SWL1850 Data Sheet

Transkript

SWL1850 Data Sheet
Data Sheet
SWL SERIES - SWL1850
SWL Valve Regulated
Lead-Acid Batteries (VRLA)
The SWL range is an enhanced NPL design resulting
in an improved energy to density ratio, giving up to
40% extra discharge capacity. All other attributes and
operational characteristics are the same, thereby
maintaining the benefit of a common mechanical and
electrical design for users of both products.
General Specifications
FEATURES
•
Yuasa VRLA batteries can be used in any orientation
excluding continuous use inverted.
Standard case material is flame retardant to (UL94) HBØ.
FR option case material is flame retardant to UL94:VØ
(oxygen index 30).
SWL batteries are manufactured in factories that comply
with ISO9001:2000.
FR option SWL’s comply with BS6290 Part 4 (1997).
SWL batteries comply with IEC 60896-21+22.
•
•
•
•
•
Layout
This battery must
never be installed
permanently suspended
by their handles
Specifications
1) Nominal Voltage
12
2) Nominal Wattage/Cell
10 min to 1.6V/Cell
5 min to 1.6V/Cell
3 min to 1.6V/Cell
319
453
536
3) Weight (Approx)/Kg
23.8
4) Energy Density (Wh/L)
88
5) Specific Energy
(Wh.kg) 10HR
39
6) Internal Resistance
(Approx)/mohm
4.4
7) Maximum (1 min)
discharge Current/A
500
8) Maximum Short Duration
(1 sec) Discharge Current
in Amperes
800
9) Operating Temperatures/°C
Charge
Discharge
10) Percentage Charge
Retention at 20°C
1 month
3 months
6 months
Terminals (mm)
Terminal
X
Y
20mm
M8
-15 to 50
-20 to 60
97
91
85
L
L
X
D
SWL1850
16
11) Standard Terminal
Type
Lead post
with brass insert
C
Y
12) Torque Nm
4.76
13) Case Material
ABS
Dimensions / mm
Length +/-1
Width +/-1
Height +/-2
SWL
350
166
174
Data Sheet
SWL SERIES - SWL1850
CHARGING CHARACTERISTICS
CHARGING CHARACTERISTICS
120
14.0
100
13.0
0.1
80
60
0.08
12.0
0.06
40
11.0
0.04
20
0.02
0
0
0
DISCHARGE CHARACTERISTIC CURVES
5
10
15
20
25
30
35
40
TEMPERATURE/LIFE CHARACTERISTIC
20
14.0
10
FLOATING VOLTAGE: 2.275 V/cell
DESIGNED LIFE (YEARS)
TERMINAL VOLTAGE (V)
13.0
12.0
11.0
0.2C
0.08C 0.05C
10.0
3C
5
1C 0.5C 0.3C
5C
9.0
8.0
0.010
0.5
0.100
1.000
10.000
100.000
1000.000
1000.000
20
DISCHARGE TIME (MIN)
30
40
50
60
TEMPERATURE (°C)
SELF DISCHARGE CHARACTERISTICS
Charging Methods (At 20°C)
Standby use: Float charging voltage 2.275vpc
CAUTION
- Avoid short circuit.
- Do not charge in a sealed container.
- Service life and operational characteristics will be
affected by temperature.
- AC Ripple reduces service life.
WARNING!
SWL (Standard) and (FR) battery types SWL1850;
SWL1850-6; SWL2500, must never be installed permanently suspended by their handles; they are not
designed for this purpose.
Yuasa Battery Corp.
Unit 22 Rassau Industrial Estate
Ebbw Vale, Gwent, NP23 5SD
Tel: 08708 506312 Fax: 08708 506317
Registered number 1548820
Cat. No.
NP7-12 February 07

Benzer belgeler

SWL 750 Data Sheet

SWL 750 Data Sheet FLOATING VOLTAGE: 2.275 V/cell DESIGNED LIFE (YEARS)

Detaylı

NPL65-12I Data Sheet

NPL65-12I Data Sheet resulting in a longer service life (7 - 10yrs). All other attributes and operational characteristics are the same, thereby maintaining the benefit of a common mechanical and electrical design for u...

Detaylı

NP38-12I Data Sheet

NP38-12I Data Sheet that when charging from fully discharged, the battery can draw an initial charge current of approximately 2cA. Care should therefore be taken to ensure that this initial charge current (if ungovern...

Detaylı

technical data sheet - Crown Batteries Europe

technical data sheet - Crown Batteries Europe Yuasa VRLA batteries can be used in any orientation excluding continuous use inverted. Standard case material is flame retardant to (UL94) HBØ. FR option case material is flame retardant to UL94:VØ...

Detaylı