Reactive Power Controller
(For Electromechanical Energymeters)
Karaca
KARACA PAZARLAMA VE TİC. LTD. ŞTİ. :
Karadeniz Caddesi Kuyu Sokak No:30 A.Dudullu / İSTANBUL / TÜRKİYE
Tel: 0216 612 22 89 - 90 Fax: 0216 612 36 40
Web: www.krk.com.tr
User Guide
UG - 03/REV 00
17- Cosj: In Automatic mode, the value displayed is cosj value. In
Menu mode, it shows that Target Cosj parameter is selected to
adjust.
18- Menu: Shows that the controller is in Menu mode.
19- Auto : Shows that the controller is in Automatic mode.
20- Man. : Shows that the controller is in Manuel mode.
21: Shows that fan is started to cool the panel.
22: Shows that the Alarm output is turned on.
C- Using The Controller:
C9
1- Selecting operation mode: “Auto/Menu/Man” button is used for
selecting mode. If “Auto” lights, the controller is in automatic mode. If
”Menu” lights, the controller is in menu mode; if “Man” lights, the
controller is in manuel mode. In Automatic mode, the controller work
to reach adjusted target Cosj value. In Manuel mode, user can switch
the steps on/off manually. In Menu mode, user can make adjustments
of the controller.
2- Switching on/off the steps: When “
“ button is pressed, after 1
second, one step is switched on. In this time “Opr” lights. When “
“
button is pressed, after 1 second, one step is switched off. In this time
“Opr” lights.
3- Target Cosj adjustment: Menu mode is selected by
“Auto/Menu/Man” button. Target Cosj adjustment is selected by
Parameter button. Using ”
“ and “
“ buttons, target Cosj can
be adjusted. In 10 seconds if any button isn’t pressed, adjusted value
is written to the memory.
4- Over voltage adjustment: Menu mode is selected by
“Auto/Menu/Man” button. Voltage adjustment is selected by
Parameter button. Using ”
“ and “
“ buttons,over voltage can
be adjusted in 231-286V range. In 10 seconds, if any button is not
pressed, adjusted value is written to the memory.
L3 L2 L1 N
K1 L1
K2 L2
K3 L3
N
L1
L2
L3
6A
k3 I3 k2 I2 k1 I1
C5
C1
L1
1 2 3 4
L1
5 6 7 8
L1
9 10 11 12
F A
Fan Alarm
(L1) (L1)
System
Connection Scheme :
12
5
Notes :
A- General Specifications :
- KPC3F, compensates the system according to three phases’ reactive
power by measuring voltage and current from three phases.
- It compensates according to three system’s cosj value. It is
recommended that it is used for electromechanical energy meters. It
must be used with threephase capacitors.
- Measures three phases’ cosj, current and voltage values.
- Computes system’s cosj value.
- Operates according to first in first out (FIFO) principle.
- Target Cosj value can be adjusted to be inductive or capacitive.
- Capacitor switch-on time and switch-off time can be adjusted
individually.
- C/k value can be adjusted.
- It indicates Over Current and Over Voltage Alarms. Alarm outputs
can be activated by user in Menu mode.
- It indicates Under Current Alarm.
- It indicates Over and Under Compensation Alarms.
- It has a fan output to cool the panel and temperature value can be
adjusted. Fan can be made passive by user in Menu mode.
- Automatic set and easy installation.
2
KRK
15
KARACA
CCihazın Kullanılması:
5- Over current adjustment: Menu mode is selected by
“Auto/Menu/Man.” button. Current adjustment is selected by
1- Çalışma
modu
seçimi:
“Oto/Menü/Man”
tuşu
Parameter
button.
Using
“
“ and
“
“ buttons, over
current can be
adjusted
in 4-6A
range. In mod
10 seconds,
button
not pressed,
kullanılarak
istenilen
seçilir.if any
“Oto”
lediisyanıyorsa
adjusted value is written to the memory.
cihaz
otomatik moddadır. ”Menü” ledi yanıyorsa menü
6- C/k adjustment: Menu mode is selected by “Auto/Menu/Man”
modunda,
“Man” ledi
yanıyorsa
cihaz manuel
moddadır.
button. C/k adjustment
is selected
by Parameter
button. Using
“
“
and “
“ modda
buttons C/k
cancihaz
be adjusted
in 0,01-1,00
In 10
Otomatik
iken
ayarlanan
hedefrange.
Cosj
seconds, if any
button is çalışır.
not pressed,
adjusted
value ise
is written
to the
değerine
ulaşmaya
Manuel
modda
sisteme
memory.
kondansatör
alma çıkarma
işlemi
kullanıcı
tarafından
7- Switch-on time(ton)
adjustment:
Menu
mode is selected
by
yapılır.
