. Cihazý temizlemek için sadece kuru bez kullanýnýz. Cihazý çalýþtýrmadan önce baðlantýlarýnýn doðru olduðunu kontrol ediniz. Cihazý panoya mont...

Detaylı

GKRC-02, GKRC-02F, GKRC-03, GKRC-03F, GKRC

GKRC-02, GKRC-02F, GKRC-03, GKRC-03F, GKRC PRECAUTIONS FOR INSTALLATION AND SAFE USE Failure to follow those instructions will result in death or serious injury. Disconnect all power before working on equipment. When the device is connected...

Detaylı

MOTOR (FAZ) KORUMA ve FAZ SIRASI RÖLELERİ

MOTOR (FAZ) KORUMA ve FAZ SIRASI RÖLELERİ Faz-Nötr aras› gerilim dengesizli¤i (sabit) %40’tan fazla oldu¤u anda ç›k›þ rölesi

Detaylı

MKC05-05P - 06-06P - FR-02 TR EN A5049 R4.FH9

MKC05-05P - 06-06P - FR-02 TR EN A5049 R4.FH9 hala devam ediyorsa cihazýn rölesi býrakýlýr (OUT led’i söner ve Asm. Led'i yanar). Sistemdeki dengesizlik ayarlanan deðerin altýna düþtüðünde ise cihaz çekme gecikmesi (Reset Delay) kadar bekler v...

Detaylı

User Manual

User Manual PRECAUTIONS FOR INSTALLATION AND SAFE USE Failure to follow those instructions will result in death or serious injury. Disconnect all power before working on equipment. When the device is connected...

Detaylı

Genel Ürün Bilgi

Genel Ürün Bilgi O BTUS E ANGLE CURVES COURBES ANGLE OBTUS

Detaylı

İndir - Entes

İndir - Entes : 1 C/O with, 5A, 1250 VA, Cosj=1 (for MK-01P, type PK10) 1 C/O with, 8A, 2000 VA, Cosj=1

Detaylı

AŞIRI / DÜŞÜK AKIM KORUMA RÖLELERİ

AŞIRI / DÜŞÜK AKIM KORUMA RÖLELERİ PRECAUTIONS FOR INSTALLATION AND SAFE USE Failure to follow those instructions will result in death or serious injury. Disconnect all power before working on equipment. When the device is connected...

Detaylı