Menü modunda
istenenisdeğerlerin
ayarı
“Auto/Menu/Man”
button. “ton”ise
adjustment
selected by Parameter
button. Using “
“ and “
“ buttons,switch-on time can be adjusted
yapılır.
in 2-60
seconds
range.kondansatörlerin
In 10 seconds, if any elle
button
is not pressed,
2Manuel
modda
kontrolü:
“
“
adjusted value is written to the memory.
tuşuna
her
basışta
bir
kademe
1sn
sonra
devreye
alınır.
8- Switch-off time(toff) adjustment: Menu mode is selected by
Bu
esnada “İşlem”
ledi
yanar.
“
tuşunabyher
“Auto/Menu/Man.”
button.
“toff”
adjustment
is “selected
Parameter
button. Using
“
“ and 1sn
“
“sonra
buttons,devreden
switch-off time
can beBu
basışta
bir kademe
çıkarılır.
adjusted in“İşlem”
2-60 seconds
range. In 10 seconds, if any button is not
esnada
ledi yanar.
pressed,adjusted value is written to the memory.
3Hedef Cosj
ayarı: “Oto/Menü/Man”
tuşu by
ile Menü
9- Temperature
adjustment:
Menu mode is selected
modu
seçilir. Parametre
tuşu ile adjustment
Cosj ayar
modu seçilir.
“Auto/Menu/Man.”
button. Temperature
is selected
by
“ kullanılarak
“ and “
“ buttons,
temperature can
”Parameter
“ vebutton.
“
“Using
tuşları
hedef Cosj
be adjusted in 30-65 C range. In 10 seconds, if any button is not
ayarlanır.
5 saniye
bir tuşa basılmaz
pressed, adjusted
valueboyunca
is written toherhangi
the memory.
ise
ayarlanan
değer
hafızaya
kaydedilir.
11- Displaying Cosj value: In Automatic mode, using “
“ and
Gerilim
“Oto/Menü/Man”
tuşubutton,
ile Menü
“4- Aşırı
“ buttons,
Cosjayarı:
parameter
is selected. By Phase
adjusted
phase’s
cosj value
or system’stuşu
cosjile
value
is displayed.
modu seçilir.
Parametre
Gerilim
ayar modu
12Displaying
In Automatic
mode, using
“
“ and
seçilir.
”
“Voltage
ve “ value:
“ tuşları
kullanılarak
231-286V
“
“ buttons, Voltage parameter is selected. By Phase button,
arası
aşırı
gerilim
ayarı
yapılır.
5
saniye
boyunca
adjusted phase’s voltage value is displayed.
Dimensions :
135mm
143mm
66mm
8mm
143mm
135mm
Back
Side
Front
herhangi bir tuşa basılmaz ise ayarlanan değer hafızaya
kaydedilir.
6
11
6- Auto/Menu/Man.: By this button, one of the Automatic, Menu and
Manuel modes can be selected.
7- Phase: In Automatic mode, it is used for selecting one of L1, L2
and L3 phases. Selected phase’s value is displayed.
Parameter: In Menu mode, it is used for selecting a parameter that
is wanted to be adjusted.
8: In Automatic mode, this button is used for selecting cosj,
voltage, current and temperature values. In Manuel mode, it is used
for switch off the step. In Menu mode, it is used for decreasing the
value displayed.
9: In Automatic mode, this button is used for selecting cosj,
voltage, current and temperature values. In Manuel mode is used for
switch on the step. In Menu mode, it used for increasing the value
displayed.
10- Opr.: It shows that the controller is in operation to compensate.
11- Over Vol.: In Automatic mode, shows Over Voltage Alarm.
Temp.: In Menu mode, shows that temperature parameter that is
needed to cool the panel is selected to adjust.
12- Low Cur.: In Automatic mode, shows Under Current Alarm.
toff: In Menu mode, shows that switch-on time is selected to
adjust.
13- Over Cur.: In Automatic mode, shows Over Current Alarm.
ton: In Menu mode, shows that switch-off time is selected to
adjust.
14- Temp.: In Automatic mode, temperature value inside the panel is
displayed.
C/k: In Menu mode, shows that C/k value is selected to adjust.
15- Current: In Automatic mode, the value displayed is Current value.
In Menu mode, it shows that Over Current parameter is selected to
adjust.
16- Voltage: In Automatic mode, the value displayed is Voltage value.
In Menu mode, it shows that Over Voltage parameter is selected to
adjust.
Installation of A Compensation System :
Example: There is a system that has Cosj=0,80 and 50kVA total
pwer. What are the total capacitor power that is needed and C/k
value?
Solution: If total power S=50kVA,
P=SxCosj=50x0,80=40kW
Cosj=0,80 value is reached to target Cosj=1,00 value by
using a multiplier that is taken from “Target Cosj Table”. Multiplier that
is taken from table is 0,75. Reactive power;
Q=PxMultiplier=40x0,75=30kVAr is found. System’s
reactive power before compensation, equals reactive power that is
reached with target cosj=1,00 value. Like in this example, system’s
reactive power is 30kVAr.
Current transformer ratio:
50kVA / (220x3) =75A it is selected as a near value to the
upper standart 100/5.
For 12 steps, if we think this way 1 2 2 2 2 2 2 2 2 2 2 2; in
total 23 electrical steps are obtained.
First step’s capacitor power 30kVAr / 23 = 1,3kVAr is found.
Nearest value 1,5kVAr or 1kVAr is selected. If we also think %20
tolerance, we choose 1kVAr.
1 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 5 5 5 = 36kVAr is found.
C/k= 1kVAr / (100/5) =0,05 is found. C/k value is selected 0,05 to
adjust.
4
G- Technical Specifications:
Supply Voltage
Power Consumption
Current Transformer
Current Meas. Range
Temperature Meas. Range
Control Output
Cosj Range
Step Delay
Switch-on time
Switch-off time
Over Current Alarm Range
Under Current Alarm
Over Voltage Alarm Range
Comp. Alarm Delay
Temperature Setting Range
Factory Set Values
: 220Vac±%20(L1-N), 50/60Hz
: <5VA
: .../5A
: 0,05..6A
: -10..100 °C
: Relay, 5A/250Vac(Resistive Load)
: 0,01..1,00
:
: 2..60sec. adj.(1sec. in Man. mode)
: 2..60sec. adj.(1sec. in Man. mode)
: 4..6A adj.
: <0,05A
: 231..286Vac adj.
: 60sec.
: 30..65 °C
: Cosj=1,00; C/k=0,05;
ton=10sec.; toff=3sec.;
O.Current Alarm=6A (Alarm ON);
O.Voltage Alarm=250V (Alarm ON);
Temperature=50 °C (Alarm ON)
Ambient Temperature
Display
Protection Class
: -5...+55 °C
: 3 Digits Red Display
: In Front: IP54
In Rear: IP20
: 0,90 kg
Weight
13
13- Displaying Current value: In Automatic mode, using “
“ and “
“ buttons, Current parameter is selected. By Phase button, adjusted
phase’s current value is displayed.
14- Displaying Temperature: In Automatic mode, using “
“ and
“
“ buttons, Temperature parameter is selected. Temperature
inside the panel is displayed.
D- Warnings and Explanations :
1- Over Current Alarm: If measured seconder current value of
current transformer is bigger than adjusted over current value, “Over
Cur.” lights. If over current alarm is active and this continues 60sec.,
the alarm is turned on.
2- Low Current Alarm: If measured seconder current value is lower
than 50mA, “Low Cur.” lights.
3- Over Voltage Alarm: If measured voltage value is bigger than
adjusted over voltage value, “Over Vol.” lights. If over voltage alarm is
active and this continues 60sec., the alarm is turned on.
4- Insufficient Compensation Alarm: If the controller switches on all
steps and it does not reach to system’s target cosj value, it lights
insufficient compensation alarm. If this continues 60sec., “
“
lights and the alarm is turned on.
5- Over Compensation Alarm: If the controller switches off all steps
and its cosj value is bigger than system’s target cosj value, it lights
over compensation alarm. If this continues 60sec., “
“ lights and
the alarm is turned on.
General Rules for Compensation
10
1- Current transformer that is connected reactive power controller
must have .../5A ratio.
2- After current and voltage connections of the controller is made
carefully according to connection scheme, Cosj and C/k values must
be adjusted according to system’s need.
3- Capacitor steps must be connected low to high order.
7
KRK
KARACA
CCihazın Kullanılması:
Notes :
B- Buttons and Lights :
1- Çalışma modu seçimi: “Oto/Menü/Man” tuşu
kullanılarak istenilen mod seçilir. “Oto” ledi yanıyorsa
cihaz otomatik moddadır. ”Menü” ledi yanıyorsa menü
modunda, “Man” ledi yanıyorsa cihaz manuel moddadır.
Otomatik modda iken cihaz ayarlanan hedef Cosj
değerine ulaşmaya çalışır. Manuel modda ise sisteme
kondansatör alma çıkarma işlemi kullanıcı tarafından
yapılır. Menü modunda ise istenen değerlerin ayarı
yapılır.
2- Manuel modda kondansatörlerin elle kontrolü: “
“
tuşuna her basışta bir kademe 1sn sonra devreye alınır.
Bu esnada “İşlem” ledi yanar. “
“ tuşuna her
basışta bir kademe 1sn sonra devreden çıkarılır. Bu
esnada “İşlem” ledi yanar.
3- Hedef Cosj ayarı: “Oto/Menü/Man” tuşu ile Menü
modu seçilir. Parametre tuşu ile Cosj ayar modu seçilir.
”
“ ve “
“ tuşları kullanılarak hedef Cosj
ayarlanır. 5 saniye boyunca herhangi bir tuşa basılmaz
ise ayarlanan değer hafızaya kaydedilir.
4- Aşırı Gerilim ayarı: “Oto/Menü/Man” tuşu ile Menü
modu seçilir. Parametre tuşu ile Gerilim ayar modu
seçilir. ”
“ ve “
“ tuşları kullanılarak 231-286V
arası aşırı gerilim ayarı yapılır. 5 saniye boyunca
herhangi bir tuşa basılmaz ise ayarlanan değer hafızaya
kaydedilir.
1
2
3
4
5
6
7
8
1
L1 L2
2
3
4
Auto
L3
Man
Menu
Cos
Ind.
Cap.
Reactive Power Controller
Compensation
Over
5
22
21
9 10 11 12
Cos
Voltage
Voltage
Current
Current
Temp.
C/k
Over Cur.
t on
Low Cur.
t off
Over Vol.
Temp.
Opr.
20
19
18
17
16
15
14
13
12
11
10
9
Normal
Insufficient
Auto/Menu / Man
Phase
8
Parameter
R
6
KPC3F-12
7
1- 1,2,3.....12: Shows the steps which capacitor is switched on.
2- L1, L2, L3: Shows the selected line. If all light, it shows system’s
cosj value.
3- Ind.: It shows that Cosj value displayed is inductive.
4- Cap.: It shows that Cosj value displayed is capacitve.
5- Compensation:
- Over: Shows Over Compensation Alarm.
- Normal: Shows that compensation is realized.
- Insufficient: Shows Under Compensation Alarm.
14
6
3- Capacitor steps must be connected low to high order.
4- When system is energized firstly, manuel mode is selected for
determining true direction of current inputs. Normally phases’
reactive loads are inductive. If the controller shows capacitive
reactive, current transformer output pins must be changed.
Warning: When loads is changed rapidly in a system, to shorten
switch on time causes shorter life for contactors and
condansators. So this is not recommended. In these systems, the
best solution is local or individual compensation.
Warning: No responsibility is assured by the manufacturer for
consequences resulting from wrong installation of this device
which is not consulted by the user guide.
F- Computing C/k Value:
C/k adjustment, determines least power that is wanted
to control. It equals first step’s capacitor power, divide by current
transformer ratio.
Example: There is a system which first step’s capacitor power is
1 kVAr. If current transformer ratio is 100/5, what is C/k value that
is needed to adjust?
Solution:
C/k = First step’s capacitor power / Current transformer ratio
C/k= 1kVAr / (100/5) =0,05 is found.
8
3
TARGET COSØ TABLE
Target CosØ
Existing
CosØ(Ind.)
0,40
0,42
0,44
0,46
0,48
0,50
0,52
0,54
0,56
0,58
0,60
0,62
0,64
0,66
0,68
0,70
0,72
0,74
0,76
0,78
0,80
0,82
0,84
0,86
0,88
0,90
0,92
0,94
0,96
0,98
0,80
1,54
1,41
1,29
1,18
1,08
0,98
0,98
0,81
0,73
0,66
0,58
0,52
0,45
0,39
0,33
0,27
0,21
0,16
0,11
0,05
-
0,85
1,67
1,54
1,42
1,31
1,21
1,11
1,03
0,94
0,86
0,78
0,71
0,65
0,58
0,52
0,46
0,40
0,34
0,29
0,23
0,18
0,13
0,08
0,03
-
0,90
1,81
1,68
1,56
1,45
1,34
1,25
1,16
1,08
1,00
0,92
0,85
0,78
0,72
0,66
0,59
0,54
0,48
0,43
0,37
0,32
0,27
0,21
0,16
0,11
0,06
-
0,95
1,96
1,83
1,71
1,60
1,56
1,40
1,31
1,23
1,15
1,08
1,01
0,94
0,87
0,81
0,75
0,69
0,64
0,58
0,53
0,47
0,42
0,37
0,32
0,26
0,21
0,16
0,10
0,04
-
1,00
2,29
2,16
2,04
1,93
1,89
1,73
1,64
1,56
1,48
1,41
1,33
1,27
1,20
1,14
1,08
1,02
0,96
0,91
0,86
0,80
0,75
0,70
0,65
0,59
0,54
0,48
0,43
0,36
0,29
0,20
(Cap.)
0,95
2,62
2,49
2,37
2,26
2,22
2,06
1,97
1,89
1,81
1,74
1,65
1,60
1,53
1,47
1,41
1,35
1,28
1,24
1,19
1,13
1,08
1,03
0,98
0,92
0,87
0,80
0,76
0,68
0,61
0,52
9